Electrical | Original | A | 12/10/2021 | DANIELG | DANIELG | | | Electrical | 1606034 |
Electronic Plan | Original | / | 12/10/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1606012 |
Resubmittal 1 | Original | / | 12/9/2021 | AUSTINK | AUSTINK | Resubmittal #1 | | Resubmittal 1 | 1605538 |
CO Springs Hazmat | Original | N | 12/6/2021 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1603296 |
CO Springs Fire | Original | N | 12/6/2021 | CSFIRE | CSFIRE | NO FIRE FINAL (see full review) | csfdit | CO Springs Fire | 1603294 |
Electrical | Original | D | 11/2/2021 | DANIELG | DANIELG | 1. Please clarify. Sheet E-P-401 indicates that receptacles in office 2423 are in panel 2AB2P1-2:52. On sheet E-602 the receptacles are shown in panel 2AC2P1-2.
2) Provide volt amps for all branch circuit, feeder and service loads for all equipment affected by the scope of work. Calculated load of panel in amps.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1587880 |
Electronic Plan | Original | / | 11/2/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1587842 |
Plumbing | Original | N | 11/1/2021 | SHANEN | SHANEN | No plumbing scope of work indicated. | | Plumbing | 1587024 |
Mechanical | Original | A | 10/29/2021 | DALEH | DALEH | | | Mechanical | 1586194 |
CSU Waste Water | Original | N | 10/28/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Waste Water | 1586070 |
CSU Water | Original | N | 10/28/2021 | CSUREVIEW | CSUREVIEW | No plumbing work. CJS | cjsavage | CSU Water | 1586069 |
CO Springs DRE | Original | N | 10/28/2021 | PDOSCH | PDOSCH | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy (see full review) | | CO Springs DRE | 1586026 |
Zoning/Planning | Original | / | 10/28/2021 | PDOSCH | PDOSCH | In Current Review by PDOSCH | | Zoning/Planning | 1586024 |
Construction | Original | A | 10/28/2021 | MICHAELA | MICHAELA | | | Construction | 1586008 |
Electronic Plan | Original | / | 10/28/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1586000 |
Enumeration | Original | N | 10/25/2021 | BRENT | BRENT | | | Enumeration | 1583484 |
Electronic Plan | Original | / | 10/25/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1583470 |
Floodplain | Original | N | 10/22/2021 | KEITH | KEITH | | | Floodplain | 1582863 |
Floodplain | Original | / | 10/21/2021 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7326201002) | | Floodplain | 1582572 |