Electrical | Original | D | 6/28/2022 | DANIELG | DANIELG | Comply 695.4(B)(2)(a)(2) NEC. Per conversation with Charles D. Gallagher from Fire Pump Sales and Services.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1705415 |
Electronic Plan | Original | / | 6/28/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1705289 |
Submittal 4 | Original | / | 6/27/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1704841 |
Electrical | Original | D | 6/14/2022 | DANIELG | DANIELG | Comply with previous review comment #2.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1697906 |
Electronic Plan | Original | / | 6/14/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1697855 |
Submittal 3 | Original | / | 6/9/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1695480 |
Electrical | Original | D | 5/26/2022 | DANIELG | DANIELG | 1. Comply with previous review comments 1, 2, and 3.
2. Provide listing from a NRTL for the fire pump controller and fire pump as a listed assembly. If not listed, then show compliance with 695.4(B)(2)(A)(1) NEC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1688663 |
Electronic Plan | Original | / | 5/26/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1688437 |
Submittal 2 | Original | / | 5/25/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1688228 |
Electrical | Original | D | 5/19/2022 | DANIELG | DANIELG | 1. Tap needs to comply with 695.3(A)(1). Tap cannot be located within the same cabinet, enclosure, vertical switchgear or switchboard section.
2. Specify SCA and SCCR for fire pump controller.
3. Specify number of poles for fire pump ATS.
4. Specify fire pump as SUSE and show main OCPD on one-line.
5. Comply 250.66 NEC. Show GEC in the fire pump controller.
6. Show compliance with 695.6(A)(1) and 230.6 NEC for fire pump service entrance conductors.
complete re-review.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1684787 |
Electronic Plan | Original | / | 5/17/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1683192 |
Electronic Plan | Original | / | 5/12/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1681633 |
CO Springs Fire | Original | N | 5/6/2022 | CSFIRE | CSFIRE | no fire final (see full review) | csfdit | CO Springs Fire | 1677907 |
CO Springs DRE | Original | N | 5/5/2022 | ESHAFER | ESHAFER | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy. (see full review) | | CO Springs DRE | 1677622 |
Zoning/Planning | Original | / | 5/5/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1677621 |
Construction | Original | N | 5/5/2022 | SHELLEY | SHELLEY | No construction work. | | Construction | 1677364 |
Enumeration | Original | N | 4/29/2022 | BECKYA | BECKYA | | | Enumeration | 1673607 |
Floodplain | Original | N | 4/28/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6406108027) | | Floodplain | 1672797 |