Triage | Original | D | 6/9/2023 | KALLISTAJ | KALLISTAJ | Strictly for extension of Plan/ePlan for 12 MOS. | | Triage | 1854295 |
Enumeration | Original | D | 10/25/2022 | ANDREAL | ANDREAL | Disapproving All Departments so revised plans can be submitted and review can be started with clarity on scope of work.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1761218 |
Health Dept. | Original | D | 10/21/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1760136 |
CSU Contract Admin. | Original | D | 10/21/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing form approved 10/18/2022. Requires payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 1759939 |
Gas/Elec. Utils | Original | D | 10/18/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | Gas/Elec. Utils | 1758238 |
CSU Waste Water | Original | D | 10/18/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 1758237 |
CSU Water | Original | D | 10/18/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Ensure service line size on civil plans match what is shown on plumbing plans. Specify the meter size on plumbing plans, size must match the commercial water meter sizing form. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Water | 1758236 |
City Engr | Original | D | 10/18/2022 | PMORRIS | PMORRIS | Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1758048 |
Electrical | Original | D | 10/18/2022 | DANIELG | DANIELG | 1. Construction review comments must be addressed.
2. Provide volt amps for all branch circuit, feeder and service loads and load summary for both panel schedules.
3. Provide panel and circuit designation on each condensing unit.
4. Provide complete accessibility plan. See https://www.pprbd.org/File/Resources/Downloads/Codes/Policy%20-%20Accessibility%20Plan%20-%20RBC106.1.pdf
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1757954 |
CO Springs DRE | Original | D | 10/18/2022 | APAQUETTE | APAQUETTE | Please provide APPROVED development plan entitlement. No approval stamp from City Planning is located on submitted DP. (see full review) | | CO Springs DRE | 1757921 |
Electronic Plan | Original | / | 10/18/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1757883 |
Plumbing | Original | D | 10/18/2022 | SHANEN | SHANEN | Construction review comments must be addressed. CSU comments if any must be addressed. P-001-1: Remove all fixtures from the fixture schedule that do not apply to building 1. P-111-1: 1"domestic and 4" fire service per sheet C8.2 (1-1/2" and 3" shown). Horizontal dry vent serving FS-1 does not comply with section 905.4 Vertical rise of vent. Every dry vent shall rise vertically to a point not less than 6-inches above the flood level rim of the highest trap or trapped fixture being vented. P-401-1: For clarity, show the DWV and water distribution piping for each unit plan on the applicable unit plan and not for the unit plan above. P-500-1: CWB-1 connected to wet vented bathroom group does not comply with section 912.1 Horizontal wet vent permitted. Only the fixtures within the bathroom groups shall connect to the wet-vented horizontal branch drain. Provide an isometric drawing for the water distribution system. Provide a typical pex manifold water distribution system showing manifold shut off valves, manifold sizing and piping to each fixture. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1757793 |
Mechanical | Original | D | 10/18/2022 | JUSTINC | JUSTINC | Mechanical review incomplete pending construction reviewer comments. Verify any changes with architect before resubmitting See (M) sheets
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1757790 |
Construction | Original | D | 10/18/2022 | SHELLEY | SHELLEY | REVIEW STOPPED - Clarify building. Portions of plans indicate this is being looked at as a townhome (IRC), and other portions indicate IBC R-2. As an R-2, the U (garage) is the driving occupancy for height and area, and must be separated at the first floor level because of height restrictions. As an IRC townhome, those restrictions do not apply. Put plan in order per the index. Provide compliant accessibility plan. See plan for other preliminary comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1757743 |
Elevators | Original | N | 10/14/2022 | ERIC | ERIC | No conveyance | | Elevators | 1756489 |
Electronic Plan | Original | / | 10/14/2022 | CHRISTAW | CHRISTAW | In Current Review by CHRISTAW | | Electronic Plan | 1756475 |
Enumeration | Original | D | 10/13/2022 | BRENT | BRENT | Include a site plan showing the parcel and all proposed buildings with addressing and the area of work highlighted in the architectural plan pages.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1756357 |
Floodplain | Original | N | 10/13/2022 | BRENT | BRENT | | | Floodplain | 1756356 |
Electronic Plan | Original | / | 10/13/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1756352 |