Mechanical | Splice 12/05/22 | A | 12/6/2022 | TCRIPPEN | TCRIPPEN | Approved, | | Mechanical | 1778862 |
Out to Review | Splice 12/05/22 | / | 12/5/2022 | NELIDA | NELIDA | Justin 719-896-0112 | | Out to Review | 1778157 |
Mechanical | Original | A | 1/28/2022 | DALEH | DALEH | Listing verified | | Mechanical | 1629040 |
Electrical | Original | A | 1/28/2022 | SHELBY | SHELBY | | | Electrical | 1629030 |
Resubmittal 4 | Original | / | 1/21/2022 | AUSTINK | AUSTINK | Resubmittal #4 | | Resubmittal 4 | 1624706 |
Mechanical | Original | D | 1/18/2022 | DALEH | DALEH | Waiting for Electrical (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1622104 |
Electrical | Original | D | 1/14/2022 | SHELBY | SHELBY | Please confirm model being installed is MC-1. Note on electrical drawing says equal to MC-1. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1621941 |
Resubmittal 3 | Original | / | 1/10/2022 | AUSTINK | AUSTINK | Resubmittal #3 | | Resubmittal 3 | 1619198 |
Mechanical | Original | D | 1/7/2022 | DALEH | DALEH | Waiting for Electrical (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1618426 |
Electrical | Original | D | 1/6/2022 | SHELBY | SHELBY | 1. Missing electrical sheets. 2. CSA (NRTL) listing of tested models is OK. Please specify model number when re sibmitting electrical sheets. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1617729 |
Electronic Plan | Original | / | 1/6/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1617721 |
Resubmittal 2 | Original | / | 1/5/2022 | AUSTINK | AUSTINK | Resubmittal #2 | | Resubmittal 2 | 1617208 |
Mechanical | Original | D | 12/15/2021 | SHELBY | SHELBY | Specifications indicates an NRTL listing ( CSA ) is available for this model ( MC-1) of coffee roaster. Please provide NRTL listing (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1608757 |
Electrical | Original | D | 12/15/2021 | SHELBY | SHELBY | Specifications indicates an NRTL listing ( CSA ) is available for this model ( MC-1) of coffee roaster. Please provide NRTL listing. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1608755 |
Electronic Plan | Original | / | 12/15/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1608740 |
Enumeration | Original | N | 12/15/2021 | AMY | AMY | | | Enumeration | 1608587 |
Electronic Plan | Original | / | 12/15/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1608580 |
Resubmittal 1 | Original | / | 12/15/2021 | AUSTINK | AUSTINK | Resubmittal #1 | | Resubmittal 1 | 1608559 |
CO Springs Fire | Original | N | 11/17/2021 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1595834 |
CO Springs Hazmat | Original | N | 11/17/2021 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1595833 |
Mechanical | Original | D | 10/13/2021 | JUSTINC | JUSTINC | Provide gas connection detail Mechanical review incomplete pending electrical reviewer comments.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1578368 |
Electronic Plan | Original | / | 10/13/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1578365 |
Electrical | Original | D | 10/13/2021 | SHELBY | SHELBY | 1. Provide NRTL listing for coffee roaster. 2. Provide electrical. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1578300 |
Plumbing | Original | N | 10/13/2021 | SHANEN | SHANEN | No plumbing scope of work indicated. | | Plumbing | 1578122 |
CO Springs DRE | Original | N | 10/13/2021 | MGRABER | MGRABER | Interior remodel, no change of use or occupancy. (see full review) | | CO Springs DRE | 1578112 |
Zoning/Planning | Original | / | 10/13/2021 | MGRABER | MGRABER | In Current Review by MGRABER | | Zoning/Planning | 1578110 |
CSU Water | Original | N | 10/13/2021 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 1577986 |
CSU Waste Water | Original | N | 10/13/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 1577985 |
Construction | Original | N | 10/13/2021 | MICHAELA | MICHAELA | | | Construction | 1577973 |
Electronic Plan | Original | / | 10/13/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1577969 |
Enumeration | Original | D | 10/7/2021 | AMY | AMY | The permit history on this building is dated. Please provide the separation of space per tenant along with all addresses on site to date. Pease clarify if any of the spaces are vacant. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1575504 |
Electronic Plan | Original | / | 10/7/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1575491 |
Floodplain | Original | N | 10/6/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5330201003) | | Floodplain | 1575120 |