CO Springs Fire | Original | D | 8/7/2023 | CSFIRE | CSFIRE | *****(DISAPPROVED) WATER SUPPLIES
To help us ensure there is adequate exterior fire protection, please provide the following:
--XXX--- Approved Water Plan (mains, hydrants, etc. for new structures in green field development)
WATER PLANS SHALL BE SUBMITTED TO CSFD AND CSU - THIS REVIEW IS SEPARATE AND PLANS ARE NOT ROUTED BETWEEN AGENCIES, HOWEVER THE REVIEWS CAN OCCUR CONCURRENTLY. PLEASE ENSURE YOUR CIVIL ENGINEER SUBMITS WATER PLANS TO CSFD FOR REVIEW AND APPROVAL PRIOR TO ASKING FOR CSFD SIGNATURES. (see full review) | csfdit | CO Springs Fire | 1881685 |
CSU Contract Admin. | Original | D | 8/7/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF approved on 05/31/2023.
AMS | ASweet | CSU Contract Admin. | 1881459 |
Health Dept. | Original | D | 8/3/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1879697 |
CO Springs DRE | Original | A | 8/3/2023 | ACOOPER | ACOOPER | Approved per DEPN-22-0088 (see full review) | | CO Springs DRE | 1879620 |
City Engr | Original | D | 8/2/2023 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (STM-REV22-0981 & 1312) | | City Engr | 1879434 |
Gas/Elec. Utils | Original | D | 8/2/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 1879354 |
CSU Water | Original | D | 8/2/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan uploade. CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA. | malcuran | CSU Water | 1879352 |
CSU Waste Water | Original | D | 8/2/2023 | CSUREVIEW | CSUREVIEW | Approved City DP uploaded. CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA. | malcuran | CSU Waste Water | 1879343 |
Zoning/Planning | Original | / | 8/2/2023 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1879149 |
Plumbing | Original | D | 8/2/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1879097 |
Construction | Original | A | 8/2/2023 | JUSTINL | JUSTINL | No changes to commercial construction sheets from previously approved plans | | Construction | 1879072 |
Electronic Plan | Original | / | 8/2/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1879051 |
Enumeration | Original | D | 8/2/2023 | AMY | AMY | Final Plat 1. Enumerations will review the pre-plat (mylar) prior to plat for address placement, street names, and title block. 2. A $10.00 per lot and tract platting fee will be due at the time of the review of the pre-plat, (two addresses per lot and tract). If an address is not needed on a tract then no fee applies. Check should be made out to PIKES PEAK REGIONAL BUILDING DEPARTMENT or PPRBD. Paid directly to the Enumerations Department. As of September 28th, 2022, an additional over the phone transaction fee of 2.95% of the total transaction will apply for any credit card payment. 3. A copy of the final recorded plat is required prior to plan submittal for RESIDENTIAL. A copy of the final recorded plat is required prior to approval in the Enumerations department on any COMMERCIAL plan submittal. Please email the Enumerations staff member that reviewed your project. Amy@pprbd.org; Brent@pprbd.org; or BeckyA@pprbd.org 4. Pre-plat reviews can be reviewed via “pdf” or in-person. The pre-plat will be stamped by Enumerations for accuracy and returned to the applicant and the planner. All payments to be mailed to RBD via a check or credit card payment over the phone. Plats should not be recorded prior to Enumerations stamping the pre-plat and receiving payment of plat fees. If any pre-plat changes occur, even if changes do not apply to Enumerations, we still need to re-stamp the pre-plat. The Enumerations stamped pre-plat copy should match the recorded document minus a few signatures. If you would like an in-person review, please make an appointment on our website, https://www.pprbd.org/Home/BookAppt 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1878979 |
Electronic Plan | Original | / | 8/2/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1878931 |
Submittal 5 | Original | / | 8/1/2023 | SIERRAC | SIERRAC | Submittal #5 | | Submittal 5 | 1878488 |
CSU Contract Admin. | Original | D | 6/5/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1851807 |
CO Springs Fire | Original | D | 5/30/2023 | CSFIRE | CSFIRE | WALK OK *****(DISAPPROVED) WATER SUPPLIES
To help us ensure there is adequate exterior fire protection, please provide the following:
--XXX--- Approved Water Plan (mains, hydrants, etc. for new structures in green field development)
WATER PLANS SHALL BE SUBMITTED TO CSFD AND CSU - THIS REVIEW IS SEPARATE AND PLANS ARE NOT ROUTED BETWEEN AGENCIES, HOWEVER THE REVIEWS CAN OCCUR CONCURRENTLY. PLEASE ENSURE YOUR CIVIL ENGINEER SUBMITS WATER PLANS TO CSFD FOR REVIEW AND APPROVAL PRIOR TO ASKING FOR CSFD SIGNATURES. (see full review) | csfdit | CO Springs Fire | 1848854 |
CO Springs DRE | Original | D | 5/30/2023 | ACOOPER | ACOOPER | include stamped approved development plans (see full review) | | CO Springs DRE | 1848746 |
Health Dept. | Original | D | 5/26/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | Health Dept. | 1848472 |
City Engr | Original | D | 5/26/2023 | PMORRIS | PMORRIS | Same comment: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1848397 |
Electrical | Original | A | 5/26/2023 | SHELBY | SHELBY | | | Electrical | 1848301 |
Mechanical | Original | A | 5/23/2023 | TCRIPPEN | TCRIPPEN | | | Mechanical | 1846701 |
Gas/Elec. Utils | Original | D | 5/23/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | Gas/Elec. Utils | 1846679 |
CSU Water | Original | D | 5/23/2023 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Water | 1846676 |
CSU Waste Water | Original | D | 5/23/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 1846638 |
Zoning/Planning | Original | / | 5/23/2023 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1846627 |
Construction | Original | A | 5/23/2023 | JUSTINL | JUSTINL | | | Construction | 1846598 |
Electronic Plan | Original | / | 5/23/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1846544 |
Plumbing | Original | D | 5/23/2023 | SHANEN | SHANEN | See progress set for disapproval comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1846306 |
Enumeration | Original | D | 5/22/2023 | AMY | AMY | See progress set for Enumerations comments on page GOO1. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1846197 |
Electronic Plan | Original | / | 5/22/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1846116 |
Submittal 4 | Original | / | 5/17/2023 | KALLISTAJ | KALLISTAJ | Submittal #4 | | Submittal 4 | 1844483 |
Plan Coordinator (Main) | Original | D | 5/16/2023 | ANDREAL | ANDREAL | Disapprove all remaining departments to allow plan to be resubmitted. Need the plans with the correct address on them submitted. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plan Coordinator (Main) | 1844136 |
CO Springs Fire | Original | D | 5/12/2023 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren Walk OK - resubmittal qualifies for walkthrough. please see link for how to request a walkthrough review from Fire: https://coloradosprings.gov/document/walk-thrumemo.pdf
We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1843092 |
Submittal 3 | Original | / | 5/12/2023 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1842874 |
Enumeration | Original | D | 3/28/2023 | AMY | AMY | The main front door to the building has been flipped to now be from Troy Hill Road. The new address to this building is 350 Troy Hill Road. Please change the addressing on the pages that you can, Enumeration will help out with it but if pages keep getting resubmitted then Enumerations will not be able to keep up with the re-submittals.
Enumerations will not approve building plans without a copy of the final recorded plat in our records. This appears to be a multi-tenant building. If it is, then the site plan needs to show the secondary addressing for the maximum number of tenant spaces the building can hold which follows the secondary addressing guidelines available on the RBD website. Send a draft copy of the secondary addressing to Amy Vanderbeek amy@pprbd.org The legal description shown on the code study form is incorrect. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1821569 |
CO Springs Fire | Original | D | 2/15/2023 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | CO Springs Fire | 1803554 |
Electrical | Original | D | 2/10/2023 | SHELBY | SHELBY | 1. Add SCCR and SCA to the fault schedule. 2. Service configuration violates CSU Line Extension and Service standards ( Connection cabinet). 3. Alternates are not allowed ( See one line). 4. Transformer and feeder schedules must be on the one line. 5. Show location of service equipment on the Electrical site plan. See https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs%202020%20NEC.pdf for fault current terms and methodologies. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1801548 |
Electronic Plan | Original | / | 2/10/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1801517 |
City Engr | Original | D | 2/6/2023 | JDAGNILLO | JDAGNILLO | See previous comment - Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facitlity) construction plan into the building permit. Contact Erin Powers (erin.powers@coloradosprings.gov) or Jonathan Scherer (jonathan .scherer@coloradosprings.gov) with the Stormwater Enterprise regarding any GECP or PCM questions.
Upload a copy of the approved Development Plan into the building permit set. | | City Engr | 1799519 |
CSU Contract Admin. | Original | D | 2/6/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted:
Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1799160 |
Health Dept. | Original | D | 2/3/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1799006 |
CO Springs DRE | Original | D | 2/3/2023 | JMALPICA | JMALPICA | Please upload approved development plan with building permit submittal. (see full review) | | CO Springs DRE | 1798985 |
Mechanical | Original | A | 2/3/2023 | TCRIPPEN | TCRIPPEN | Approved. | | Mechanical | 1798937 |
Plumbing | Original | D | 2/3/2023 | SHANEN | SHANEN | P1.0: 6" building drain connecting to a 4" sewer (per referenced civil plans sheet U2.0) does not comply with section 704.2. P1.1: Unable to verify water service size or location with referenced civil plans sheet U1.0. Provide a vent for the 6" floor sink (FS) in compliance with chapter 9 Vents. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1798927 |
CSU Water | Original | D | 2/3/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Water | 1798916 |
CSU Waste Water | Original | D | 2/3/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Waste Water | 1798915 |
Gas/Elec. Utils | Original | D | 2/3/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 1798914 |
Construction | Original | D | 2/3/2023 | JUSTINL | JUSTINL | Still need to address wind speeds referenced in design on structural sheets. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1798881 |
Electronic Plan | Original | / | 2/3/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1798650 |
Enumeration | Original | D | 2/3/2023 | BRENT | BRENT | What is the name of the final plat for this project? Enumerations will not approve building plans without a copy of the final recorded plat in our records. This appears to be a multi-tenant building. If it is, then the site plan needs to show the secondary addressing for the maximum number of tenant spaces the building can hold which follows the secondary addressing guidelines available on the RBD website. The legal description shown on the code study form is incorrect. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1798644 |
Electronic Plan | Original | / | 2/3/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1798628 |
Submittal 2 | Original | / | 2/2/2023 | ANDREAL | ANDREAL | Submittal #2 | | Submittal 2 | 1798444 |
CO Springs Hazmat | Original | N | 11/29/2022 | CSFIRE | CSFIRE | hazmat addressed at tenant finish | dwithee | CO Springs Hazmat | 1776097 |
CO Springs Fire | Original | D | 11/29/2022 | CSFIRE | CSFIRE | We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1776094 |
Health Dept. | Original | D | 11/23/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1775037 |
City Engr | Original | D | 11/22/2022 | PMORRIS | PMORRIS | Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Contact Erin Powers (erin.powers@coloradosprings.gov) or Jonathan Scherer (jonathan.scherer@coloradosprings.gov with the Stormwater Enterprise regarding any GECP or PCM questions.
Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1774073 |
Electrical | Original | D | 11/18/2022 | SHELBY | SHELBY | Remove all equipment not part of the core and shell. ( Bathrooms and electrical rooms are OK). PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1772742 |
Electronic Plan | Original | / | 11/18/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1772740 |
CO Springs DRE | Original | D | 11/17/2022 | JMALPICA | JMALPICA | Please upload an approved LUR development plan. (see full review) | | CO Springs DRE | 1772660 |
Mechanical | Original | D | 11/17/2022 | TCRIPPEN | TCRIPPEN | Disapproved:This plan was turn in as core and shell no ducts allowed and no interior finishes provide combustion air unit heaters. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1772434 |
Plumbing | Original | D | 11/17/2022 | TCRIPPEN | TCRIPPEN | Disapproved see CSUs notes. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1772419 |
Elevators | Original | N | 11/17/2022 | ERIC | ERIC | No conveyance | | Elevators | 1772379 |
CSU Contract Admin. | Original | D | 11/17/2022 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable development fees/charges. Please contact our office at 719-668-8111 for additional information and to request an estimate. AG
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5 | aguerin | CSU Contract Admin. | 1772283 |
CSU Water | Original | D | 11/17/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Water | 1772266 |
CSU Waste Water | Original | D | 11/17/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 1772264 |
Gas/Elec. Utils | Original | D | 11/17/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 1772262 |
Construction | Original | D | 11/17/2022 | MICHAELA | MICHAELA | This plan has been submitted as a Core and Shell. Please remove all pages that reference any interior finishes. Revise structural plan for the correct wind speed. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1772240 |
Electronic Plan | Original | / | 11/17/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1772066 |
Enumeration | Original | D | 11/16/2022 | BRENT | BRENT | What is the name of the final plat for this project? Enumerations will not approve building plans without a copy of the final recorded plat in our records. This appears to be a multi-tenant building. If it is, then the site plan needs to show the secondary addressing for the maximum number of tenant spaces the building can hold which follows the secondary addressing guidelines available on the RBD website. The tax schedule number and legal description shown on the code study form are incorrect. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1771956 |
Electronic Plan | Original | / | 11/15/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1771272 |
Floodplain | Original | N | 10/31/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6413000137) | | Floodplain | 1763394 |