Black Forest Hazmat (CSFD) | Original | N | 8/17/2022 | CSFIRE | CSFIRE | N/A | phil.valdez | Black Forest Hazmat (CSFD) | 1729177 |
Black Forest Fire (CSFD) | Original | A | 8/10/2022 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren
You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded | csfdit | Black Forest Fire (CSFD) | 1726456 |
Gas/Elec. Utils | Original | D | 8/10/2022 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' electric service territory. Not in Colorado Springs Utilities' gas service territory. MLW | mlwilliams | Gas/Elec. Utils | 1725915 |
Mechanical | Original | N | 8/8/2022 | DALEH | DALEH | | | Mechanical | 1724749 |
Gas/Elec. Utils | Original | D | 8/5/2022 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' electric service territory. Not in Colorado Springs Utilities' gas service territory. MLW | mlwilliams | Gas/Elec. Utils | 1724277 |
Electrical | Original | A | 8/5/2022 | BERTHA | BERTHA | | | Electrical | 1724167 |
Electronic Plan | Original | / | 8/5/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1724164 |
Plumbing | Original | N | 8/5/2022 | SHANEN | SHANEN | U occupancy. No connections to sewer or water service indicated. | | Plumbing | 1723969 |
Construction | Original | A | 8/5/2022 | BPHILLIPS | BPHILLIPS | | | Construction | 1723959 |
Electronic Plan | Original | / | 8/5/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1723958 |
Submittal 3 | Original | / | 8/4/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1723666 |
Black Forest Fire (CSFD) | Original | D | 8/4/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | Black Forest Fire (CSFD) | 1723588 |
Electrical | Original | D | 8/2/2022 | BERTHA | BERTHA | Comply with previous review comment #3
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1722261 |
Electronic Plan | Original | / | 8/2/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1722195 |
Plumbing | Original | D | 8/1/2022 | SHANEN | SHANEN | Floor drain (FD1) discharging to daylight does not comply with section 301.3 Connections to drainage system. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1721831 |
Mechanical | Original | D | 8/1/2022 | DALEH | DALEH | If this louver is located on the door Architect needs to show this on the door schedule, so that Mechanical can N/A this Mechanical submittal (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1721323 |
County Water | Original | D | 8/1/2022 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | County Water | 1721285 |
County Waste Water | Original | D | 8/1/2022 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | County Waste Water | 1721284 |
Gas/Elec. Utils | Original | D | 8/1/2022 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 1721283 |
Construction | Original | A | 8/1/2022 | BPHILLIPS | BPHILLIPS | | | Construction | 1721220 |
Electronic Plan | Original | / | 8/1/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1721204 |
Submittal 2 | Original | / | 7/29/2022 | STEPHANIEV | STEPHANIEV | Submittal #2 | | Submittal 2 | 1720623 |
CSU Contract Admin. | Original | N | 6/27/2022 | CSUAPPSPRM | CSUAPPSPRM | Gas only service territory, no fees/charges due. AG | aguerin | CSU Contract Admin. | 1704949 |
Black Forest Hazmat (CSFD) | Original | N | 6/27/2022 | CSFIRE | CSFIRE | | dwithee | Black Forest Hazmat (CSFD) | 1704885 |
Black Forest Fire (CSFD) | Original | D | 6/27/2022 | CSFIRE | CSFIRE | 1. Incomplete submittal per RBD - missing architectural plans
2. Missing mechanical plans - Reference 2019 NFPA 20 Standard for Fire Pumps: 4.14.3 - an approved or listed source of heat shall be provided for maintaining the tempurature of a pump roomor pump house...above 40 degrees.
3. Pump rooms shall be provided iwth emergency lighting - 4.14.5 of NFPA 20
4. Provision shall be made for ventilation of a pump room or pump house - 4.14.6 NFPA 20.
5. Floors shall be pitched for adequate drainage of escaping water from critical equipment... 4.14.7.1 NFPA 20
6. Pump house shall be provided with a floor drain that will discharge to a frost free location 4.14.7.2 | csfdit | Black Forest Fire (CSFD) | 1704883 |
Electrical | Original | D | 6/24/2022 | BERTHA | BERTHA | 1. Provide all conductor size, type and quantity on the one-line - fire pump and jockey pump
2. Provide listing for assembly listed for fire pump service.
3. Comply with 250.102(C)(1)
4. Provide fault current information (SCA, SCCR, AIC) in tabular form, for all new and re-fed electrical equipment including; panel boards, switchboards, service equipment, transfer equipment, elevator control panel, fire pump control panel, industrial control panels, air conditioning and refrigeration equipment. See terms and methodologies below.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1704072 |
Plumbing | Original | D | 6/23/2022 | SHANEN | SHANEN | Process piping plan must be provided to verify that there is no plumbing scope of work that requires a permit. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1702898 |
Electronic Plan | Original | / | 6/17/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1700272 |
Health Dept. | Original | N | 6/16/2022 | HEALTHDEPT | HEALTHDEPT | Not applicable (Concrete pump house) less than 1 acre. MT | mtemple | Health Dept. | 1699527 |
Mechanical | Original | D | 6/14/2022 | DALEH | DALEH | Plans are submitted as a conditioned building Provide Mechanical drawings as needed Exhaust fans ? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1698008 |
County Zoning | Original | A | 6/14/2022 | DSDRANGEL | DSDRANGEL | 4400 sq ft/1000 = 4.4 x 3180.00 = $13992.00 | | County Zoning | 1697753 |
County Waste Water | Original | D | 6/13/2022 | CSUREVIEW | CSUREVIEW | Because it was in our queue, and based on the communication Springs Utilities had with PPRBD, CSU was instructed to disapprove the plans in these cases so that PPRBD could forward them to the appropriate entity. In this case, it is better to speak with PPRBD. CM | CoreyM | County Waste Water | 1697711 |
County Water | Original | D | 6/13/2022 | CSUREVIEW | CSUREVIEW | Because it was in our queue, and based on the communication Springs Utilities had with PPRBD, CSU was instructed to disapprove the plans in these cases so that PPRBD could forward them to the appropriate entity. In this case, it is better to speak with PPRBD. CM | CoreyM | County Water | 1697710 |
Gas/Elec. Utils | Original | D | 6/13/2022 | CSUREVIEW | CSUREVIEW | Approved Development Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CM | CoreyM | Gas/Elec. Utils | 1697708 |
Zoning/Planning | Original | / | 6/13/2022 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1697691 |
Construction | Original | D | 6/13/2022 | BPHILLIPS | BPHILLIPS | Structural plan needs to reference soils report provided. Provide architectural drawings and IECC/Comcheck form. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1697679 |
Elevators | Original | N | 6/13/2022 | ERIC | ERIC | No conveyance | | Elevators | 1697449 |
Electronic Plan | Original | / | 6/13/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1697043 |
Enumeration | Original | A | 6/7/2022 | BRENT | BRENT | | | Enumeration | 1694346 |
Electronic Plan | Original | / | 6/7/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1694328 |
Floodplain | Original | N | 6/7/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5207000004) | | Floodplain | 1694213 |