Plumbing | Original | A | 1/11/2022 | SHANEN | SHANEN | | | Plumbing | 1619934 |
Resubmittal 4 | Original | / | 1/10/2022 | AUSTINK | AUSTINK | Resubmittal #4 | | Resubmittal 4 | 1618969 |
Plumbing | Original | D | 12/10/2021 | SHANEN | SHANEN | Schedule a mixing (shower) valve and sprayer for the wash tubs (remote mixing valve and single tempered water line is not compliant with sections 412.3 and 607.1.2). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1606404 |
Resubmittal 3 | Original | / | 12/9/2021 | AUSTINK | AUSTINK | Resubmittal #3 | | Resubmittal 3 | 1605381 |
Electrical | Original | A | 12/8/2021 | SHELBY | SHELBY | | | Electrical | 1604948 |
Plumbing | Original | D | 12/7/2021 | SHANEN | SHANEN | Incomplete review. No plumbing plans provided with this re-submittal. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1604355 |
Resubmittal 2 | Original | / | 12/7/2021 | AUSTINK | AUSTINK | Resubmittal #2 | | Resubmittal 2 | 1604307 |
Electrical | Original | D | 12/3/2021 | SHELBY | SHELBY | 1.Electrical floor plan does not match C,M, or Plumbing floor plans. Complete re review. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1602495 |
Mechanical | Original | A | 12/2/2021 | JUSTINC | JUSTINC | | | Mechanical | 1601633 |
Plumbing | Original | D | 12/2/2021 | SHANEN | SHANEN | Schedule a mixing (shower) valve and sprayer for the wash tubs (remote mixing valve and single tempered water line is not compliant with sections 412.3 and 607.2). Sprayer must be equipped with a vacuum breaker. Provide manufacturer's cut sheets for the wash tubs. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1601509 |
Electronic Plan | Original | / | 12/2/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1601505 |
Resubmittal 1 | Original | / | 12/1/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1601437 |
CO Springs Fire | Original | N | 11/17/2021 | CSFIRE | CSFIRE | NO FIRE FINAL REQUIRED | rpeterson | CO Springs Fire | 1595836 |
CO Springs Hazmat | Original | N | 11/17/2021 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1595835 |
CO Springs DRE | Original | N | 10/15/2021 | DFOXX | DFOXX | Interior remodel only, no change of use. (see full review) | | CO Springs DRE | 1579677 |
Plumbing | Original | D | 10/14/2021 | SHANEN | SHANEN | Provide manufacturer's cut sheets for the wash tubs. Schedule a mixing (shower) valve and sprayer for the wash tubs (remote mixing valve and single tempered water line is not compliant with sections 412.3 and 607.2). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1579307 |
Electrical | Original | A | 10/13/2021 | SHELBY | SHELBY | | | Electrical | 1578466 |
Electronic Plan | Original | / | 10/13/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1578462 |
CSU Water | Original | N | 10/13/2021 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 1578376 |
CSU Waste Water | Original | N | 10/13/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 1578375 |
Mechanical | Original | D | 10/13/2021 | JUSTINC | JUSTINC | Cannot provide birdscreen at dryer vent termination. Provide backdraft damper Backdraft damper for EF-2
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1578360 |
Zoning/Planning | Original | / | 10/13/2021 | DFOXX | DFOXX | In Current Review by DFOXX | | Zoning/Planning | 1578348 |
Zoning/Planning | Original | / | 10/13/2021 | KDODGE | KDODGE | In Current Review by KDODGE | | Zoning/Planning | 1578342 |
Construction | Original | A | 10/13/2021 | MICHAELA | MICHAELA | | | Construction | 1578280 |
Electronic Plan | Original | / | 10/13/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1577991 |
Enumeration | Original | N | 10/11/2021 | BECKYA | BECKYA | Plan was submitted under the wrong address. Enumerations changed the plan screen and label to show correct address. | | Enumeration | 1576832 |
Electronic Plan | Original | / | 10/11/2021 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1576785 |
Floodplain | Original | N | 10/7/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6411401036) | | Floodplain | 1575780 |