Electrical | Original | A | 1/11/2023 | DANIELG | DANIELG | | | Electrical | 1790085 |
Submittal 5 | Original | / | 1/11/2023 | ANDREAL | ANDREAL | Submittal #5 | | Submittal 5 | 1790082 |
Electrical | Original | D | 1/10/2023 | DANIELG | DANIELG | Comply 240.4(B) NEC. Service lateral is undersized for 200A service.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1789740 |
Electronic Plan | Original | / | 1/10/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1789701 |
Submittal 4 | Original | / | 1/9/2023 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1789447 |
Electrical | Original | D | 1/5/2023 | DANIELG | DANIELG | Provide conductor size, type, and quantity for service lateral.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1788318 |
Electrical | Original | D | 11/9/2022 | BERTHA | BERTHA | Submit revised plans - per walk through consultation with Dana.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1768756 |
Submittal 3 | Original | / | 11/9/2022 | ANDREAL | ANDREAL | Submittal #3 | | Submittal 3 | 1768698 |
CO Springs DRE | Original | A | 10/18/2022 | MALCURAN | MALCURAN | Approved per plans date stamped 5/20/2022 under AR CM3 22-00231.....MDA.... Please email City Planning when the final Zoning inspection is ready. | | CO Springs DRE | 1758301 |
Electrical | Original | D | 10/11/2022 | DANIELG | DANIELG | 1. Specify where the service disconnecting means is located.
2. Show the size of the GEC on the one-line.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1754557 |
Electronic Plan | Original | / | 10/11/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1754543 |
Zoning/Planning | Original | / | 10/10/2022 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1753499 |
Enumeration | Original | A | 10/10/2022 | BECKYA | BECKYA | | | Enumeration | 1753458 |
Submittal 2 | Original | / | 10/7/2022 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1752798 |
CO Springs DRE | Original | D | 10/6/2022 | MALCURAN | MALCURAN | Disapproved. Please upload and label the City's Land Use Review approved plan set. | | CO Springs DRE | 1752365 |
Mechanical | Original | N | 8/23/2022 | DALEH | DALEH | | | Mechanical | 1732219 |
Electrical | Original | D | 8/22/2022 | DANIELG | DANIELG | 1. Remove ground from service conductors.
2. Show compliance with 250.66 NEC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1731523 |
Electronic Plan | Original | / | 8/22/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1731519 |
Zoning/Planning | Original | / | 8/19/2022 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1731110 |
CSU Water | Original | N | 8/19/2022 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSM | stefanm | CSU Water | 1731000 |
CSU Waste Water | Original | N | 8/19/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSM | stefanm | CSU Waste Water | 1730998 |
CO Springs Hazmat | Original | N | 8/19/2022 | CSFIRE | CSFIRE | no fire final | Jacob.Watson | CO Springs Hazmat | 1730926 |
CO Springs Fire | Original | N | 8/19/2022 | CSFIRE | CSFIRE | no fire final | Jacob.Watson | CO Springs Fire | 1730923 |
Construction | Original | N | 8/19/2022 | MICHAELA | MICHAELA | | | Construction | 1730403 |
Enumeration | Original | D | 8/18/2022 | BECKYA | BECKYA | Each carrier on a tower is assigned a separate address. The address that was provided for Dish Wireless was 1509 Pecan Street, Unit C. Please change all pages to this address.
Also, this is a new carrier attaching to an existing tower but the carrier is new; therefore, this is not a modification plan. Description has been changed to New Cell Site.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1730171 |
Floodplain | Original | N | 7/26/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7414301027) | | Floodplain | 1718851 |