CO Springs Fire | Splice 04/24/23 | N | 4/25/2023 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren N/A | phil.valdez | CO Springs Fire | 1835060 |
Electrical | Splice 04/24/23 | A | 4/24/2023 | BERTHA | BERTHA | Revised panel/circuit number. | | Electrical | 1834292 |
Electronic Plan | Splice 04/24/23 | / | 4/24/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1834289 |
Mechanical | Splice 04/24/23 | A | 4/24/2023 | JUSTINC | JUSTINC | Revised exhaust fan schedule | | Mechanical | 1834134 |
Construction | Splice 04/24/23 | A | 4/24/2023 | SHELLEY | SHELLEY | Revised listing, verified dimensions. | | Construction | 1834096 |
Construction | Splice 02/23/23 | A | 2/28/2023 | SHELLEY | SHELLEY | Floor plan revision at nurse team station | | Construction | 1807914 |
Submittal 2 | Splice 02/23/23 | / | 2/27/2023 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1807269 |
Electrical | Splice 02/23/23 | A | 2/24/2023 | BERTHA | BERTHA | Added dimmer, added receptacle. | | Electrical | 1806849 |
CO Springs Fire | Splice 02/23/23 | A | 2/24/2023 | CSFIRE | CSFIRE | Nurse Station changes (see full review) | Jacob.Watson | CO Springs Fire | 1806847 |
Electronic Plan | Splice 02/23/23 | / | 2/24/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1806845 |
Mechanical | Splice 02/23/23 | A | 2/23/2023 | JUSTINC | JUSTINC | Layout and note revisions | | Mechanical | 1806138 |
Plumbing | Splice 02/23/23 | A | 2/23/2023 | SHANEN | SHANEN | Delta 3 revisions: Adjusted sheet P434. | | Plumbing | 1806124 |
Construction | Splice 02/23/23 | D | 2/23/2023 | SHELLEY | SHELLEY | specify new wall types at nurse team station. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1806118 |
CO Springs Fire | Splice 02/06/23 | A | 2/7/2023 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1799842 |
Mechanical | Splice 02/06/23 | A | 2/6/2023 | JUSTINC | JUSTINC | Layout revised | | Mechanical | 1799373 |
Construction | Splice 02/06/23 | A | 2/6/2023 | SHELLEY | SHELLEY | Port locations, furred wall at EVS | | Construction | 1799262 |
CO Springs Fire | Splice 02/03/23 | A | 2/6/2023 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | jt09ff | CO Springs Fire | 1799167 |
Mechanical | Splice 02/03/23 | A | 2/3/2023 | JUSTINC | JUSTINC | Layout revisions | | Mechanical | 1798948 |
Construction | Splice 02/03/23 | A | 2/3/2023 | SHELLEY | SHELLEY | Minor floor plan revisions, finish details | | Construction | 1798736 |
Electrical | Splice 01/30/23 | A | 2/2/2023 | BERTHA | BERTHA | Minor lighting and power revisions. | | Electrical | 1798330 |
Electronic Plan | Splice 01/30/23 | / | 2/2/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1798275 |
CO Springs Fire | Splice 01/30/23 | A | 2/2/2023 | CSFIRE | CSFIRE | Submitted By: Withee, Doreen E, (see full review) | csfdit | CO Springs Fire | 1798071 |
Mechanical | Splice 01/30/23 | A | 2/1/2023 | JUSTINC | JUSTINC | Revised CFM at (2) locations clouded in red for clarity | | Mechanical | 1797774 |
Construction | Splice 01/30/23 | A | 2/1/2023 | SHELLEY | SHELLEY | Multiple plan details to include existing door on nutrish room, cabinetry, dimensions, etc. | | Construction | 1797765 |
Electrical | Splice 01/12/23 | A | 1/27/2023 | BERTHA | BERTHA | Revised power, revised schedules. | | Electrical | 1796394 |
Electronic Plan | Splice 01/12/23 | / | 1/27/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1796360 |
Submittal 2 | Splice 01/12/23 | / | 1/23/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1793734 |
CO Springs Fire | Splice 01/12/23 | A | 1/13/2023 | CSFIRE | CSFIRE | details for cabinetry, finishes, equipment (see full review) | Jacob.Watson | CO Springs Fire | 1791237 |
Electrical | Splice 01/12/23 | D | 1/13/2023 | BERTHA | BERTHA | Remove all sheets without revisions pertaining to this splice. Remove all old clouds.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1791200 |
Electronic Plan | Splice 01/12/23 | / | 1/13/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1791158 |
Mechanical | Splice 01/12/23 | A | 1/12/2023 | JUSTINC | JUSTINC | Revised VAV schedule | | Mechanical | 1790976 |
Plumbing | Splice 01/12/23 | A | 1/12/2023 | SHANEN | SHANEN | Delta 2 revisions: Adjusted sheet P434 and P930. | | Plumbing | 1790961 |
Electronic Plan | Splice 01/12/23 | / | 1/12/2023 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1790944 |
Construction | Splice 01/12/23 | A | 1/12/2023 | SHELLEY | SHELLEY | Revised details, cabinetry, finishes, equipment | | Construction | 1790931 |
Electrical | Original | A | 8/19/2022 | BERTHA | BERTHA | | | Electrical | 1730968 |
Electronic Plan | Original | / | 8/19/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1730891 |
Plumbing | Original | A | 8/19/2022 | SHANEN | SHANEN | | | Plumbing | 1730428 |
Construction | Original | A | 8/19/2022 | MICHAELA | MICHAELA | | | Construction | 1730397 |
Submittal 4 | Original | / | 8/18/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1730240 |
CO Springs Fire | Original | A | 8/11/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1726750 |
Mechanical | Original | A | 7/27/2022 | JUSTINC | JUSTINC | | | Mechanical | 1719421 |
Plumbing | Original | A | 7/26/2022 | SHANEN | SHANEN | | | Plumbing | 1718880 |
Electrical | Original | D | 7/26/2022 | BERTHA | BERTHA | Comply with previous review comment.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1718849 |
Electronic Plan | Original | / | 7/26/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1718812 |
Construction | Original | A | 7/26/2022 | MICHAELA | MICHAELA | | | Construction | 1718529 |
Submittal 3 | Original | / | 7/25/2022 | ANDREAL | ANDREAL | Submittal #3 | | Submittal 3 | 1718117 |
CO Springs Fire | Original | A | 7/8/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1710208 |
CO Springs Fire | Original | A | 7/8/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1710207 |
CO Springs DRE | Original | N | 7/5/2022 | APAQUETTE | APAQUETTE | Interior remodel only. No change in footprint, No change in parking. No change in occupancy. (see full review) | | CO Springs DRE | 1707944 |
Electrical | Original | D | 7/2/2022 | BERTHA | BERTHA | Provide panel schedules and load summaries for all distribution equipment affected by the scope of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1707879 |
Electronic Plan | Original | / | 6/28/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1705716 |
Zoning/Planning | Original | / | 6/28/2022 | APAQUETTE | APAQUETTE | In Current Review by APAQUETTE | | Zoning/Planning | 1705679 |
Plumbing | Original | D | 6/28/2022 | SHANEN | SHANEN | Clarify OSD. OSD not found in symbols, abbreviations or fixture schedule. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Note: Data may be calculated from point of connection. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1705399 |
Mechanical | Original | A | 6/28/2022 | JUSTINC | JUSTINC | | | Mechanical | 1705183 |
Electronic Plan | Original | / | 6/28/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1705154 |
Construction | Original | A | 6/28/2022 | MICHAELA | MICHAELA | | | Construction | 1705138 |
Submittal 2 | Original | / | 6/27/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1704311 |
CO Springs Hazmat | Original | A | 5/19/2022 | CSFIRE | CSFIRE | Submitted by: Tillery, Demarcus
You are responsible for reviewing the APPROVAL comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | CO Springs Hazmat | 1684766 |
CO Springs Fire | Original | D | 5/16/2022 | CSFIRE | CSFIRE | Address RBD comments regarding architectural submittal - a full review cannot be conducted without this being done.
Plans were checked in for HazMat review due to medgas. (see full review) | csfdit | CO Springs Fire | 1682808 |
Electrical | Original | D | 5/12/2022 | BERTHA | BERTHA | 1. Clarify panel and circuit number for all new/relocated devices.
2. Alternates are not allowed. Remove all alternates.
3. Provide 2015 IECC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1681490 |
Electronic Plan | Original | / | 5/10/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1679850 |
Plumbing | Original | D | 5/9/2022 | SHANEN | SHANEN | Provide a piping materials schedule. Provide water pipe size analysis data, see 2018 IPC appendix E. P520: Clarify OSD. OSD location shall comply with section 802.4 Waste receptors. Waste receptors shall not be installed in concealed spaces. Waste receptors shall not be installed in plenums, crawl spaces, attics, interstitial spaces above ceiling and below floor. Ready access shall be provided to waste receptors. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1678950 |
Mechanical | Original | A | 5/6/2022 | JUSTINC | JUSTINC | No alternates in permit set drawings See 3rd floor plan for permit scope. Any changes will require a plan splice | | Mechanical | 1678165 |
Electronic Plan | Original | / | 5/6/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1678041 |
CSU Water | Original | N | 5/4/2022 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | CSU Water | 1676820 |
CSU Waste Water | Original | N | 5/4/2022 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | CSU Waste Water | 1676819 |
CO Springs DRE | Original | D | 5/4/2022 | JMALPICA | JMALPICA | Please complete section 4.0 of the code study form. (see full review) | | CO Springs DRE | 1676770 |
Construction | Original | D | 5/4/2022 | MICHAELA | MICHAELA | Assemble the plan correctly. Put pages in order into one architectural set. Wall D1 is indicate for both fire barriers and smoke partitions. Create a second wall type, they cannot be the same. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1676724 |
Electronic Plan | Original | / | 5/3/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1675156 |
Enumeration | Original | N | 4/21/2022 | AMY | AMY | | | Enumeration | 1668742 |
Electronic Plan | Original | / | 4/21/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1668741 |
Floodplain | Original | N | 4/18/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6235212001) | | Floodplain | 1667127 |