Scanned/Finished Bin (North) | Splice 03/27/23 | / | 3/27/2023 | | SCANNING | Location = Scanned/Finished Bin (North) by SCANNING | | Scanned/Finished Bin (North) | 1821121 |
Mechanical | Splice 03/27/23 | A | 3/27/2023 | SHANEN | SHANEN | Delta 2 revisions dated 3/13/23: Adjusted sheet M-1. | | Mechanical | 1821118 |
Out to Review | Splice 03/27/23 | / | 3/27/2023 | AMYP | AMYP | RON 719-209-1867 | | Out to Review | 1821099 |
Mechanical | Original | A | 12/16/2022 | JUSTINC | JUSTINC | | | Mechanical | 1782778 |
Submittal 4 | Original | / | 12/15/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1782692 |
Mechanical | Original | D | 12/5/2022 | JUSTINC | JUSTINC | Comments from the first review still not addressed? Why only showing the comments and not how they are addressed. Need an interlock schedule for each of the new KEF's Need the Captive Aire sheet as part of the mechanical submittal upload Need an air balance report.
These items must be on the stamped plans
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1777910 |
Submittal 3 | Original | / | 11/30/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1776400 |
Electrical | Original | A | 11/30/2022 | RICHG | RICHG | | | Electrical | 1776251 |
Health Dept. | Original | N | 11/21/2022 | HEALTHDEPT | HEALTHDEPT | Not applicable. Reviewed new oven spec sheet and discussed proper drainage with contact, Jed Moody. AB | abrannon | Health Dept. | 1773881 |
Plumbing | Original | A | 11/17/2022 | SHANEN | SHANEN | | | Plumbing | 1772070 |
Mechanical | Original | D | 11/16/2022 | JUSTINC | JUSTINC | Comments from last review not addressed? Response letter is only showing plumbing comment
Review incomplete
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1771945 |
Submittal 2 | Original | / | 11/16/2022 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1771936 |
CO Springs Fire | Original | N | 11/8/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1767670 |
CO Springs Hazmat | Original | N | 11/8/2022 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1767659 |
Plumbing | Original | D | 11/7/2022 | TCRIPPEN | TCRIPPEN | Disapproved: Gas piping and related items to be on the mechanical pages per our web site.Schedule plumbing materials that can be used on this job. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1767392 |
Electrical | Original | D | 11/1/2022 | RICHG | RICHG | 1. Provide Conduit/conductor size, type, and quantity, beginning at the utility transformer, to include all conductors in the chain of supply for the electrical equipment in the scope of work
2. Provide panel schedules for all distribution equipment affected by the scope of work to include volt amps for all branch circuit, feeder and service loads and total load on panel depicted in amps.
3. Provide listings (NRTL) for Oven's and Proof Box
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1764056 |
Electronic Plan | Original | / | 11/1/2022 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1764051 |
CO Springs DRE | Original | N | 10/28/2022 | JMALPICA | JMALPICA | Interior remodel. No changes to the exterior. NA (see full review) | | CO Springs DRE | 1762956 |
Health Dept. | Original | D | 10/28/2022 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.CM | cmille96 | Health Dept. | 1762920 |
Zoning/Planning | Original | / | 10/28/2022 | JMALPICA | JMALPICA | In Current Review by JMALPICA | | Zoning/Planning | 1762899 |
Mechanical | Original | D | 10/28/2022 | JUSTINC | JUSTINC | Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection. Revise to PPRBD adopted code year - 2015 Provide captive aire cut sheets with this mechanical sheet Provide kitchen air balance schedule for ENTIRE kitchen - Note balance MUST be within 10% per AHJ Provide kitchen interlock schedule for kitchen exhaust system
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1762721 |
CSU Water | Original | N | 10/28/2022 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSM | stefanm | CSU Water | 1762695 |
CSU Waste Water | Original | N | 10/28/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSM | stefanm | CSU Waste Water | 1762694 |
Electronic Plan | Original | / | 10/28/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1762686 |
Construction | Original | N | 10/28/2022 | BPHILLIPS | BPHILLIPS | | | Construction | 1762631 |
Electronic Plan | Original | / | 10/26/2022 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1761749 |
Enumeration | Original | N | 10/25/2022 | BRENT | BRENT | | | Enumeration | 1761083 |
Electronic Plan | Original | / | 10/25/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1761076 |
Floodplain | Original | N | 9/23/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5330202008) | | Floodplain | 1745768 |