Elevators | Original | A | 3/22/2022 | ERIC | ERIC | TK Elevator machineroom-less traction elevator, no generator power | | Elevators | 1653731 | Submittal 4 | Original | / | 3/22/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1653726 | CO Springs Fire | Original | N | 3/10/2022 | CSFIRE | CSFIRE | CONSTRUCTION PLANS SHALL BE SUBMITTED TO CSFD FOR REVIEW AND APPROVAL (see full review) | csfdit | CO Springs Fire | 1648291 | Mechanical | Original | N | 2/17/2022 | JUSTINC | JUSTINC | No new or revised mechanical scope indicated | | Mechanical | 1638399 | Electronic Plan | Original | / | 2/17/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1638388 | Construction | Original | N | 2/17/2022 | LBENNETT | LBENNETT | Construction plan to be reviewed by the state of Colorado per project manager Jo Walker | | Construction | 1638293 | Electronic Plan | Original | / | 2/17/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1638130 | Elevators | Original | D | 2/10/2022 | ERIC | ERIC | TK Elevator machineroom-less traction elevator, no generator power
The hoistway of a machineroom-less traction elevator is considered the machine/control space and contains the motor controller.
The disconnects located in the door frame do not meet the requirements listed below. . 2020 NFPA 70 section 620.51(C)(1) Driving machines or motion and operation controllers not within sight of the disconnecting means shall be provided with a manually operated switch installed in the control circuit to prevent starting, the manually operated switch shall be installed adjacent to this equipment
2020 NFPA 70 section 620.22(A) The overcurrent device protecting the branch circuit shall be located in the elevator machine room, control room, machinery space or control space. . (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1635095 | Submittal 3 | Original | / | 2/9/2022 | AUSTINK | AUSTINK | Submittal #3 | | Submittal 3 | 1634338 | Electrical | Original | D | 1/31/2022 | SHELBY | SHELBY | Sheets provided do not show/include the elevator scope. All prior review comments must be addressed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1630419 | Elevators | Original | D | 1/26/2022 | ERIC | ERIC | TK Elevator machineroom-less traction elevator, no generator power
The hoistway of a machineroom-less traction elevator is considered the machine/control space and contains the motor controller.
A main non-fused disconnect is required to be within sight of the motor controller NFPA 70 section 620.51(C)(1)
NFPA 70 section 620.22(A) requires the overcurrent device for the cab circuit to be located in the control/machine space. . (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1627331 | Submittal 2 | Original | / | 1/26/2022 | AUSTINK | AUSTINK | Submittal #2 | | Submittal 2 | 1627097 | Electrical | Original | D | 1/19/2022 | SHELBY | SHELBY | 1. Remove all sheets showing non Elevator scope of work. 2. Electrical sheets must reflect Elevator corrections. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1623060 | Elevators | Original | D | 1/12/2022 | ERIC | ERIC | TK Elevator machineroom-less traction elevator, no generator power Several references to using existing hoistway and removing existing walls and hoist beam please clarify.
Page EP102-B Additional disconnects required in hoistway, NON-fused main disconnect to be located adjacent to drive machine, fused 110v cab disconnect located in same location, see NFPA 70 section 620.51(c)(1)
Page EL102-B 19fc of lighting required at elevator door frame at upper landing to illuminate test and control panel in door jamb
Please provide mechanical plans, hoistway ventilation is required, see IBC section 3005.2, ASME A17.1 section 2.7.9.2 and TK Elevator submittals.
Ventilation opening shall be protected with an approved motorized damper, controlled via thermostat at top of hoistway, interlocked with elevator lobby and hoistway fire alarm initiating devices and will remove power from ventilation and damper will close. . (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1620193 | Floodplain | Original | N | 1/10/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6216300001) | | Floodplain | 1619063 |
|
| |
|