CO Springs Fire | Original | A | 7/18/2023 | CSFIRE | CSFIRE | We are pleased to inform you this plan is approved You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1871601 |
Plumbing | Original | D | 7/5/2023 | SHANEN | SHANEN | See sheet P6.0 of the progress set for review comments. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1866240 |
City Engr | Original | D | 7/3/2023 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (STM-REV22-1165) | | City Engr | 1865851 |
CSU Contract Admin. | Original | D | 7/3/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1865841 |
CSU Water | Original | D | 7/3/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.t
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. SSM | stefanm | CSU Water | 1865774 |
CSU Waste Water | Original | D | 7/3/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1865773 |
Gas/Elec. Utils | Original | D | 7/3/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1865770 |
CO Springs DRE | Original | D | 7/3/2023 | ESHAFER | ESHAFER | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1865744 |
Zoning/Planning | Original | / | 7/3/2023 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1865743 |
Submittal 6 | Original | / | 7/1/2023 | BPHILLIPS | BPHILLIPS | Submittal #6 | | Submittal 6 | 1865663 |
Health Dept. | Original | A | 6/27/2023 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted.
Construction activity permit PT1301 is valid from 7/1/23 - 1/1/24. To continue any earthmoving operations after 1/1/24, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application .
Water recreation plan review application received. Final approval not required for building permit or Certificate of Occupancy.
For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1863218 |
CO Springs Fire | Original | D | 5/8/2023 | CSFIRE | CSFIRE | *****(DISAPPROVED) WATER SUPPLIES
To help us ensure there is adequate exterior fire protection, please provide the following:
--XXX--- Approved Water Plan
NOTE: Water plans shall be submitted to both CSFD and CSU for review and approval. This review can occur concurrently, however plans are not routed between agencies. CSFD approval and signatures are required prior to CSU signing the plans. (see full review) | csfdit | CO Springs Fire | 1841035 |
City Engr | Original | D | 5/4/2023 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (STM-REV22-1165) | | City Engr | 1839460 |
Electrical | Original | A | 5/1/2023 | BERTHA | BERTHA | | | Electrical | 1838018 |
Health Dept. | Original | D | 5/1/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1301 is valid from 7/1/23 - 1/1/24. To continue any earthmoving operations after 1/1/24, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application .
Retail food establishment plan review is in process and not yet approved.
Water recreation plan review application received. Final approval not required for building permit or Certificate of Occupancy.
For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1837531 |
Electronic Plan | Original | / | 4/28/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1837465 |
Mechanical | Original | A | 4/28/2023 | JUSTINC | JUSTINC | | | Mechanical | 1837360 |
Plumbing | Original | D | 4/28/2023 | SHANEN | SHANEN | CSU approved utility service plans required. Plumbing plans must correspond with approved utility service plans. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1837297 |
CO Springs DRE | Original | D | 4/28/2023 | ESHAFER | ESHAFER | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1837251 |
Zoning/Planning | Original | / | 4/28/2023 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1837250 |
CSU Contract Admin. | Original | D | 4/28/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1837236 |
CSU Water | Original | D | 4/28/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Water | 1837180 |
CSU Waste Water | Original | D | 4/28/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Waste Water | 1837179 |
Gas/Elec. Utils | Original | D | 4/28/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 1837178 |
Submittal 5 | Original | / | 4/28/2023 | SIERRAC | SIERRAC | Submittal #5 | | Submittal 5 | 1837162 |
CO Springs Fire | Original | D | 4/25/2023 | CSFIRE | CSFIRE | Still need approved development and water plans
WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/fire-department/page/plan-and-construction-review-status
We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1835418 |
City Engr | Original | D | 4/18/2023 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (STM-REV22-1165) | | City Engr | 1831441 |
Plumbing | Original | D | 4/17/2023 | SHANEN | SHANEN | CSU approved utility service plans required. Plumbing plans must correspond with approved utility service plans. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1831106 |
Health Dept. | Original | D | 4/15/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1301 is valid from 7/1/23 - 1/1/24. To continue any earthmoving operations after 1/1/24, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application .
Retail food establishment plan review is in process and not yet approved.
Water recreation plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/public-pools-and-spas. Please email application and all required documents to healthinfo@elpasoco.com.
For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1830696 |
Electrical | Original | A | 4/14/2023 | BERTHA | BERTHA | | | Electrical | 1830669 |
Electronic Plan | Original | / | 4/14/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1830668 |
CSU Water | Original | D | 4/14/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 1830627 |
CSU Waste Water | Original | D | 4/14/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1830626 |
Gas/Elec. Utils | Original | D | 4/14/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1830625 |
CO Springs DRE | Original | D | 4/14/2023 | ESHAFER | ESHAFER | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1830624 |
Zoning/Planning | Original | / | 4/14/2023 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1830623 |
CSU Contract Admin. | Original | D | 4/14/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1830602 |
Construction | Original | A | 4/14/2023 | JUSTINL | JUSTINL | TRUSSES PENDING Revised door hardware | | Construction | 1830592 |
Electronic Plan | Original | / | 4/14/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1830568 |
Enumeration | Original | A | 4/14/2023 | BECKYA | BECKYA | | | Enumeration | 1830513 |
Submittal 4 | Original | / | 4/14/2023 | SIERRAC | SIERRAC | Submittal #4 | | Submittal 4 | 1830327 |
CO Springs Fire | Original | D | 4/11/2023 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/fire-department/page/plan-and-construction-review-status We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1828750 |
Electrical | Original | D | 4/7/2023 | BERTHA | BERTHA | See progress set for review comments. Comments are located on the one-line sheet.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1827348 |
Electronic Plan | Original | / | 4/7/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1827335 |
Health Dept. | Original | D | 3/31/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1301 is valid from 7/1/23 - 1/1/23. To continue any earthmoving operations after 1/1/23, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application .
Retail food establishment plan review is in process and not yet approved.
Water recreation plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/public-pools-and-spas. Please email application and all required documents to healthinfo@elpasoco.com.
For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1824192 |
Plumbing | Original | D | 3/31/2023 | SHANEN | SHANEN | CSU approved utility service plans required. Plumbing plans must correspond with approved utility service plans. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1824076 |
City Engr | Original | D | 3/31/2023 | PMORRIS | PMORRIS | Same comments: Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1823890 |
Gas/Elec. Utils | Original | D | 3/30/2023 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | Gas/Elec. Utils | 1823459 |
CSU Water | Original | D | 3/30/2023 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | CSU Water | 1823458 |
CSU Waste Water | Original | D | 3/30/2023 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | CSU Waste Water | 1823457 |
CO Springs DRE | Original | D | 3/30/2023 | ESHAFER | ESHAFER | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1823445 |
Zoning/Planning | Original | / | 3/30/2023 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1823444 |
CSU Contract Admin. | Original | D | 3/30/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previous:
Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1823386 |
Construction | Original | A | 3/30/2023 | JUSTINL | JUSTINL | TRUSSES PENDING | | Construction | 1823381 |
Electronic Plan | Original | / | 3/30/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1823264 |
Enumeration | Original | A | 3/30/2023 | BECKYA | BECKYA | | | Enumeration | 1823225 |
Submittal 3 | Original | / | 3/29/2023 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1822507 |
CO Springs Fire | Original | D | 3/17/2023 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1817593 |
Health Dept. | Original | D | 3/2/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com.
Retail food establishment plan review required. Please email completed application and all required documents to healthinfo@elpasoco.com.
Water recreation plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/public-pools-and-spas. Please email application and all required documents to healthinfo@elpasoco.com.
For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1809320 |
Plumbing | Original | D | 3/1/2023 | SHANEN | SHANEN | Construction and CSU comments must be addressed. P1.1: Bottle filler does not meet section 410 drinking fountain requirements. The only substitution for the required high/low drinking fountain that is considered is an accessible height drinking fountain with a bottle filler. An alternate materials and methods application form required to use an accessible height drinking fountain with bottle filler in lieu of required high/low drinking fountain. See link: https://www.pprbd.org/File/Resources/Downloads/Permit/Alternate_M%20AND%20M.pdf P3.3: HWR piping as drawn does not match legend symbol. P4.0: Diagram P4 does not comply with section 905.4 as drawn. P4.2, P4.3, P4.4: BT vents do not comply with section 905.4 as drawn. P4.7: TB not located in the fixture schedule, clarify. TB (BT?) vents do not comply with section 905.4 as drawn. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1808612 |
CO Springs DRE | Original | D | 2/28/2023 | ESHAFER | ESHAFER | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1808548 |
Zoning/Planning | Original | / | 2/28/2023 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1808547 |
City Engr | Original | D | 2/28/2023 | PMORRIS | PMORRIS | Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1808290 |
Electrical | Original | D | 2/28/2023 | BERTHA | BERTHA | Comply with previous review comment - Provide indication that compliance with 620.26 will be met - this comment should have referenced 620.62 – Add a note on the one-line sheet “Documentation confirming compliance with 620.62 is required prior to final.”
Comply with previous review comment - Provide SCCR (withstand rating) for all equipment in the Electrical Short Circuit schedule.
Comply with previous review comment - Comply with 110.26(C)(2) - door swings in - Mechanical 166
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1808279 |
CSU Contract Admin. | Original | D | 2/28/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1808266 |
Mechanical | Original | A | 2/28/2023 | JUSTINC | JUSTINC | | | Mechanical | 1808158 |
Electronic Plan | Original | / | 2/28/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1808143 |
Elevators | Original | A | 2/28/2023 | ERIC | ERIC | 2 Schindler 3300 machineroom-less traction elevators with fire rated suspension means, no generator. | | Elevators | 1808065 |
Gas/Elec. Utils | Original | D | 2/28/2023 | CSUREVIEW | CSUREVIEW | See previous comments. DMM | dmakings | Gas/Elec. Utils | 1808049 |
CSU Waste Water | Original | D | 2/28/2023 | CSUREVIEW | CSUREVIEW | See previous comments. DMM | dmakings | CSU Waste Water | 1808048 |
CSU Water | Original | D | 2/28/2023 | CSUREVIEW | CSUREVIEW | See previous comments. DMM | dmakings | CSU Water | 1808047 |
Construction | Original | D | 2/28/2023 | JUSTINL | JUSTINL | TRUSSES PENDING Limited review of life safety at pool. Separate plans to be submitted for pool by pool contractor. See A101A No floor ceiling assembly provided detail 1 on A003 at lobby A2 assembly. Indicated floor ceiling tested assembly. Tests noted in fire finish paint are for a complete system, not just the fire protection paint. N640 and D990 for beams are for use with a combination of concrete and metal floors and does not match floor construction used in plans. Provide alternative listing for protection of steel beams. Wall type indicator on LS-1 shows walls at front desk and pool equipment room is rated as a corridor. This is not a corridor. Remove wall indicator. If this is to be rated as a partition, indicate rated for other than IBC or provide code path for rating requirements. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1808019 |
Electronic Plan | Original | / | 2/23/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1806614 |
Enumeration | Original | A | 2/21/2023 | BECKYA | BECKYA | CSFD will review and approve the secondary addressing for the hotel. Note: site plan on page AS101-PAGE 20. | | Enumeration | 1804956 |
Submittal 2 | Original | / | 2/16/2023 | BECKYA | BECKYA | Submittal #2 | | Submittal 2 | 1804085 |
CO Springs Hazmat | Original | N | 12/19/2022 | CSFIRE | CSFIRE | Submitted by: Tillery, Demarcus
HazMat N/A (see full review) | DTillery94 | CO Springs Hazmat | 1783456 |
Electrical | Original | D | 12/16/2022 | BERTHA | BERTHA | 1. Pending approval in Elevators - see Elevator review comments.
2. Provide compliance with 240.87
3. Provide indication that compliance with 620.26 will be met.
4. Provide SCCR (withstand rating) for all equipment in the Electrical Short Circuit schedule.
5. Provide indication of compliance with 680.14
6. Provide indication of compliance with 680.22(B)(2) - Provide dimensions from maximum pool water level.
7. Comply with 110.26(C)(2) - door swings in - Mechanical 166
8. Provide 2015 IECC
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1783177 |
City Engr | Original | D | 12/13/2022 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. | | City Engr | 1781734 |
CO Springs Fire | Original | D | 12/10/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1780739 |
Mechanical | Original | D | 12/9/2022 | JUSTINC | JUSTINC | See (M) sheets for comments associated with this review PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1780387 |
Electronic Plan | Original | / | 12/9/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1780182 |
Plumbing | Original | D | 12/8/2022 | SHANEN | SHANEN | Preliminary review. Construction and CSU comments must be addressed. P1.0: Legend symbols for vent, water and storm drain piping do not match plumbing plans. Clarify GR piping and provide a symbol that corresponds with the plumbing plans. P1.1 Fixture schedule: Hydration station does not meet section 410 drinking fountain requirements. The only substitution for the required high/low drinking fountain that is considered is an accessible height drinking fountain with a bottle filler. An alternate materials and methods application form required to use an accessible height drinking fountain with bottle filler in lieu of required high/low drinking fountain. See link: https://www.pprbd.org/File/Resources/Downloads/Permit/Alternate_M%20AND%20M.pdf P2.0: Guest laundry FD-1 location is not in compliance with section 802.4 Waste receptors. P2.2: All condensate piping shall be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. P3.0: Exposed water service piping shall be minimized inside the building prior to the water meter and/or approved backflow prevention assembly or method. P4.0: P16 riser diagram does not match sheet P2.0 (HS or SK-6?). P4.1: Provide isometric drawing for complete DWV system. Provide isometric drawing for complete water distribution system. P5.0 Domestic water service entry detail: Clarify how a water service riser located in an exterior wall complies with section 305.4 Freezing. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1779622 |
CSU Contract Admin. | Original | D | 12/7/2022 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) submitted for review. Payment of applicable utility charges and fees will be required once CWMSF is approved. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CZ | c.zani | CSU Contract Admin. | 1779259 |
Electronic Plan | Original | / | 12/7/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1779186 |
Elevators | Original | D | 12/7/2022 | ERIC | ERIC | 2 Schindler 3300 machineroom-less traction elevators with fire rated suspension means, no generator.
Page E2.3 19 fc lighting required at top of each elevator hoistway, each to be on dedicated circuits Page E3.3 Dedicated circuit gfci outlet required at top of hoistways for each elevator. . PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Elevators | 1779166 |
Health Dept. | Original | D | 12/6/2022 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com.
Retail food establishment plan review required. Please email completed application and all required documents to healthinfo@elpasoco.com.
Water recreation plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/public-pools-and-spas. Please email application and all required documents to healthinfo@elpasoco.com.
For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | Health Dept. | 1779009 |
Gas/Elec. Utils | Original | D | 12/6/2022 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. CM | CoreyM | Gas/Elec. Utils | 1779003 |
CSU Waste Water | Original | D | 12/6/2022 | CSUREVIEW | CSUREVIEW | - The plumbing plans show a lint interceptor but not the DP or utility plan. The lint interceptor must be shown on the DP & utility plan too. MEP and civil plans must collaborate in this case. - An approved development plan by the City of Colorado Springs must be attached to the permit set. The DP plan is currently under review. - On-site utility plans must be approved by CSU and attached to the permit set. CM | CoreyM | CSU Waste Water | 1778998 |
CSU Water | Original | D | 12/6/2022 | CSUREVIEW | CSUREVIEW | - An approved development plan by the City of Colorado Springs must be attached to the permit set. The DP plan is currently under review. - On-site utility plans must be approved by CSU and attached to the permit set. - Plumbing Plan needs to reference an approved water meter detail. See CSU.org for the details. - CWMSF is required. CM | CoreyM | CSU Water | 1778984 |
CO Springs DRE | Original | D | 12/6/2022 | APAQUETTE | APAQUETTE | Please provide APPROVED development plan entitlement. No approval stamp from City Planning is located on submitted DP. (see full review) | | CO Springs DRE | 1778967 |
Construction | Original | D | 12/6/2022 | JUSTINL | JUSTINL | TRUSSES PENDING No structural plans included for pool. Need to indicate if pool will be permitted separately. If not, provide engineering for pool Multiple J wall tag listings on A003 Identify if C1 is intended to be used as a rated wall. GA file 3242 requires RC - Separate listing may be required Unable to locate H and H1 wall tags on floor plans. If wall tags are not used then they need to be removed from listings pages Spray foam insulation noted at multiple exterior wall listings - WP8171 does not show it has been tested with use of spray foam - UL U344 also does not show it has been tested with spray foam - Provide updated listing as well as Provide ES report for spray foam or change insulation to rated assembly approved insulation Each horizontal assembly should have a designator similar to the partition types Assemblies noted for fire finish are invalid. Need to provide valid assemblies where the product can be used. Remove load bearing wall indicators from life safety sheets Need to label listed assembly types on LS-5 or provide listing tags corresponding with A003 and A004 Guest laundry room exceeds 100 SQ FT - must comply with section 509.4.2 Compare floor assemblies on A302A, A302B, A303B - calls for joist and floor trusses. one shows insulation, the other does not. These need to match and be consistent Indicate dimensions of plumbing fixtures at grab bar placement at all public restrooms on A457 Indicate intended method used for meeting requirements of hard, non-absorbent surface at water closets per 1210 in IBC at all required locations on A457 Sheet A703 referenced A3 wall tag. No A3 wall tag provided on A003 J wall tag is a shaft liner - not a load bearing wall - Indicate how supporting construction for 2 hour floor ceiling will be achieved. NOTE: C1 wall tag noted on A101 is not rated - cannot be used for supporting construction purpose Indicate how CMU laundry chute is supported at 1st floor ceiling - Detail to right does not show CMU chute down to foundation - Stops 5'6" from floor Ceiling of elevator shaft appears to extend beyond upper section of roof - 1 hour rating required, not 2 hour Need 2 hour floor ceiling rated assembly for laundry room on sheet A703 Verify fire ratings of door tags match required fire ratings on floor plans - Multiple discrepancies. This includes door 173 at guest laundry room Indicate all structural members that require individual encasement per 704.2 and 704.3 Sheets A8.00 and A8.01 not provided – Sheets and details referenced on multiple structural pages Provide test report for non-combustible 2x10 PT as indicated on sheet S1-2B Indicate beam pad out requirements detail 6 on S3-1 Indicate hardware landing requirements and ledger fastening requirements detail 8 S3-1 Provide complete COMcheck report per C407.4.1 - only 2 pages provided
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1778950 |
Electronic Plan | Original | / | 11/28/2022 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1775458 |
Enumeration | Original | A | 11/28/2022 | AMY | AMY | 1. Tax schedule number on the Code Study form has been corrected for you. If this sheet gets changed out correct this information. 2. CSFD will review and approve the secondary addressing for the hotel. Note: site plan on page AS101-PAGE 20. | | Enumeration | 1775249 |
Electronic Plan | Original | / | 11/28/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1775171 |
Floodplain | Original | N | 11/22/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220001035) | | Floodplain | 1774426 |