Electrical | Original | A | 4/12/2023 | DANIELG | DANIELG | | | Electrical | 1829082 |
Electronic Plan | Original | / | 4/12/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1829068 |
Submittal 3 | Original | / | 4/12/2023 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 1828951 |
County Zoning | Original | N | 3/22/2023 | DSDRANGEL | DSDRANGEL | | | County Zoning | 1819533 |
CO Springs Hazmat | Original | A | 3/22/2023 | CSFIRE | CSFIRE | Diesel tank is a deferred submittal to CSFD (see full review) | Jacob.Watson | CO Springs Hazmat | 1819389 |
CO Springs Fire | Original | N | 3/22/2023 | CSFIRE | CSFIRE | review forwarded to HazMat | Jacob.Watson | CO Springs Fire | 1819363 |
Electrical | Original | D | 3/22/2023 | DANIELG | DANIELG | Provide load calculation for existing panel.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1819274 |
Electronic Plan | Original | / | 3/22/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1819263 |
County Water | Original | D | 3/21/2023 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities water service territory. mjg | mgackle | County Water | 1819032 |
County Waste Water | Original | D | 3/21/2023 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities wastewater service territory. mjg | mgackle | County Waste Water | 1819031 |
Submittal 2 | Original | / | 3/21/2023 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1819008 |
County Zoning | Original | D | 9/20/2022 | DSDRANGEL | DSDRANGEL | Project required through EPC Planning. Contact the planner of the day at 719-520-6944 or via e-mail at dsd-pod@elpasoco.com for project set up. | | County Zoning | 1743838 |
CO Springs Fire | Original | D | 9/19/2022 | CSFIRE | CSFIRE | REFERENCE DIESEL GENERATOR Provide completed Hazardous Materials Operations Triage form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility.
Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2009 IFC Table 105.6.20.
PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS, AND FILL OUT THE REQUESTED INFORMATION.
All forms and packets are available at https://coloradosprings.gov/hazmat?mlid=42381 | jt09ff | CO Springs Fire | 1743482 |
CO Springs Hazmat | Original | D | 9/19/2022 | CSFIRE | CSFIRE | REFERENCE DIESEL GENERATOR Provide completed Hazardous Materials Operations Triage form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility.
Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2009 IFC Table 105.6.20.
PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS, AND FILL OUT THE REQUESTED INFORMATION.
All forms and packets are available at https://coloradosprings.gov/hazmat?mlid=42381 | jt09ff | CO Springs Hazmat | 1743481 |
Mechanical | Original | N | 9/19/2022 | JUSTINC | JUSTINC | | | Mechanical | 1743350 |
Electrical | Original | D | 9/18/2022 | SHELBY | SHELBY | 1. Indicate generator size ( KVA). 2. Please provide a load calculation for the existing panel. 3. Show SCA, SCCR and AIC. See https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs%202020%20NEC.pdf for fault current terms and methodologies. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1742747 |
Electronic Plan | Original | / | 9/18/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1742746 |
County Water | Original | D | 9/16/2022 | CSUREVIEW | CSUREVIEW | Not within CSU service area AJ | ajuvera | County Water | 1742413 |
County Waste Water | Original | D | 9/16/2022 | CSUREVIEW | CSUREVIEW | Not within CSU service area AJ | ajuvera | County Waste Water | 1742412 |
Zoning/Planning | Original | / | 9/16/2022 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1742059 |
Construction | Original | N | 9/16/2022 | SHELLEY | SHELLEY | No construction work. | | Construction | 1742041 |
Electronic Plan | Original | / | 9/15/2022 | CHRISTAW | CHRISTAW | In Current Review by CHRISTAW | | Electronic Plan | 1741670 |
Enumeration | Original | N | 9/14/2022 | BRENT | BRENT | | | Enumeration | 1740874 |
Electronic Plan | Original | / | 9/14/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1740870 |
Floodplain | Original | N | 9/13/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5307001021) | | Floodplain | 1740232 |