CO Springs Fire | Splice 10/09/23 | N | 10/10/2023 | CSFIRE | CSFIRE | No Fire Final | phil.valdez | CO Springs Fire | 1911641 |
Construction | Splice 10/09/23 | A | 10/9/2023 | DANM | DANM | Clarifying an ADA unit being marked as such on the Architectural and General Code plans. | | Construction | 1910948 |
Electronic Plan | Splice 10/09/23 | / | 10/9/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1910947 |
CO Springs Fire | Splice 08/04/23 | N | 8/7/2023 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman (see full review) | csfdit | CO Springs Fire | 1881306 |
Construction | Splice 08/04/23 | A | 8/4/2023 | DANM | DANM | Removing (closing off) some exterior doors that are not required for egress | | Construction | 1880298 |
Electronic Plan | Splice 08/04/23 | / | 8/4/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1880284 |
CO Springs Fire | Splice 08/02/23 | N | 8/3/2023 | CSFIRE | CSFIRE | Submitted By: Withee, Doreen E,Submitted By: Withee, Doreen E (see full review) | csfdit | CO Springs Fire | 1879621 |
Construction | Splice 08/02/23 | A | 8/2/2023 | DANM | DANM | Change infill wall construction between units from CMU construction to fire-retardant-treated wood with new listed assembly | | Construction | 1879054 |
Electronic Plan | Splice 08/02/23 | / | 8/2/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1879037 |
CO Springs Fire | Splice 07/18/23 | N | 7/19/2023 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1872236 |
Construction | Splice 07/18/23 | A | 7/18/2023 | DANM | DANM | Existing doors between units removed | | Construction | 1872176 |
Construction | Splice 07/18/23 | D | 7/18/2023 | DANM | DANM | This splice cannot be approved until a building permit is pulled 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1871818 |
Electronic Plan | Splice 07/18/23 | / | 7/18/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1871665 |
Electrical | Original | A | 8/3/2022 | SHELBY | SHELBY | | | Electrical | 1723167 |
Submittal 5 | Original | / | 8/3/2022 | KALLISTAJ | KALLISTAJ | Submittal #5 | | Submittal 5 | 1723026 |
Electrical | Original | D | 8/2/2022 | DANIELG | DANIELG | Per conversation with the engineer Marc Remmert.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1722700 |
Submittal 4 | Original | / | 7/29/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1720968 |
Electrical | Original | D | 7/13/2022 | DANIELG | DANIELG | The FLA for each transformer in this scope of work has been exceeded.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1712950 |
Electronic Plan | Original | / | 7/13/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1712929 |
Submittal 3 | Original | / | 7/13/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1712882 |
Electrical | Original | D | 7/7/2022 | DANIELG | DANIELG | Comply with previous review comment # 1.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1709685 |
Electronic Plan | Original | / | 7/7/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1709626 |
Construction | Original | A | 7/7/2022 | DANM | DANM | | | Construction | 1709498 |
Electronic Plan | Original | / | 7/7/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1709340 |
Submittal 2 | Original | / | 6/30/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1706943 |
Plumbing | Original | N | 6/15/2022 | TCRIPPEN | TCRIPPEN | No plumbing, | | Plumbing | 1698853 |
Electrical | Original | D | 6/14/2022 | DANIELG | DANIELG | 1. Provide panel schedule for all panels in this scope of work.
2. Show OCPD's on the one-line.
3. Show KVA of each transformer on the one-line.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1697930 |
Electronic Plan | Original | / | 6/10/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1696572 |
CO Springs DRE | Original | N | 6/8/2022 | KDODGE | KDODGE | Interior remodel, commercial, no change of use or occupancy. electrical only in west wing. (see full review) | | CO Springs DRE | 1694757 |
Construction | Original | D | 6/7/2022 | DANM | DANM | Upon further review, clarify ADA kitchenette shown on drawings.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1694222 |
CO Springs Hazmat | Original | N | 6/7/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1693916 |
CO Springs Fire | Original | N | 6/7/2022 | CSFIRE | CSFIRE | no fire final (see full review) | csfdit | CO Springs Fire | 1693912 |
Mechanical | Original | N | 6/7/2022 | DALEH | DALEH | | | Mechanical | 1693875 |
Stratmoor Hills Water | Original | D | 6/7/2022 | STRATMOORWSD | STRATMOORWSD | This is not in our district. It belongs to CSU | nancy@stratmoorhills | Stratmoor Hills Water | 1693803 |
Stratmoor Hills Waste Water | Original | D | 6/7/2022 | STRATMOORWSD | STRATMOORWSD | This is not in our water district it belongs to CSU | nancy@stratmoorhills | Stratmoor Hills Waste Water | 1693802 |
Construction | Original | D | 6/6/2022 | DANM | DANM | All disciplines for scope of work for Central Wing and North Wing should be combined (e.g., previous plumbing submittal and current electrical submittal). Clarify ADA kitchenette shown on drawings. Clarify use of what appears to be two under counter outlets in guest rooms. Not installing cabinets as part of the scope of work will make it difficult for inspectors to establish code compliance.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1693626 |
Electronic Plan | Original | / | 6/3/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1691966 |
Electronic Plan | Original | / | 6/3/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1691948 |
Enumeration | Original | N | 5/31/2022 | BECKYA | BECKYA | Scope is for the west wing. We added a site map to the first page of the electrical plans. | | Enumeration | 1690281 |
Electronic Plan | Original | / | 5/27/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1689381 |
Floodplain | Original | N | 5/25/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6429408015) | | Floodplain | 1688229 |