CO Springs Fire | Splice 03/09/23 | A | 3/10/2023 | CSFIRE | CSFIRE | details for duct wrapping (see full review) | Jacob.Watson | CO Springs Fire | 1814557 |
Mechanical | Splice 03/09/23 | A | 3/9/2023 | JUSTINC | JUSTINC | Revised for field applied shaft with duct wrap | | Mechanical | 1813896 |
Electronic Plan | Splice 03/09/23 | / | 3/9/2023 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1813875 |
Construction | Splice 03/09/23 | A | 3/9/2023 | SHELLEY | SHELLEY | Shaft wrap continuity. | | Construction | 1813871 |
Construction | Splice 11/02/22 | A | 12/22/2022 | SHELLEY | SHELLEY | After further review and consult, 3M wrap is ok for use with duct. Approved splice.
Revised details for duct from basement through roof, and minor floor plan change. | | Construction | 1784599 |
Construction | Splice 11/02/22 | D | 12/22/2022 | SHELLEY | SHELLEY | Provide a Fire Protection Engineer letter qualifying the use of duct wrap approved only for use with grease ducts in this application. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1784582 |
Submittal 3 | Splice 11/02/22 | / | 12/21/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1784404 |
Mechanical | Splice 11/02/22 | A | 12/5/2022 | JUSTINC | JUSTINC | exhaust revisions | | Mechanical | 1777866 |
Construction | Splice 11/02/22 | D | 12/2/2022 | SHELLEY | SHELLEY | Previous comment not addressed. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1777323 |
Submittal 2 | Splice 11/02/22 | / | 12/2/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1777253 |
CO Springs Fire | Splice 11/02/22 | N | 11/4/2022 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 1766587 |
Mechanical | Splice 11/02/22 | D | 11/3/2022 | JUSTINC | JUSTINC | Splice is showing the basement level of the shaft to be removed. Original mechanical plans indicate this a chase. This is a rated shaft and will need compliant penetration protection. Provide revised (M) sheet showing how this shaft and and all penetrations with it will be protected.
MECHANICAL REVIEW INCOMPLETE
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1765442 |
Construction | Splice 11/02/22 | D | 11/3/2022 | SHELLEY | SHELLEY | Clarify how bottom of shaft is being protected if shaft if stopping at 1st floor. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1765440 |
CO Springs Fire | Splice 10/26/22 | A | 10/27/2022 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 1762166 |
Construction | Splice 10/26/22 | A | 10/26/2022 | SHELLEY | SHELLEY | Added gas fireplace | | Construction | 1762049 |
Electrical | Splice 09/08/22 | A | 9/17/2022 | SHELBY | SHELBY | | | Electrical | 1742661 |
Electronic Plan | Splice 09/08/22 | / | 9/17/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1742660 |
Mechanical | Splice 09/08/22 | A | 9/9/2022 | JUSTINC | JUSTINC | Layout revisions | | Mechanical | 1739204 |
Electronic Plan | Splice 09/08/22 | / | 9/9/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1739189 |
Electrical | Splice 07/20/22 | A | 7/30/2022 | SHELBY | SHELBY | | | Electrical | 1721063 |
Electronic Plan | Splice 07/20/22 | / | 7/30/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1721062 |
CO Springs Fire | Splice 07/20/22 | A | 7/21/2022 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1716688 |
Mechanical | Splice 07/20/22 | A | 7/20/2022 | JUSTINC | JUSTINC | Layout revised | | Mechanical | 1716457 |
Plumbing | Splice 07/20/22 | A | 7/20/2022 | SHANEN | SHANEN | Delta 5 revisions: Adjusted sheet PD1.1.1, P1.1.1 and P2.1.1. | | Plumbing | 1716444 |
Construction | Splice 07/20/22 | A | 7/20/2022 | SHELLEY | SHELLEY | Removed furred wall, misc. details, and framing for penetration. | | Construction | 1716431 |
Electrical | Original | A | 7/1/2022 | SHELBY | SHELBY | | | Electrical | 1707808 |
Electronic Plan | Original | / | 7/1/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1707806 |
CO Springs DRE | Original | A | 6/30/2022 | ESHAFER | ESHAFER | Interior finish only: No change in footprint, No change to exterior, No change in parking, No change in occupancy. (see full review) | | CO Springs DRE | 1706699 |
Plumbing | Original | A | 6/29/2022 | SHANEN | SHANEN | | | Plumbing | 1706261 |
Construction | Original | A | 6/29/2022 | SHELLEY | SHELLEY | | | Construction | 1706243 |
Enumeration | Original | A | 6/27/2022 | BECKYA | BECKYA | | | Enumeration | 1705060 |
Submittal 3 | Original | / | 6/27/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1704873 |
Electrical | Original | D | 6/21/2022 | SHELBY | SHELBY | 1. Please provide load justification for CP1-GEN-DP , EBBNMDC, EBBEMDC. 2. For transformers CL2 and NL2 the supply side bonding jumpers and grounding electrode conductors are incorrect. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1702157 |
Electronic Plan | Original | / | 6/21/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1702156 |
Plumbing | Original | D | 6/20/2022 | SHANEN | SHANEN | If kitchen sink is to be substituted for half of the required drinking fountains, the existence and location of the other half of the required drinking fountains must be noted. Note: Drinking fountain shall be ANSI A117.1-2009 compliant. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1700591 |
Mechanical | Original | A | 6/17/2022 | JUSTINC | JUSTINC | | | Mechanical | 1700278 |
CO Springs DRE | Original | A | 6/17/2022 | ESHAFER | ESHAFER | Interior finish only: No change in footprint, No change to exterior, No change in parking, No change in occupancy. (see full review) | | CO Springs DRE | 1700155 |
Construction | Original | A | 6/17/2022 | SHELLEY | SHELLEY | | | Construction | 1700078 |
Enumeration | Original | A | 6/16/2022 | BECKYA | BECKYA | | | Enumeration | 1699437 |
Submittal 2 | Original | / | 6/16/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1699337 |
CSU Contract Admin. | Original | N | 6/9/2022 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees for this plan set.
AMS | ASweet | CSU Contract Admin. | 1695281 |
CO Springs Hazmat | Original | N | 6/8/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1694622 |
CO Springs Fire | Original | A | 6/8/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1694621 |
Construction | Original | D | 6/3/2022 | DANM | DANM | Provide reason for rated walls throughout on Life Safety Plan - identify if fire barriers or fire partitions or smoke barriers. Travel distances on Life Safety Plan do not seem to match Egress Travel Summary Table. Only one listing allowed for fire-resistance-rated wall P1A.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1692053 |
Electronic Plan | Original | / | 6/3/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1692049 |
CO Springs DRE | Original | A | 6/2/2022 | ESHAFER | ESHAFER | Interior finish only: No change in footprint, No change to exterior, No change in parking, No change in occupancy. (see full review) | | CO Springs DRE | 1691612 |
City Engr | Original | N | 5/27/2022 | PMORRIS | PMORRIS | | | City Engr | 1689407 |
Health Dept. | Original | N | 5/26/2022 | HEALTHDEPT | HEALTHDEPT | Not applicable. AF | Amanda Furno | Health Dept. | 1688667 |
Electrical | Original | D | 5/25/2022 | SHELBY | SHELBY | 1. Show conductor size, type, and quantity between transformers and disconnect. 2. Please provide load calculation for EBBNH1, EBBNMDC, CP1-GEN-DP, AND EBBEMDC. 3. Use 2015 IECC. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1688285 |
CSU Water | Original | N | 5/25/2022 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 1688089 |
CSU Waste Water | Original | N | 5/25/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 1688088 |
Gas/Elec. Utils | Original | A | 5/25/2022 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 1688087 |
Zoning/Planning | Original | / | 5/25/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1687957 |
Plumbing | Original | D | 5/25/2022 | SHANEN | SHANEN | Provide an occupant load to fixture count analysis to verify compliance with section 403.1 Minimum number of fixtures. A high/low drinking fountain is a required fixture, note if it is existing/provided in the common areas. Provide water pipe size analysis data for the added plumbing fixtures, see 2018 IPC appendix E (calculations may be taken from the point of connection). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1687914 |
Mechanical | Original | D | 5/25/2022 | JUSTINC | JUSTINC | This has been indicated as a rated SHAFT not CHASEClarify how protecting penetration without using a damper in hazardous exhaust How protecting thru penetration to 4th floor? Provide ventilation schedules per 2015 IMC 403.3.1.1
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1687899 |
Electronic Plan | Original | / | 5/25/2022 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1687894 |
Construction | Original | D | 5/25/2022 | DANM | DANM | G sheets appear to be missing - specify codes used, code data, occupant load calculations and Life Safety Plan. Provide reason for rated corridor walls - identify if fire barriers or fire partitions - OK to show on Life Safety Plan. Only one listing allowed for fire-resistance-rated wall P1A.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1687850 |
Electronic Plan | Original | / | 5/25/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1687621 |
Elevators | Original | N | 5/25/2022 | ERIC | ERIC | No conveyance | | Elevators | 1687617 |
Electronic Plan | Original | / | 5/25/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1687538 |
Enumeration | Original | A | 5/25/2022 | BECKYA | BECKYA | Pharmacy is relocating. | | Enumeration | 1687527 |
Floodplain | Original | N | 5/23/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6406108027) | | Floodplain | 1686691 |