Mechanical | Splice 07/22/23 | A | 7/26/2023 | JUSTINC | JUSTINC | Revised ventilation strategy | | Mechanical | 1875475 |
Resubmittal 1 | Splice 07/22/23 | / | 7/26/2023 | QUINTONW | QUINTONW | Resubmittal #1 | | Resubmittal 1 | 1875452 |
Mechanical | Splice 07/22/23 | D | 7/24/2023 | JUSTINC | JUSTINC | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1874080 |
Electrical | Splice 06/30/23 | A | 7/6/2023 | BERTHA | BERTHA | Revised power plan, revised schedules, revised one-line | | Electrical | 1867047 |
Electronic Plan | Splice 06/30/23 | / | 7/3/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1865747 |
Mechanical | Splice 08/23/22 | A | 8/23/2022 | JUSTINC | JUSTINC | Revised for combustion air changes | | Mechanical | 1732399 |
Construction | Splice 07/19/22 | A | 7/27/2022 | MICHAELA | MICHAELA | Additional structural detail | | Construction | 1719670 |
Resubmittal 1 | Splice 07/19/22 | / | 7/27/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #1 | | Resubmittal 1 | 1719187 |
Construction | Splice 07/19/22 | D | 7/20/2022 | MICHAELA | MICHAELA | Provide a revised S1.0 locating the new details. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1715932 |
Electrical | Splice 06/23/22 | A | 6/27/2022 | BERTHA | BERTHA | Added humidor. | | Electrical | 1704599 |
Electronic Plan | Splice 06/23/22 | / | 6/27/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1704547 |
Mechanical | Splice 06/23/22 | A | 6/27/2022 | JUSTINC | JUSTINC | Revised backgrounds | | Mechanical | 1704329 |
Electronic Plan | Splice 06/23/22 | / | 6/27/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1704312 |
Plumbing | Splice 06/23/22 | A | 6/27/2022 | SHANEN | SHANEN | Delta 4 revisions: Adjusted sheet P1.1. | | Plumbing | 1704301 |
Construction | Splice 06/23/22 | A | 6/27/2022 | MICHAELA | MICHAELA | Architectural and structural updates. | | Construction | 1704299 |
Electrical | Splice 06/06/22 | A | 6/22/2022 | BERTHA | BERTHA | Revised service. | | Electrical | 1702557 |
Electronic Plan | Splice 06/06/22 | / | 6/22/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1702397 |
Mechanical | Splice 06/06/22 | N | 6/22/2022 | JUSTINC | JUSTINC | No new or revised mechanical scope indicated | | Mechanical | 1702393 |
Electronic Plan | Splice 06/06/22 | / | 6/22/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1702385 |
Electrical | Splice 06/06/22 | D | 6/15/2022 | BERTHA | BERTHA | 1. Clarify what DOAS-1 is. 2. Provide location of DOAS-1. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1699042 |
Electronic Plan | Splice 06/06/22 | / | 6/15/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1698830 |
Construction | Splice 05/05/22 | A | 5/6/2022 | MICHAELA | MICHAELA | Updated scope of work. | | Construction | 1677804 |
WP Zoning | Original | A | 3/24/2022 | DBURGESS | DBURGESS | ZDP approved 3/24/2022. Subcontractor Business Licenses verified - to be maintained throughout project if changes are made. GC to schedule pre-construction meeting with City Superindendent & Construction Inspector Phil Pyles prior to construction activities. Phil's #719-243-4507. | | WP Zoning | 1654712 |
WP Fire (CSFD Commercial) | Original | A | 2/28/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | WP Fire (CSFD Commercial) | 1642602 |
Electrical | Original | A | 2/17/2022 | SHELBY | SHELBY | | | Electrical | 1638714 |
Plumbing | Original | A | 2/9/2022 | SHANEN | SHANEN | | | Plumbing | 1634390 |
Construction | Original | A | 2/8/2022 | MICHAELA | MICHAELA | | | Construction | 1633687 |
Resubmittal 2 | Original | / | 2/7/2022 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1633545 |
WP Fire (CSFD Commercial) | Original | D | 2/7/2022 | DBURGESS | DBURGESS | Disapproved at this time to release the plan set to address review comments. | | WP Fire (CSFD Commercial) | 1632895 |
WP Zoning | Original | D | 2/7/2022 | DBURGESS | DBURGESS | ZDP is pending approval of the Subcontractor / Vendor List. Fire Service Line design received by City of WP on 2/03/2022 and is being reviewed by the City of WP Utilities Dept. This component should be be submitted to PPRBD to complete the plan record when resubmitting plumbing revisions. WP Zoning disapproved at this time to release the plan set to address review comments. | | WP Zoning | 1632894 |
Electrical | Original | D | 2/4/2022 | SHELBY | SHELBY | Confirm new service gear conforms to 230.71(B) NEC. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1632742 |
Electronic Plan | Original | / | 2/4/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1632741 |
Plumbing | Original | D | 2/3/2022 | SHANEN | SHANEN | Need construction reviewer provided occupancy type and occupant load to verify compliance with section 403.1 Minimum number of fixtures. Glass washer shall discharge indirectly. SK1 shall discharge indirectly to a waste receptor through an air gap if it is to be used for ware washing. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1631732 |
Mechanical | Original | A | 2/2/2022 | JUSTINC | JUSTINC | | | Mechanical | 1631368 |
Construction | Original | D | 2/1/2022 | MICHAELA | MICHAELA | A2.3 - Revise as requested or remove. Match framing with structural pages or remove from plan. A5.1 - Section 1 - It still seems that there would need to be a vertical wall at this location that would require insulation. See plan. Structural - Specify all hangers. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1631234 |
Resubmittal 1 | Original | / | 2/1/2022 | AUSTINK | AUSTINK | Resubmittal #1 | | Resubmittal 1 | 1630828 |
WP Health Dept | Original | N | 1/18/2022 | DBURGESS | DBURGESS | N/A per Teller County Environmental Health Officer Keri Ptak - no retail food license required unless serving food. | | WP Health Dept | 1622402 |
WP Zoning | Original | D | 1/5/2022 | DBURGESS | DBURGESS | ZDP is pending approval of the Subcontractor / Vendor List. WP Zoning disapproved at this time to release the plan set to address review comments. | | WP Zoning | 1616816 |
WP Fire (CSFD Commercial) | Original | D | 12/29/2021 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | WP Fire (CSFD Commercial) | 1614040 |
WP Waste Water | Original | A | 12/21/2021 | KSIMPKINS | KSIMPKINS | All comments have been addressed. Approved to move forward. | | WP Waste Water | 1611046 |
WP Water | Original | A | 12/21/2021 | KSIMPKINS | KSIMPKINS | All comments have been addressed. Approved to move forward. | | WP Water | 1611043 |
Plumbing | Original | D | 12/10/2021 | SHANEN | SHANEN | Clarify how the sanitary sewer is protected from bar area fixtures that might discharge fats, oils or grease (FOG) to the building drain. A grease interceptor may be required. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1606081 |
Electrical | Original | A | 12/9/2021 | SHELBY | SHELBY | | | Electrical | 1605913 |
Mechanical | Original | D | 12/9/2021 | JUSTINC | JUSTINC | Provide refrigeration calculation per 2015 IMC 1103.1 Verify if within allowable limits per table on plan. If over the allowable limits indicate how protecting on plan.
Provide stamped letter or sheet from structural engineer for all new equipment on roof that exceeds 300# AHJ threshold.
Clarify equipment interlock
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1605860 |
Electronic Plan | Original | / | 12/9/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1605849 |
Elevators | Original | A | 12/8/2021 | ERIC | ERIC | Garaventa vertical platform lift. No elevator contractor stated. Ensure at least 5 fc of lighting at lift. | | Elevators | 1604900 |
Construction | Original | D | 12/8/2021 | MICHAELA | MICHAELA | Address clear floor space at two doors. #105 and 101. Snow load is 40 PSFWind speed is 130 MPH V-ult. Exposure is C Provide engineering at steel trusses. Provide framing details for upper awning. Verify all new windows are in unmodified existing openings or indicate framing requirements on framing plans. Address connection requirements at ridge and collar tie. Address rafter connection to top plate. Address support and connections of ceiling joists. Address insulation requirements. Provide IECC certificate for areas of new roof and wall framing. Address hinge being created at wall extension.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1604816 |
Electronic Plan | Original | / | 12/8/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1604599 |
WP Zoning | Original | D | 12/2/2021 | DBURGESS | DBURGESS | Change In Use Zoning Development Permit (ZDP) required per City of WP Municipal Code section 18.72.020. Please submit 2021 Multi-Use ZDP with full-size construction plans and remit $144.00 application fee. City cannot sign off on PPRBD Construction Drawings until Change In Use ZDP is processed & approved. Please contact David Burgess at (719) 687-5202 with questions. | | WP Zoning | 1602044 |
WP Floodplain | Original | N | 12/2/2021 | DBURGESS | DBURGESS | Verified not in a floodplain | | WP Floodplain | 1602029 |
WP Enumeration | Original | A | 12/2/2021 | DBURGESS | DBURGESS | Address, owner & parcel number verified. | | WP Enumeration | 1602028 |