CO Springs Fire | Original | A | 7/6/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | rpeterson | CO Springs Fire | 1708894 |
CO Springs Fire | Original | A | 7/6/2022 | CSFIRE | CSFIRE | Submitted By: Peterson, Roland Thomas ,Submitted By: Peterson, Roland Thomas (see full review) | csfdit | CO Springs Fire | 1708893 |
Construction | Original | A | 6/30/2022 | SHELLEY | SHELLEY | No apparent changes. | | Construction | 1706729 |
Enumeration | Original | A | 6/27/2022 | AMY | AMY | | | Enumeration | 1704316 |
Electronic Plan | Original | / | 6/27/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1704295 |
Resubmittal 4 | Original | / | 6/23/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #4 | | Resubmittal 4 | 1702905 |
CO Springs DRE | Original | A | 6/21/2022 | CJACKSON | CJACKSON | (see full review) | | CO Springs DRE | 1701399 |
CO Springs Fire | Original | A | 6/13/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1697578 |
Zoning/Planning | Original | / | 6/7/2022 | CJACKSON | CJACKSON | In Current Review by CJACKSON | | Zoning/Planning | 1693932 |
Zoning/Planning | Original | / | 6/6/2022 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1693498 |
Construction | Original | A | 6/3/2022 | DANM | DANM | | | Construction | 1692224 |
Electronic Plan | Original | / | 6/3/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1692211 |
Enumeration | Original | D | 6/2/2022 | AMY | AMY | The A-1 page showing the separation of space with addressing listed for each space was not included in this submittal. We need to see this sheet that shows the existing with the expansion of space with all addresses labeled. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1691116 |
Electronic Plan | Original | / | 6/2/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1691097 |
Enumeration | Original | / | 6/2/2022 | WEBSITE | WEBSITE | Overtime Authorized for Enumeration by BOb Stanley | Bob Stanley | Enumeration | 1691096 |
Resubmittal 3 | Original | / | 6/1/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #3 | | Resubmittal 3 | 1690983 |
CO Springs Fire | Original | D | 5/31/2022 | CSFIRE | CSFIRE | Submitted By: Trimble, James Charles WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1690050 |
Electrical | Original | A | 5/26/2022 | SHELBY | SHELBY | | | Electrical | 1689121 |
Electronic Plan | Original | / | 5/26/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1689118 |
CO Springs DRE | Original | D | 5/23/2022 | CJACKSON | CJACKSON | Please upload the approved development plan minor modification. (see full review) | | CO Springs DRE | 1686330 |
Zoning/Planning | Original | D | 5/23/2022 | CJACKSON | CJACKSON | Please upload the approved development plan minor modification. (see full review) | | Zoning/Planning | 1686304 |
Zoning/Planning | Original | / | 5/23/2022 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1686091 |
Construction | Original | D | 5/20/2022 | DANM | DANM | Sheet D101 and D102 are missing from the resubmittal - please resubmit.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1685913 |
Electronic Plan | Original | / | 5/20/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1685909 |
Electrical | Original | / | 5/20/2022 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by BOb Stanley | Bob Stanley | Electrical | 1685536 |
Construction | Original | / | 5/20/2022 | WEBSITE | WEBSITE | Overtime Authorized for Construction by BOb Stanley | Bob Stanley | Construction | 1685535 |
Enumeration | Original | N | 5/20/2022 | BRENT | BRENT | | | Enumeration | 1685534 |
Electronic Plan | Original | / | 5/20/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1685522 |
Resubmittal 2 | Original | / | 5/20/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #2 | | Resubmittal 2 | 1685452 |
Zoning/Planning | Original | / | 4/21/2022 | CJACKSON | CJACKSON | In Current Review by CJACKSON | | Zoning/Planning | 1669391 |
CO Springs Fire | Original | D | 4/21/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1668904 |
Electrical | Original | D | 4/11/2022 | SHELBY | SHELBY | A floor plan is required showing the location of the service and feeder over current devices. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1663503 |
Electronic Plan | Original | / | 4/11/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1663492 |
CO Springs DRE | Original | D | 4/6/2022 | ACOOPER | ACOOPER | Comment remains (see full review) | | CO Springs DRE | 1661335 |
Zoning/Planning | Original | / | 4/5/2022 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1660834 |
Enumeration | Original | D | 4/5/2022 | BRENT | BRENT | It appears that the scope of work has changed from a suite expansion to a separate tenant space. Clarify scope. If this is to be a separate tenant space, then the address is 3077 N. Academy. If it is to be a part of 3073 N. Academy, then all plan pages need to show this address. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1660647 |
Electronic Plan | Original | / | 4/5/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1660630 |
Construction | Original | D | 4/5/2022 | DANM | DANM | Quality of resubmittal is poor and difficult to read - make sure any changes to the drawings are carried out by the design professional. A door is required between the two spaces in order for this submittal to be considered a suite expansion as discussed. 3-hr rate fire door required per IBC Table 716.5 for a 4-hr fire wall. Vestibule required at main entrance to space per IECC C402.5.7.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1660364 |
Electronic Plan | Original | / | 4/4/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1660056 |
Resubmittal 1 | Original | / | 4/4/2022 | BPHILLIPS | BPHILLIPS | Resubmittal #1 | | Resubmittal 1 | 1659707 |
CO Springs Fire | Original | D | 11/17/2021 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | CO Springs Fire | 1595804 |
CO Springs Hazmat | Original | N | 11/17/2021 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1595802 |
Mechanical | Original | A | 11/17/2021 | JUSTINC | JUSTINC | | | Mechanical | 1595571 |
Electronic Plan | Original | / | 11/17/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1595540 |
Electrical | Original | D | 11/16/2021 | SHELBY | SHELBY | Previous review comments have not been addressed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1595055 |
Electronic Plan | Original | / | 11/16/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1595052 |
Plumbing | Original | N | 11/16/2021 | SHANEN | SHANEN | No plumbing scope of work indicated. All required plumbing fixtures are existing to remain. | | Plumbing | 1594944 |
Enumeration | Original | N | 11/16/2021 | BRENT | BRENT | Expansion of existing self storage into 3077 S. Academy tenant space. Will use 3073 S. Academy address. | | Enumeration | 1594443 |
Construction | Original | D | 11/15/2021 | DANM | DANM | This is going to be an expansion of 3073 S Academy Blvd. All previous disapproval comments stand except existing restrooms in other parts of the existing suite can be utilized by this expansion.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1594347 |
Plumbing | Original | D | 10/13/2021 | SHANEN | SHANEN | Change of occupancy requires compliance with 2018 IPC section 403.1 Minimum number of fixtures. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1578156 |
CO Springs DRE | Original | D | 10/13/2021 | ACOOPER | ACOOPER | Request a pre-application meeting at https://coloradosprings.gov/planning-and-development/webform/pre-application-meeting-request (see full review) | | CO Springs DRE | 1578007 |
Mechanical | Original | D | 10/12/2021 | JUSTINC | JUSTINC | Mechanical review pending background revisions from construction reviewer comments.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1577893 |
CSU Water | Original | A | 10/12/2021 | CSUREVIEW | CSUREVIEW | Backflow okay. SSM | stefanm | CSU Water | 1577888 |
CSU Waste Water | Original | N | 10/12/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSM | stefanm | CSU Waste Water | 1577886 |
Electronic Plan | Original | / | 10/12/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1577876 |
Electrical | Original | D | 10/12/2021 | SHELBY | SHELBY | Please show location of branch circuit, feeder, and service over current devices. See https://www.pprbd.org/File/Resources/Downloads/Codes/Policy%20-%20Executive%20Suites.pdf (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1577794 |
Construction | Original | D | 10/12/2021 | DANM | DANM | PPRBD has been informed that the current scope of work is a different owner than the adjacent self-storage tenant space. Restrooms are required within a tenant space and cannot be accessed through an adjacent tenant space. Vestibule required at main entrance to space per IECC C402.5.7. 3-hr rated Fire Door required per IBC Table 716.5 for a 4-hr fire wall. Door to adjacent space not shown on previously approved permit - clarify. Building space above the scope of work is part of 3077 S Academy and will require a separate submittal and permit to be occupied. Storage Unit drawings should be stamped and signed by a Colorado licensed design professional.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1577570 |
Electronic Plan | Original | / | 10/11/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1577123 |
Enumeration | Original | N | 10/6/2021 | BRENT | BRENT | | | Enumeration | 1575087 |
Enumeration | Original | D | 10/5/2021 | BRENT | BRENT | Since this is an expansion of the existing self-storage business, this should use the existing tenant address of 3073 S. Academy Blvd. Update all plan pages and the code study form to shown this address. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1574084 |
Electronic Plan | Original | / | 10/5/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1574030 |
Floodplain | Original | N | 9/30/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6435320023) | | Floodplain | 1571937 |