Mechanical | Splice 10/06/22 | A | 10/6/2022 | JUSTINC | JUSTINC | Revised gas | | Mechanical | 1752345 |
Electrical | Original | A | 5/12/2022 | DANIELG | DANIELG | | | Electrical | 1681627 |
Electronic Plan | Original | / | 5/12/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1681621 |
Plumbing | Original | A | 5/12/2022 | SHANEN | SHANEN | | | Plumbing | 1681534 |
Mechanical | Original | A | 5/12/2022 | JUSTINC | JUSTINC | | | Mechanical | 1681501 |
Electronic Plan | Original | / | 5/12/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1681482 |
Construction | Original | A | 5/12/2022 | DANM | DANM | | | Construction | 1681479 |
Electronic Plan | Original | / | 5/12/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1681447 |
Submittal 2 | Original | / | 5/11/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1680210 |
CO Springs Hazmat | Original | N | 5/4/2022 | CSFIRE | CSFIRE | | Jacob.Watson | CO Springs Hazmat | 1676829 |
CO Springs Fire | Original | N | 5/4/2022 | CSFIRE | CSFIRE | Submitted By: Watson, Jacob Thomas no fire final (see full review) | csfdit | CO Springs Fire | 1676823 |
Plumbing | Original | D | 4/21/2022 | SHANEN | SHANEN | Provide a piping materials schedule. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1669566 |
Mechanical | Original | D | 4/21/2022 | JUSTINC | JUSTINC | Provide ventilation schedule Clarify relief of supply air? Returns or exhaust? This is a VB building if using return air plenum all materials within plenum must meet flame spread requirements
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1668978 |
Electronic Plan | Original | / | 4/21/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1668956 |
CSU Water | Original | N | 4/20/2022 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 1668450 |
CSU Waste Water | Original | N | 4/20/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 1668449 |
Electrical | Original | D | 4/20/2022 | DANIELG | DANIELG | 1. Provide conductor size, type, and quantity from utility transformer to the scope of work.
2. Provide panel schedules only for this scope of work.
3. Homogenize new load with existing load in panel schedules.
4. Provide load from 112.5 KVA transformer in panel LK.
complete re-review.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1668386 |
Electronic Plan | Original | / | 4/20/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1668347 |
CO Springs DRE | Original | N | 4/20/2022 | PDOSCH | PDOSCH | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy (see full review) | | CO Springs DRE | 1668259 |
Zoning/Planning | Original | / | 4/20/2022 | PDOSCH | PDOSCH | In Current Review by PDOSCH | | Zoning/Planning | 1668258 |
Construction | Original | D | 4/20/2022 | DANM | DANM | Clarify if the Community Gathering space is assembly occupancy. Clarify if Beverage area is simply an employee break area. 34" max. height at front of sink. Provide listed assembly for infill wall. Clarify UL listing for wall shown in Entrance From The Chapel plan detail - previous sheet shows an IBC prescriptive listing.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1668196 |
Electronic Plan | Original | / | 3/25/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1655729 |
Electronic Plan | Original | / | 3/25/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1655604 |
Enumeration | Original | N | 3/23/2022 | BRENT | BRENT | Tax schedule number and legal description shown on the code study form corrected by Enumerations. | | Enumeration | 1654490 |
Electronic Plan | Original | / | 3/23/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1654480 |
Floodplain | Original | N | 3/21/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6233201004) | | Floodplain | 1653259 |