Monument Water | Original | N | 6/1/2023 | TOWNOFMON | TOWNOFMON | Approved by Monument Planning Department; no Monument inspection required. PPRBD inspection is needed. Monument approval is based on documents submitted through the Cascade permitting system. If plans are changed within Pikes Peak Regional Building, the Town may enforce zoning violations. | lukejameskerr | Monument Water | 1850433 |
Monument Zoning | Original | A | 6/1/2023 | TOWNOFMON | TOWNOFMON | Plan conditionally approved by Town of Monument. Permit Fees are due within 10 days of permit authorization. Note that no final Monument Inspection for C/O can be completed unless all permit fees are paid, Development items/requests are completed and inspection requirements are met which could include the Monument Water Department. Any change to the approved plot plan or variations in the model as depicted on the plot plan requires a plot plan modification and re-review. For more information you may email the Planning Department at planning@tomgov.org. Thank you | lukejameskerr | Monument Zoning | 1850395 |
Electrical | Original | D | 5/26/2023 | SHELBY | SHELBY | 1. Remove wherehouse information from plan set. 2. Show transformer location. 3. Show trans former GEC. 4. Comply 450.14 NEC if applicable. 5. Include cooling equipment on the fault schedule with SCA and SCCR. See https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs%202020%20NEC.pdf PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1848265 |
Electronic Plan | Original | / | 5/26/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1848203 |
Health Dept. | Original | N | 5/18/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1299 is valid from 02/28/2023-08/28/2023. AF | Amanda Furno | Health Dept. | 1845019 |
Plumbing | Original | D | 5/18/2023 | SHANEN | SHANEN | See progress set for review comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1844965 |
Tri-Lakes Hazmat (CSFD) | Original | N | 5/16/2023 | CSFIRE | CSFIRE | | dwithee | Tri-Lakes Hazmat (CSFD) | 1844345 |
Tri-Lakes Fire (CSFD) | Original | A | 5/16/2023 | CSFIRE | CSFIRE | We are pleased to inform you this plan is approved You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! E (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1844344 |
Mechanical | Original | A | 5/16/2023 | JUSTINC | JUSTINC | | | Mechanical | 1844195 |
Gas/Elec. Utils | Original | D | 5/16/2023 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' electric or gas service territory. mjg | mgackle | Gas/Elec. Utils | 1844170 |
Construction | Original | D | 5/16/2023 | JUSTINL | JUSTINL | See review set or progress set for review comments.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1844156 |
Electronic Plan | Original | / | 5/16/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1844092 |
Enumeration | Original | A | 5/16/2023 | BRENT | BRENT | | | Enumeration | 1844064 |
Electronic Plan | Original | / | 5/16/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1844036 |
Submittal 2 | Original | / | 5/16/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1844002 |
Tri-Lakes Hazmat (CSFD) | Original | D | 10/28/2022 | CSFIRE | CSFIRE | | Jacob.Watson | Tri-Lakes Hazmat (CSFD) | 1762693 |
Tri-Lakes Fire (CSFD) | Original | D | 10/27/2022 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren
Submitted By: Valdez, Philip Warren
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1762413 |
Tri-Lakes Fire (CSFD) | Original | D | 10/27/2022 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren
Submitted By: Valdez, Philip Warren
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1762412 |
Health Dept. | Original | D | 10/21/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1760156 |
Electrical | Original | D | 10/20/2022 | SHELBY | SHELBY | 1. Show location of all electrical gear on floor plan. 2. Provide required fault current information in tabular form. See https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs%202020%20NEC.pdf 3. Show GEC size on one line. 4. Transformer A must comply 450.14 NEC Complete re review. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1759815 |
Electronic Plan | Original | / | 10/20/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1759813 |
Monument Zoning | Original | D | 10/20/2022 | TOWNOFMON | TOWNOFMON | DECLINED-This project is not completed in Planning yet. Cannot review without all of the items needed for the Development project. Please call Mark Kitzmiller at 484-269-3738 | trust@tomgov.org | Monument Zoning | 1759653 |
Monument Water | Original | D | 10/20/2022 | TOWNOFMON | TOWNOFMON | DECLINED-This project is not completed in Planning yet. Cannot review without all of the items needed for the Development project. Please call Mark Kitzmiller at 484-269-3738 | trust@tomgov.org | Monument Water | 1759651 |
Plumbing | Original | D | 10/20/2022 | SHANEN | SHANEN | Construction approved occupant load required to verify compliance with section 403.1 Minimum number of fixtures. Per preliminary occupant load provided on the code study form a service sink and high/low drinking fountain are required. Show the location of and piping for the required service sink and the high/low drinking fountain. All gas piping, mechanical condensate piping and mechanical venting must be on the mechanical plans. Remove all references to these systems from the plumbing plans. P2.10: Horizontal dry vents serving FD-1 and FS-1 do not comply with section 905.4 Vertical rise of vent. Every dry vent shall rise vertically to a point not less than 6-inches above the flood level rim of the highest trap or trapped fixture being vented. P3.00: Schedule service sink and high/low drinking fountain.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1759343 |
Mechanical | Original | D | 10/20/2022 | JUSTINC | JUSTINC | All gas piping related items to be on mechanical plans.Remove all references to gas piping from the plumbing plans and provide on mechanical plans. How complying with 2015 IECC C403.2.4.3?
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1758999 |
Electronic Plan | Original | / | 10/20/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1758979 |
Gas/Elec. Utils | Original | D | 10/20/2022 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities service territory. | dmakings | Gas/Elec. Utils | 1758922 |
CSU Contract Admin. | Original | N | 10/19/2022 | CSUAPPSPRM | CSUAPPSPRM | Out of Colorado Springs Utilities service area. Will need to follow up with correct provider for applicable fees. CZ | c.zani | CSU Contract Admin. | 1758616 |
Construction | Original | D | 10/19/2022 | MICHAELA | MICHAELA | Code Study - Correct occupant load. A0.0 - Correct codes. A0.1 - 2015 OLF for office use is 1:100 SF OLF for the lobby and the conference rooms is 1:15 and must be calculated separately. A circulation path may be removed from the lobby SF when performing the calculation. A0.4 - ADA is a federal program and not enforced in this jurisdiction. The 2009 ICC/ANSI 117.1 is the accessibility code required to be complied with. Revise this page accordingly. A6.02 - Address compliance with ANSI 117.1 sec. 307.4 for reduced vertical clearance. A6.04 - Locate a 3-hr wall in the structure or remove wall type. Structural - Please add specifically Pf and Pg as noted in sec the 2017 PPRBC. Specifically reference the soils report being used to to design the foundation.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1758594 |
Elevators | Original | N | 10/19/2022 | ERIC | ERIC | No conveyance | | Elevators | 1758378 |
Electronic Plan | Original | / | 10/19/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1758315 |
Enumeration | Original | A | 10/18/2022 | BRENT | BRENT | | | Enumeration | 1758173 |
Electronic Plan | Original | / | 10/18/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1758151 |
Waste Water Div | Original | / | 10/13/2022 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 1756054 |
Floodplain | Original | N | 10/13/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7135000005) | | Floodplain | 1756053 |