Electrical | Original | A | 3/7/2023 | RICHG | RICHG | | | Electrical | 1812030 |
Electrical | Original | D | 3/3/2023 | RICHG | RICHG | Provide metering report from utilities.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1809872 |
Electronic Plan | Original | / | 3/3/2023 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1809820 |
Plumbing | Original | A | 3/1/2023 | SHANEN | SHANEN | | | Plumbing | 1808628 |
Mechanical | Original | A | 2/28/2023 | JUSTINC | JUSTINC | | | Mechanical | 1808200 |
Construction | Original | A | 2/28/2023 | JUSTINL | JUSTINL | | | Construction | 1808157 |
Electronic Plan | Original | / | 2/28/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1808108 |
Submittal 4 | Original | / | 2/27/2023 | SIERRAC | SIERRAC | Submittal #4 | | Submittal 4 | 1807284 |
Mechanical | Original | A | 2/14/2023 | JUSTINC | JUSTINC | | | Mechanical | 1802682 |
Plumbing | Original | D | 2/14/2023 | SHANEN | SHANEN | P-001, PP100: Design professional stamp is illegible. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1802469 |
Electrical | Original | D | 2/13/2023 | RICHG | RICHG | MSC panel is over loaded.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1802298 |
Electronic Plan | Original | / | 2/13/2023 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1802284 |
Construction | Original | D | 2/13/2023 | JUSTINL | JUSTINL | Design professional stamp not legible on all architectural pages and structural page. Cover sheet not legible. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1802270 |
Electronic Plan | Original | / | 2/10/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1801715 |
Submittal 3 | Original | / | 2/10/2023 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 1801523 |
Plan Coordinator (Main) | Original | D | 1/24/2023 | KALLISTAJ | KALLISTAJ | Disapprove all remaining departments to allow plan to be resubmitted PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plan Coordinator (Main) | 1794735 |
Submittal 2 | Original | / | 1/24/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1794726 |
Electrical | Original | D | 12/16/2022 | RICHG | RICHG | 1. Provide SCA and SCCR for all new refrigeration equipment.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1782819 |
Electronic Plan | Original | / | 12/16/2022 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1782818 |
Mechanical | Original | D | 12/15/2022 | JUSTINC | JUSTINC | Provide refrigeration calculation per 2015 IMC 1103.1 Verify if within allowable limits per table on plan. If over the allowable limits indicate how protecting on plan. Revise to adopted 2015 I codes
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1782638 |
CSU Water | Original | A | 12/15/2022 | CSUREVIEW | CSUREVIEW | Backflow okay. MLW | mlwilliams | CSU Water | 1782408 |
CSU Waste Water | Original | N | 12/15/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 1782406 |
CO Springs DRE | Original | N | 12/15/2022 | ZNOYES | ZNOYES | Commercial Interior Remodel Only. No change of use or occupancy. Reconfiguration and addition of mechanical systems and equipment (see full review) | | CO Springs DRE | 1782390 |
CO Springs Hazmat | Original | N | 12/15/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1782311 |
CO Springs Fire | Original | N | 12/15/2022 | CSFIRE | CSFIRE | no fire final (see full review) | csfdit | CO Springs Fire | 1782309 |
Plumbing | Original | D | 12/15/2022 | SHANEN | SHANEN | P-001, PP100: Design professional stamp is illegible. PP100 Keynote PP03: Show compliance with section 608 Protection of potable water supply. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1782252 |
Construction | Original | D | 12/15/2022 | MICHAELA | MICHAELA | Revise to current adopted codes. 2015 I codes except 2018 IPC and 2020 NEC. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1782239 |
Electronic Plan | Original | / | 12/14/2022 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1782049 |
Enumeration | Original | N | 12/14/2022 | AMY | AMY | | | Enumeration | 1781860 |
Electronic Plan | Original | / | 12/14/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1781842 |
Floodplain | Original | N | 12/13/2022 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6233202006) | | Floodplain | 1781603 |