Electrical | Original | A | 7/1/2022 | SHELBY | SHELBY | | | Electrical | 1707801 |
Electronic Plan | Original | / | 7/1/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1707788 |
Submittal 3 | Original | / | 7/1/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1707337 |
Electrical | Original | D | 6/20/2022 | SHELBY | SHELBY | Please address previous review comment 1. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1701280 |
Electronic Plan | Original | / | 6/20/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1701279 |
Submittal 2 | Original | / | 6/9/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1695743 |
Electrical | Original | D | 6/1/2022 | SHELBY | SHELBY | 1. Please provide a load calculation for CP1-GEN-DP. 2. Add a note acknowledging the need for a coordination study per 517.31 (G) NEC prior to final inspection. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1691018 |
Electronic Plan | Original | / | 5/31/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1689980 |
Electronic Plan | Original | / | 5/20/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1685902 |
Electronic Plan | Original | / | 5/19/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1684788 |
CO Springs Fire | Original | N | 5/6/2022 | CSFIRE | CSFIRE | no fire final (see full review) | csfdit | CO Springs Fire | 1677919 |
CO Springs DRE | Original | N | 5/5/2022 | ESHAFER | ESHAFER | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy. (see full review) | | CO Springs DRE | 1677619 |
Zoning/Planning | Original | / | 5/5/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1677618 |
Construction | Original | N | 5/5/2022 | SHELLEY | SHELLEY | No construction work. | | Construction | 1677369 |
Enumeration | Original | N | 5/4/2022 | AMY | AMY | | | Enumeration | 1676594 |
Electronic Plan | Original | / | 5/4/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1676591 |
Floodplain | Original | N | 5/3/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6406108027) | | Floodplain | 1675233 |