Tri-Lakes Fire (CSFD) | Original | N | 6/14/2022 | CSFIRE | CSFIRE | Cell Tower modification - N/A
DCT | DTillery94 | Tri-Lakes Fire (CSFD) | 1698333 |
Electrical | Original | A | 6/10/2022 | BERTHA | BERTHA | | | Electrical | 1696624 |
Electronic Plan | Original | / | 6/10/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1696452 |
Enumeration | Original | N | 6/9/2022 | BECKYA | BECKYA | | | Enumeration | 1695196 |
Submittal 2 | Original | / | 6/8/2022 | BECKYA | BECKYA | Submittal #2 | | Submittal 2 | 1695122 |
Tri-Lakes Fire (CSFD) | Original | D | 4/6/2022 | CSFIRE | CSFIRE | (DISAPPROVED) HAZARDOUS MATERIALS: Provide completed Hazardous Materials Operations Triage form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility. Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2009 IFC Table 105.6.20. PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS, AND FILL OUT THE REQUESTED INFORMATION. All forms and packets are available at https://coloradosprings.gov/hazmat?mlid=42381
Battery info: Lion batteries we need to know energy output in KWh, for all others we need to know total electrolyte capacity in gallons | dwithee | Tri-Lakes Fire (CSFD) | 1661332 |
Woodmoor Water | Original | N | 3/24/2022 | WOODWATER | WOODWATER | No water or sewer improvements | wwsdengineer | Woodmoor Water | 1655289 |
Woodmoor Waste Water | Original | N | 3/24/2022 | WOODWATER | WOODWATER | No water or sewer improvements | wwsdengineer | Woodmoor Waste Water | 1655288 |
Electrical | Original | D | 3/18/2022 | BERTHA | BERTHA | 1. Provide electrical site plan showing all electrical service equipment and disconnects serving the structure.
2. Provide SCA and SCCR for new HPL3 Cabinet
3. Provide volt amps for all branch circuits and load for PPC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1652500 |
Electronic Plan | Original | / | 3/18/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1652496 |
Mechanical | Original | N | 3/15/2022 | JUSTINC | JUSTINC | No new or revised mechanical scope indicated | | Mechanical | 1650146 |
County Zoning | Original | N | 3/14/2022 | DSDRANGEL | DSDRANGEL | | | County Zoning | 1650041 |
Zoning/Planning | Original | / | 3/14/2022 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1650032 |
Construction | Original | N | 3/14/2022 | SHELLEY | SHELLEY | No construction work. | | Construction | 1649989 |
Enumeration | Original | D | 3/14/2022 | AMY | AMY | The plan was checked in under the correct address 18945 Pebble Beach Way. All of the plan pages except for the Code Study have the incorrect address. Correct the pages in the plan submittal. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1649935 |
Electronic Plan | Original | / | 3/14/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1649921 |
Floodplain | Original | N | 3/14/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7112301104) | | Floodplain | 1649238 |