CO Springs DRE | Original | A | 11/28/2022 | ACOOPER | ACOOPER | Approved per CM1 16-0070-A2MN22 (see full review) | | CO Springs DRE | 1775609 |
Zoning/Planning | Original | / | 11/23/2022 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1774746 |
Submittal 4 | Original | / | 11/21/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1773854 |
Electrical | Original | A | 11/21/2022 | BERTHA | BERTHA | | | Electrical | 1773726 |
Electronic Plan | Original | / | 11/21/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1773602 |
CO Springs DRE | Original | D | 11/21/2022 | ACOOPER | ACOOPER | Please upload approved development plan (see full review) | | CO Springs DRE | 1773427 |
Zoning/Planning | Original | / | 11/18/2022 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1773284 |
Submittal 3 | Original | / | 11/18/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1772814 |
Electrical | Original | D | 8/22/2022 | BERTHA | BERTHA | Comply with previous review comments
Provide conduit/conductor size, type, and quantity, beginning at the utility transformer, to include all conductors in the chain of supply for the electrical equipment in the scope of work
Provide information for ATS - number of poles, amperage, SCA and SCCR.
Provide KW for generator - compliance with 702.12 - 2020 NEC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1731768 |
Electronic Plan | Original | / | 8/22/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1731689 |
CO Springs DRE | Original | D | 8/22/2022 | ACOOPER | ACOOPER | Include approved DP (see full review) | | CO Springs DRE | 1731535 |
CO Springs Hazmat | Original | N | 8/19/2022 | CSFIRE | CSFIRE | no fire final | Jacob.Watson | CO Springs Hazmat | 1730716 |
CO Springs Fire | Original | N | 8/19/2022 | CSFIRE | CSFIRE | no fire final | Jacob.Watson | CO Springs Fire | 1730714 |
Zoning/Planning | Original | / | 8/18/2022 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1730178 |
Enumeration | Original | A | 8/18/2022 | BRENT | BRENT | | | Enumeration | 1729990 |
Electronic Plan | Original | / | 8/18/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1729980 |
Submittal 2 | Original | / | 8/15/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1728078 |
CO Springs Hazmat | Original | D | 7/19/2022 | CSFIRE | CSFIRE | PENDING RECEIPT OF REQURIED INFORMATION FROM FIRE CONSTRUCTION REVIEW | dwithee | CO Springs Hazmat | 1715854 |
CO Springs Fire | Original | D | 7/19/2022 | CSFIRE | CSFIRE | (DISAPPROVED) HAZARDOUS MATERIALS: Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2009 IFC Table 105.6.20. PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS, AND FILL OUT THE REQUESTED INFORMATION. All forms and packets are available at https://coloradosprings.gov/hazmat?mlid=42381
NOTE: YOU DID NOT PROVIDE ANY INFORMATION REGARDING THE ENERGY STORAGE SYSTEM (BATTERIES). WE NEED TO KNOW EITHER THE AGGREGATE ELECTROLYTE AMOUNT OR THE ENERGY CAPACITY IF LION BATTERIES. | dwithee | CO Springs Fire | 1715853 |
CO Springs DRE | Original | D | 7/13/2022 | ACOOPER | ACOOPER | Denied pending Minor amendment approval (see full review) | | CO Springs DRE | 1712997 |
Zoning/Planning | Original | / | 7/8/2022 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1710714 |
CSU Water | Original | N | 7/8/2022 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | CSU Water | 1710679 |
CSU Waste Water | Original | N | 7/8/2022 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | CSU Waste Water | 1710677 |
Mechanical | Original | N | 7/8/2022 | JUSTINC | JUSTINC | No new or revised mechanical scope indicated | | Mechanical | 1710263 |
Electrical | Original | D | 7/8/2022 | BERTHA | BERTHA | Provide conduit/conductor size, type, and quantity, beginning at the utility transformer, to include all conductors in the chain of supply for the electrical equipment in the scope of work
Provide location of new AC panel on site plan.
Provide information for ATS - number of poles, amperage, SCA and SCCR.
Provide KW for generator - compliance with 702.12 - 2020 NEC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1710256 |
Electronic Plan | Original | / | 7/8/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1710242 |
Construction | Original | N | 7/8/2022 | SHELLEY | SHELLEY | No construction work. | | Construction | 1710235 |
Enumeration | Original | D | 7/7/2022 | BRENT | BRENT | The address assigned for this AT&T installation is 2524 Arlington Dr. Update all plan pages and the code study form to show the correct address. The tax schedule number and legal description shown on the code study form are incorrect. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1709721 |
Electronic Plan | Original | / | 7/7/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1709710 |
Floodplain | Original | N | 7/1/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6428103031) | | Floodplain | 1707483 |