CO Springs DRE | Original | A | 8/5/2022 | PLANGE | PLANGE | Building plans comply with approved plans for DP16-00821MM01. (see full review) | | CO Springs DRE | 1724136 |
Zoning/Planning | Original | A | 8/5/2022 | PLANGE | PLANGE | Building plans comply with approved plans for DP16-00821MM01. | | Zoning/Planning | 1724132 |
Submittal 4 | Original | / | 8/5/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1724089 |
CO Springs DRE | Original | D | 8/5/2022 | PLANGE | PLANGE | Please upload the approved Minor Modification application materials as part of the building permit resubmittal. (see full review) | | CO Springs DRE | 1724068 |
Zoning/Planning | Original | D | 8/5/2022 | PLANGE | PLANGE | Please upload the approved Minor Modification application materials as part of the building permit resubmittal. | | Zoning/Planning | 1724065 |
Electrical | Original | A | 7/28/2022 | DANIELG | DANIELG | | | Electrical | 1720285 |
Electronic Plan | Original | / | 7/28/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1720207 |
Submittal 3 | Original | / | 7/28/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1719832 |
CO Springs Hazmat | Original | N | 7/13/2022 | CSFIRE | CSFIRE | HazMat N/A - DCT (see full review) | DTillery94 | CO Springs Hazmat | 1712887 |
CO Springs Fire | Original | A | 7/12/2022 | CSFIRE | CSFIRE | Submitted By: Watson, Jacob Thomas
You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1711868 |
CO Springs DRE | Original | D | 7/6/2022 | AODOM | AODOM | please request a pre-app meeting below to discuss changes with a planner https://coloradosprings.gov/planning-and-development/webform/pre-application-meeting-request (see full review) | | CO Springs DRE | 1708631 |
Zoning/Planning | Original | / | 7/1/2022 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1707631 |
Electrical | Original | D | 7/1/2022 | DANIELG | DANIELG | 1. Comply with previous review comment #2.
2. Provide SCA for new panel B.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1707374 |
Mechanical | Original | A | 7/1/2022 | JUSTINC | JUSTINC | | | Mechanical | 1707338 |
Electronic Plan | Original | / | 7/1/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1707329 |
Construction | Original | A | 7/1/2022 | BPHILLIPS | BPHILLIPS | | | Construction | 1707253 |
Electronic Plan | Original | / | 7/1/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1707252 |
Submittal 2 | Original | / | 6/30/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1706764 |
CO Springs Fire | Original | D | 5/31/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | rpeterson | CO Springs Fire | 1690327 |
CO Springs Hazmat | Original | D | 5/31/2022 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1690325 |
Plumbing | Original | A | 5/25/2022 | SHANEN | SHANEN | | | Plumbing | 1687549 |
Electrical | Original | D | 5/23/2022 | DANIELG | DANIELG | 1. Provide SCA and SCCR for CU-1.
2. Provide conductor size, type, and quantity for the scope of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1686077 |
Electronic Plan | Original | / | 5/23/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1686062 |
Mechanical | Original | D | 5/20/2022 | JUSTINC | JUSTINC | No alternates on permit set Clarify condensate removal Provide refrigeration calculation per 2015 IMC 1103.1 Verify if within allowable limits per table on plan. If over the allowable limits indicate how protecting on plan.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1685706 |
Electronic Plan | Original | / | 5/20/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1685695 |
Health Dept. | Original | A | 5/20/2022 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. Water recreation plan review application received, but final approval not required for building permit or Certificate of Occupancy. KM | kmaldonado | Health Dept. | 1685632 |
CSU Water | Original | N | 5/20/2022 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 1685618 |
CSU Waste Water | Original | N | 5/20/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 1685616 |
CO Springs DRE | Original | D | 5/20/2022 | ACOOPER | ACOOPER | Show which direction elevation on sheet A-301 is facing (see full review) | | CO Springs DRE | 1685567 |
Zoning/Planning | Original | / | 5/20/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1685562 |
Electronic Plan | Original | / | 5/20/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1685561 |
Construction | Original | A | 5/20/2022 | BPHILLIPS | BPHILLIPS | | | Construction | 1685530 |
Electronic Plan | Original | / | 5/20/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1685283 |
Enumeration | Original | N | 5/18/2022 | AMY | AMY | | | Enumeration | 1684119 |
Electronic Plan | Original | / | 5/18/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1684111 |
Floodplain | Original | N | 5/17/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5318220016) | | Floodplain | 1683319 |