Construction | Splice 03/30/23 | A | 4/11/2023 | SHELLEY | SHELLEY | UL listing update | | Construction | 1828437 |
Construction | Splice 03/30/23 | D | 4/5/2023 | DANM | DANM | UL listing is not current - see UL website.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1825898 |
Electronic Plan | Splice 03/30/23 | / | 4/5/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1825895 |
Submittal 2 | Splice 03/30/23 | / | 4/5/2023 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 1825811 |
Mechanical | Splice 03/30/23 | A | 3/31/2023 | DALEH | DALEH | clouds | | Mechanical | 1823856 |
CO Springs Fire | Splice 03/30/23 | A | 3/31/2023 | CSFIRE | CSFIRE | details for floor and ceiling penetrations | Jacob.Watson | CO Springs Fire | 1823776 |
Construction | Splice 03/30/23 | D | 3/30/2023 | DANM | DANM | See Progress Set for disapproval comments
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1823454 |
Electronic Plan | Splice 03/30/23 | / | 3/30/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1823426 |
Mechanical | Splice 03/17/23 | A | 3/30/2023 | DALEH | DALEH | Approved as noted | | Mechanical | 1823183 |
Plumbing | Splice 03/17/23 | A | 3/29/2023 | SHANEN | SHANEN | Delta 4 revisions: Adjusted sheet P-102. | | Plumbing | 1822696 |
Submittal 2 | Splice 03/17/23 | / | 3/29/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1822616 |
CO Springs Fire | Splice 03/24/23 | A | 3/27/2023 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1820805 |
Construction | Splice 03/24/23 | A | 3/24/2023 | DANM | DANM | Clarification that common area electrical room wall indicated on drawing does not have existing fire rating | | Construction | 1820703 |
Electronic Plan | Splice 03/24/23 | / | 3/24/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1820674 |
Mechanical | Splice 03/17/23 | D | 3/21/2023 | DALEH | DALEH | Per conversation with inspector this duct appears to be penetrating a rated floor/ceiling assembly how protecting ? Duct routing on upper level that penetrates a corridor, indicate on plans if corridor is rated and if so show floor plan of that level and how protecting penetrations. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1818736 |
Plumbing | Splice 03/17/23 | D | 3/17/2023 | SHANEN | SHANEN | Provide sizing for the existing CW riser at the revised 1-1/2" CW point of connection. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1817423 |
CSU Contract Admin. | Original | N | 12/22/2022 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved for existing meter. No fees due this plan set. CZ | c.zani | CSU Contract Admin. | 1784724 |
Mechanical | Original | A | 12/21/2022 | DALEH | DALEH | | | Mechanical | 1784464 |
Submittal 4 | Original | / | 12/21/2022 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1784387 |
CSU Contract Admin. | Original | D | 12/20/2022 | CSUAPPSPRM | CSUAPPSPRM | Requires resubmittal of Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate.
CZ | c.zani | CSU Contract Admin. | 1784035 |
CO Springs Hazmat | Original | A | 12/20/2022 | CSFIRE | CSFIRE | Submitted by: Tillery, Demarcus
You are responsible for reviewing the APPROVAL comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | CO Springs Hazmat | 1783952 |
Mechanical | Original | D | 12/19/2022 | DALEH | DALEH | Mechanical plans not uploaded for review Need to upload complete mechanical drawings PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1783256 |
Plumbing | Original | A | 12/16/2022 | SHANEN | SHANEN | | | Plumbing | 1783045 |
CSU Water | Original | A | 12/16/2022 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | CSU Water | 1783032 |
Submittal 3 | Original | / | 12/16/2022 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1783022 |
CO Springs Hazmat | Original | D | 12/14/2022 | CSFIRE | CSFIRE | Comment 1 - Please indicate the category in which the med gas system is designed (Category 1,2, or 3). See Chapter 15 of NFPA 99
Comment 2 - For interior supply locations. A 1-hour rated shaft enclosure is required for supply and exhaust ducts. See Section 5306.2.2 of the 2015 IFC (see full review) | DTillery94 | CO Springs Hazmat | 1782054 |
CO Springs Fire | Original | A | 12/2/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1777512 |
Mechanical | Original | D | 11/28/2022 | DALEH | DALEH | Med gas room exhaust does not meet code See 2015 IMC section 502.9.1 Waiting for fire approval PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1775474 |
Plumbing | Original | D | 11/23/2022 | SHANEN | SHANEN | P-501 Water heater detail: Expansion tank installed upstream of vacuum breaker is not in compliance with section 607.3 Thermal expansion control. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1774638 |
Electrical | Original | A | 11/22/2022 | SHELBY | SHELBY | | | Electrical | 1774529 |
CSU Contract Admin. | Original | D | 11/22/2022 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1774152 |
CSU Water | Original | D | 11/22/2022 | CSUREVIEW | CSUREVIEW | Customer Contract Admin requires approval of CWMSF prior to CSU Water sign off. SSM | stefanm | CSU Water | 1774079 |
Construction | Original | A | 11/22/2022 | MICHAELA | MICHAELA | | | Construction | 1773968 |
Enumeration | Original | N | 11/21/2022 | BRENT | BRENT | | | Enumeration | 1773768 |
Electronic Plan | Original | / | 11/21/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1773759 |
Submittal 2 | Original | / | 11/21/2022 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1773355 |
CO Springs Hazmat | Original | D | 10/27/2022 | CSFIRE | CSFIRE | | Jacob.Watson | CO Springs Hazmat | 1762423 |
CO Springs Fire | Original | D | 10/27/2022 | CSFIRE | CSFIRE | Submitted By: Watson, Jacob Thomas
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1762422 |
Electrical | Original | D | 10/21/2022 | SHELBY | SHELBY | 1. Provide a load calculation for the MDP. 2. Transformer SSBJ is incorrect [ 250.30(A)(2) NEC]. 3. Show SCCR and SCA at/for cooling equipment. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1760290 |
Electronic Plan | Original | / | 10/21/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1760264 |
CSU Waste Water | Original | N | 10/20/2022 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CM | CoreyM | CSU Waste Water | 1759567 |
CSU Water | Original | D | 10/20/2022 | CSUREVIEW | CSUREVIEW | A new commercial water meter sizing form is needed. Contact 719-668-8111 or CCA@csu.org | CoreyM | CSU Water | 1759565 |
Plumbing | Original | D | 10/20/2022 | SHANEN | SHANEN | Provide required water pipe size analysis data, see 2018 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Data may be calculated from point of connection. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1759515 |
CO Springs DRE | Original | N | 10/20/2022 | MOBRIEN | MOBRIEN | Interior tenant improvements. No exterior changes or change of occupancy. New interior walls, flooring, lighting, HVAC, etc. | | CO Springs DRE | 1759420 |
Mechanical | Original | D | 10/20/2022 | JUSTINC | JUSTINC | Add note: Provide (1) copy of test and balance report to mechanical inspector by final inspection Clarify how the proposed layout will comply with 2015 IFC 5306.2.2 Med-gas Provide refrigeration calculation per 2015 IMC 1103.1 mini-split system
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1759418 |
Electronic Plan | Original | / | 10/20/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1759382 |
Zoning/Planning | Original | / | 10/20/2022 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1759068 |
Construction | Original | D | 10/20/2022 | MICHAELA | MICHAELA | G-001 - Why does the med-gas room have a 2-hr. hatch? G-502 - How is duct, open to the med-gas room being 1-hr. protected to the exterior? There is no provision in the code to use a wall listing for the ceiling in this location. Provide a listed horizontal assembly. A-601 - Why is the glass in door 6 rated? PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1758915 |
Electronic Plan | Original | / | 10/19/2022 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1758755 |
Enumeration | Original | D | 10/19/2022 | BRENT | BRENT | Include a site plan showing all tenant spaces on the second floor with addressing and the area of work for this plan highlighted, in the architectural plan pages PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1758414 |
Electronic Plan | Original | / | 10/19/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1758400 |
Floodplain | Original | N | 10/14/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6232406001) | | Floodplain | 1756767 |