Electrical | Original | A | 10/21/2022 | SHELBY | SHELBY | | | Electrical | 1760333 |
Electronic Plan | Original | / | 10/21/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1760329 |
Submittal 3 | Original | / | 10/20/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1759416 |
Electrical | Original | D | 9/19/2022 | DANIELG | DANIELG | Please clarify. Utility meter and 30KW generator is indicated as new on one-line.
2. Remove ground from service conductors.
3. Provide SCA and AIC for panel ILC.
4. Show compliance with 445.18 NEC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1742916 |
Electronic Plan | Original | / | 9/19/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1742905 |
Submittal 2 | Original | / | 9/16/2022 | BPHILLIPS | BPHILLIPS | Submittal #2 | | Submittal 2 | 1742408 |
CO Springs DRE | Original | A | 7/22/2022 | PLANGE | PLANGE | Project complies with previous entitlement (AR CM3 18-00186MM01) (see full review) | | CO Springs DRE | 1717372 |
Mechanical | Original | N | 7/21/2022 | JUSTINC | JUSTINC | No new or revised mechanical scope indicated | | Mechanical | 1716975 |
CO Springs Hazmat | Original | N | 7/20/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1716467 |
CO Springs Fire | Original | N | 7/20/2022 | CSFIRE | CSFIRE | no fire final | csfdit | CO Springs Fire | 1716466 |
Electrical | Original | D | 7/18/2022 | DANIELG | DANIELG | Provide electrical plans. Adding load to panel PDF with two new 50A rectifiers.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1714614 |
Electronic Plan | Original | / | 7/18/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1714613 |
Zoning/Planning | Original | A | 7/15/2022 | PLANGE | PLANGE | Project complies with previous entitlement (AR CM3 18-00186MM01) | | Zoning/Planning | 1714326 |
CSU Water | Original | N | 7/15/2022 | CSUREVIEW | CSUREVIEW | No apparent conflicts. MLW | mlwilliams | CSU Water | 1714085 |
CSU Waste Water | Original | N | 7/15/2022 | CSUREVIEW | CSUREVIEW | No apparent conflicts. MLW | mlwilliams | CSU Waste Water | 1714083 |
Construction | Original | N | 7/14/2022 | SHELLEY | SHELLEY | No construction work. | | Construction | 1713978 |
Enumeration | Original | N | 7/14/2022 | BECKYA | BECKYA | | | Enumeration | 1713602 |
Electronic Plan | Original | / | 7/14/2022 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1713593 |
Floodplain | Original | N | 7/13/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6410101070) | | Floodplain | 1713125 |