Electrical | Original | A | 4/4/2022 | DANIELG | DANIELG | | | Electrical | 1659847 |
Electronic Plan | Original | / | 4/4/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1659809 |
Submittal 4 | Original | / | 4/1/2022 | ANDREAL | ANDREAL | Submittal #4 | | Submittal 4 | 1659083 |
Electrical | Original | D | 3/28/2022 | DANIELG | DANIELG | Branch circuit overcurrent devices must be accessible to the occupants they supply.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1656361 |
Electronic Plan | Original | / | 3/28/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1656289 |
Electrical | Original | / | 3/28/2022 | WEBSITE | WEBSITE | Overtime Deauthorized for Electrical by DAVID BRINKER | peakpro | Electrical | 1655980 |
Electrical | Original | / | 3/28/2022 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by DAVID BRINKER | peakpro | Electrical | 1655979 |
Mechanical | Original | A | 3/23/2022 | DALEH | DALEH | | | Mechanical | 1654144 |
Submittal 3 | Original | / | 3/22/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1653337 |
Woodmoor Water | Original | A | 3/21/2022 | WOODWATER | WOODWATER | Plans Approved for Construction. Inspection is Required prior to permit sign-off. | wwsdengineer | Woodmoor Water | 1652943 |
Woodmoor Waste Water | Original | A | 3/21/2022 | WOODWATER | WOODWATER | Plans approved for construction. Inspection is required prior to permit sign-off. Modified Tap Application pending. | wwsdengineer | Woodmoor Waste Water | 1652941 |
Tri-Lakes Fire (CSFD) | Original | A | 3/15/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1650673 |
Electrical | Original | D | 3/11/2022 | BERTHA | BERTHA | 1. Comply with previous review comment #1 - Provide compliance with 240.24(B) - 2020 NEC. Provide location of all panels used in the scope of work - 1LA, 2HA, etc (see red-line mark up on drawings.) 2. Provide location of Panel 2HA on floor plan, provide Panel 2HA on one-line, provide Panel 2HA schedule. See red-line mark up on drawings.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1648877 |
Electronic Plan | Original | / | 3/11/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1648862 |
Mechanical | Original | D | 3/7/2022 | DALEH | DALEH | Need to upload all Mechanical sheets This upload only has one Mechanical sheet No review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1645822 |
Electronic Plan | Original | / | 3/7/2022 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1645765 |
Plumbing | Original | A | 3/7/2022 | SHANEN | SHANEN | | | Plumbing | 1645685 |
Construction | Original | A | 3/7/2022 | MICHAELA | MICHAELA | | | Construction | 1645640 |
Enumeration | Original | A | 3/3/2022 | BECKYA | BECKYA | | | Enumeration | 1644683 |
Submittal 2 | Original | / | 3/3/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1644666 |
Tri-Lakes Fire (CSFD) | Original | D | 2/28/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1642733 |
Electrical | Original | D | 2/22/2022 | DANIELG | DANIELG | 1. Comply 240.24 NEC. Please see link: https://www.pprbd.org/File/Resources/Downloads/Codes/Policy%20-%20Executive%20Suites.pdf
2. Show panel L1A on one-line.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1639746 |
Electronic Plan | Original | / | 2/22/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1639602 |
Woodmoor Water | Original | D | 2/16/2022 | WOODWATER | WOODWATER | The plans look good, but before we can sign off on them, the applicant will need to submit a modified tap application and pay for additional drainage fixture units. | wwsdengineer | Woodmoor Water | 1637571 |
Woodmoor Water | Original | D | 2/16/2022 | WOODWATER | WOODWATER | The plans look good, but before we can sign off on them, the applicant will need to submit a modified tap application and pay for additional drainage fixture units. | wwsdengineer | Woodmoor Water | 1637565 |
Woodmoor Waste Water | Original | D | 2/16/2022 | WOODWATER | WOODWATER | The plans look good, but before we can sign off on them, the applicant will need to submit a modified tap application and pay for additional drainage fixture units. | wwsdengineer | Woodmoor Waste Water | 1637562 |
Construction | Original | D | 2/14/2022 | SHELLEY | SHELLEY | Floor plan on file matches C75124, splice 9/31/14. Address other comments. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1636494 |
Mechanical | Original | D | 2/10/2022 | DALEH | DALEH | Waiting for proper floor plans per Construction review comments Revise Mechanical as needed No review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1635581 |
Plumbing | Original | A | 2/10/2022 | SHANEN | SHANEN | | | Plumbing | 1635446 |
Monument Zoning | Original | N | 2/8/2022 | TOWNOFMON | TOWNOFMON | Pikes Peak Regional Building inspection is needed. The Town of Monument zoning approval is based on the submission to Monument provided within our Cascade permitting system. If that submission differs or is changed within Pikes Peak Regional Building, we cannot be held liable for the zoning decision. | trust@tomgov.org | Monument Zoning | 1633782 |
Construction | Original | D | 2/7/2022 | MICHAELA | MICHAELA | This is the most recent floor plan for suite 240. There seem to be existing walls that have been created without a permit. Add these walls to those that will require an inspection. Locate required clear floor space in toilet room 206. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1633315 |
Electronic Plan | Original | / | 2/7/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1633035 |
Enumeration | Original | A | 2/4/2022 | BECKYA | BECKYA | | | Enumeration | 1632369 |
Floodplain | Original | N | 1/28/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7123106023) | | Floodplain | 1629038 |