Mechanical | Splice 01/03/23 | A | 1/3/2023 | JUSTINC | JUSTINC | Revised exhaust | | Mechanical | 1786946 |
Plumbing | Splice 09/22/22 | A | 10/10/2022 | SHANEN | SHANEN | Delta 3 revisions: Adjusted sheet P111 and P111A. | | Plumbing | 1753408 |
Submittal 2 | Splice 09/22/22 | / | 10/10/2022 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1753340 |
Plumbing | Splice 09/22/22 | D | 9/27/2022 | SHANEN | SHANEN | P111A: 3/4" DCW is undersized. Provide an analysis to verify 3/4" DCW is adequately sized to serve all fixtures as shown. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1746566 |
Plumbing | Splice 09/16/22 | A | 9/19/2022 | SHANEN | SHANEN | Delta 2 revisions: Adjusted sheet P111 and P111A. | | Plumbing | 1742786 |
CO Springs Fire | Splice 09/01/22 | A | 9/6/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1737757 |
Electrical | Splice 09/01/22 | A | 9/2/2022 | DANIELG | DANIELG | Delta revision 2. Minor floor-plan revisions. | | Electrical | 1737270 |
Electronic Plan | Splice 09/01/22 | / | 9/2/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1737256 |
Plumbing | Splice 09/01/22 | A | 9/2/2022 | SHANEN | SHANEN | Clouded revisions only: Adjusted sheet PD111, P111 and P111A. | | Plumbing | 1737209 |
Construction | Splice 09/01/22 | A | 9/2/2022 | BPHILLIPS | BPHILLIPS | Minor floorplan revisions. | | Construction | 1737170 |
Electronic Plan | Splice 09/01/22 | / | 9/2/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1737169 |
Electrical | Splice 07/05/22 | A | 7/28/2022 | DANIELG | DANIELG | Delta revision 1. As built. | | Electrical | 1719906 |
Electronic Plan | Splice 07/05/22 | / | 7/28/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1719856 |
Submittal 2 | Splice 07/05/22 | / | 7/28/2022 | STEPHANIEV | STEPHANIEV | Submittal #2 | | Submittal 2 | 1719785 |
CO Springs Fire | Splice 07/05/22 | A | 7/6/2022 | CSFIRE | CSFIRE | Submitted By: Valdez, Phil You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! Thomas (see full review) | phil.valdez | CO Springs Fire | 1708878 |
Electrical | Splice 07/05/22 | D | 7/5/2022 | DANIELG | DANIELG | Please clarify. Panel schedules L1A and L1B do not match original approved plans. Provide service load summary for panel MDP.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1708505 |
Electronic Plan | Splice 07/05/22 | / | 7/5/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1708499 |
Plumbing | Splice 07/05/22 | A | 7/5/2022 | SHANEN | SHANEN | Delta 2 revisions: Adjusted sheet P111B. | | Plumbing | 1708484 |
CO Springs Hazmat | Original | A | 4/26/2022 | CSFIRE | CSFIRE | Submitted by: Tillery, Demarcus
You are responsible for reviewing the APPROVAL comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | CO Springs Hazmat | 1671646 |
Mechanical | Original | A | 4/20/2022 | JUSTINC | JUSTINC | | | Mechanical | 1668143 |
Submittal 3 | Original | / | 4/19/2022 | JAY | JAY | Submittal #3 | | Submittal 3 | 1667836 |
CO Springs DRE | Original | A | 4/18/2022 | ESHAFER | ESHAFER | Approved per prior approval. (see full review) | | CO Springs DRE | 1666873 |
CO Springs Hazmat | Original | D | 4/18/2022 | CSFIRE | CSFIRE | Submitted by: Tillery, Demarcus
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal to RBD: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | CO Springs Hazmat | 1666602 |
Zoning/Planning | Original | / | 4/11/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1663524 |
Plumbing | Original | A | 4/11/2022 | SHANEN | SHANEN | | | Plumbing | 1663263 |
Mechanical | Original | A | 4/11/2022 | JUSTINC | JUSTINC | | | Mechanical | 1663193 |
Electronic Plan | Original | / | 4/11/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1663156 |
Construction | Original | A | 4/11/2022 | BPHILLIPS | BPHILLIPS | | | Construction | 1663151 |
Electronic Plan | Original | / | 4/11/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1663132 |
Submittal 2 | Original | / | 4/11/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1663030 |
CO Springs Hazmat | Original | D | 3/21/2022 | CSFIRE | CSFIRE | Submitted by: Tillery, Demarcus
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal to RBD: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | CO Springs Hazmat | 1652956 |
CO Springs Fire | Original | A | 3/17/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | rpeterson | CO Springs Fire | 1652109 |
Plumbing | Original | A | 3/4/2022 | SHANEN | SHANEN | | | Plumbing | 1645360 |
CO Springs DRE | Original | A | 3/4/2022 | ESHAFER | ESHAFER | Interior finish only: No change in footprint, No change to exterior, No change in parking, No change in occupancy. (see full review) | | CO Springs DRE | 1645343 |
Electrical | Original | A | 3/2/2022 | SHELBY | SHELBY | | | Electrical | 1644249 |
Electronic Plan | Original | / | 3/2/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1644239 |
Zoning/Planning | Original | / | 3/2/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1644016 |
Mechanical | Original | D | 3/1/2022 | JUSTINC | JUSTINC | Clarify if ducts are above or below rated horizontal assembly. If above clarify how protecting penetrations
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1643522 |
CSU Water | Original | N | 3/1/2022 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 1643506 |
CSU Waste Water | Original | N | 3/1/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Waste Water | 1643505 |
Construction | Original | D | 3/1/2022 | BPHILLIPS | BPHILLIPS | Prove separation of exits on life safety plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1643494 |
Electronic Plan | Original | / | 2/24/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1641385 |
Enumeration | Original | N | 2/9/2022 | BECKYA | BECKYA | Combining existing suites 140 and 150, tenant is using Suite 140 as business address.
Enumerations crossed off suite 150 on the Architectural Plans and the Code Study Form. The plans should only show one suite number. If these corrected plans are switched out/revised, please be sure to make this change before resubmitting the plans. | | Enumeration | 1634782 |
Floodplain | Original | N | 2/7/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5318220005) | | Floodplain | 1633559 |