Out to Review | Splice 03/30/23 | / | 3/30/2023 | SYDNEYB | SYDNEYB | Holliday | | Out to Review | 1823329 |
Plan Coordinator (Main) | Splice 03/30/23 | / | 3/30/2023 | | RICHG | Location = Plan Coordinator (Main) by RICHG | | Plan Coordinator (Main) | 1823322 |
Electrical | Splice 03/30/23 | A | 3/30/2023 | RICHG | RICHG | | | Electrical | 1823321 |
Construction | Splice 03/09/23 | A | 3/9/2023 | CHRISTINEH | CHRISTINEH | Provided stamped detail for damper/doorway transition | | Construction | 1814144 |
Out to Review | Splice 03/09/23 | / | 3/9/2023 | NELIDA | NELIDA | Chuck 719-287-7600 | | Out to Review | 1814125 |
Mechanical | Splice 02/28/23 | A | 2/28/2023 | TCRIPPEN | TCRIPPEN | Approved. | | Mechanical | 1808319 |
Out to Review | Splice 02/28/23 | / | 2/28/2023 | NELIDA | NELIDA | 719-287-7600 Chuck | | Out to Review | 1808306 |
CO Springs Fire | Original | A | 9/14/2022 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | csfdit | CO Springs Fire | 1740944 |
Construction | Original | A | 9/14/2022 | MICHAELA | MICHAELA | | | Construction | 1740778 |
Enumeration | Original | A | 9/13/2022 | BECKYA | BECKYA | | | Enumeration | 1740737 |
Submittal 5 | Original | / | 9/13/2022 | BECKYA | BECKYA | Submittal #5 | | Submittal 5 | 1740642 |
CO Springs Fire | Original | D | 9/12/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1739919 |
Mechanical | Original | A | 8/30/2022 | DALEH | DALEH | | | Mechanical | 1735377 |
Construction | Original | D | 8/30/2022 | MICHAELA | MICHAELA | A0.1 - This will be the final approved plan set. You need to add back all of the notes regarding travel distance. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1735265 |
Enumeration | Original | A | 8/26/2022 | BECKYA | BECKYA | | | Enumeration | 1734385 |
Submittal 4 | Original | / | 8/26/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1734282 |
CO Springs Fire | Original | A | 8/26/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1734176 |
Mechanical | Original | D | 8/9/2022 | DALEH | DALEH | Indicate fire damper locations at penetration of new rated wall See plan for better clarity to comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1725487 |
Construction | Original | A | 8/9/2022 | MICHAELA | MICHAELA | | | Construction | 1725213 |
Enumeration | Original | A | 8/9/2022 | BECKYA | BECKYA | Tenant owns both suites 230 and 240, using 240 as business address. | | Enumeration | 1725200 |
Submittal 3 | Original | / | 8/8/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1724788 |
CO Springs Fire | Original | D | 8/5/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1724283 |
Mechanical | Original | D | 7/25/2022 | DALEH | DALEH | Waiting for Construction comments Revise Mechanical as needed
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1718082 |
Electrical | Original | A | 7/21/2022 | DANIELG | DANIELG | | | Electrical | 1716639 |
Electronic Plan | Original | / | 7/21/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1716634 |
Construction | Original | D | 7/20/2022 | MICHAELA | MICHAELA | If you choose not to take advantage of computing the occupant load for the training room using the number of chairs and the speaker area, 36 chairs = 36 occ.111 SF/20 = 6 occ.Total 42 occ. which would result in a B occupancy, and use your method creating an A occupancy, you will need to provide height and area calculations for the change of occupancy and prove that the A occupancy can work in a non-separated, non-sprinklered structure. If you choose to separate it you will need to provide fire barriers and sum of the ratios calculations. A1.0 - Per the Life Safety Plan this is the path of the rated corridor. Clarify purpose of wall indicated as rated where no IBC purpose seems to exist. If being rated for other than the IBC indicate that on the plan. If this is to separate the A occupancy it must be done with Fire Barriers not partitions. Code Study - Clarify occupancy separation and indicate change of occupancy. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1716119 |
Enumeration | Original | N | 7/18/2022 | BECKYA | BECKYA | Tenant owns both suites, using 240 as business address. | | Enumeration | 1714994 |
Electronic Plan | Original | / | 7/18/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1714958 |
Submittal 2 | Original | / | 7/18/2022 | ANDREAL | ANDREAL | Submittal #2 | | Submittal 2 | 1714767 |
CO Springs Hazmat | Original | N | 6/27/2022 | CSFIRE | CSFIRE | no fire final | phil.valdez | CO Springs Hazmat | 1704492 |
CO Springs Fire | Original | A | 6/27/2022 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren
You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | csfdit | CO Springs Fire | 1704366 |
CO Springs Fire | Original | A | 6/27/2022 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren
You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | csfdit | CO Springs Fire | 1704358 |
CO Springs DRE | Original | N | 6/23/2022 | ESHAFER | ESHAFER | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy (see full review) | | CO Springs DRE | 1702916 |
Plumbing | Original | N | 6/15/2022 | TCRIPPEN | TCRIPPEN | No plumbing. | | Plumbing | 1699030 |
Zoning/Planning | Original | / | 6/14/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1698201 |
Electrical | Original | D | 6/14/2022 | DANIELG | DANIELG | Pending enumeration approval.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1697958 |
Electronic Plan | Original | / | 6/14/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1697938 |
Mechanical | Original | D | 6/13/2022 | DALEH | DALEH | See Construction plan review comments on this area revise as required Show how protecting all penetrations through new rated corridor to include existing duct Label all rooms usage Must show on plan where the tie in occurs from existing duct to new Show existing duct as dotted typical See plans for better clarity to comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1697470 |
CSU Waste Water | Original | N | 6/13/2022 | CSUREVIEW | CSUREVIEW | No plumbing work. CM | CoreyM | CSU Waste Water | 1697400 |
CSU Water | Original | N | 6/13/2022 | CSUREVIEW | CSUREVIEW | No plumbing work. CM | CoreyM | CSU Water | 1697399 |
Construction | Original | D | 6/13/2022 | MICHAELA | MICHAELA | Comply with all requirements of the Life Safety Plan policy. Occupant load factor would be 1:20 for a classroom or the number of chairs. If less than 50 it would be a B occupancy. Layout of existing stair door location does not match RBD records. Provide a listed assembly for a 1-hr corridor fire partition. Label all rooms as to use. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1697048 |
Electronic Plan | Original | / | 6/6/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1693329 |
Enumeration | Original | D | 6/6/2022 | BECKYA | BECKYA | The permit history we have for this building is old, provide current suite layout and show which suites are unoccupied/vacant.
Please pick which suite number will be used as business address, cannot have two different suite numbers. If using 230, then this project will be considered a Commercial Remodel. If using 240, then this would be considered a commercial finish to create a new suite. Update all plans (including the Code Study Form) to show which suite number will be used.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1692935 |
Electronic Plan | Original | / | 6/6/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1692805 |
Floodplain | Original | N | 5/26/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5318220005) | | Floodplain | 1688618 |