CSU Water | Original | D | 4/25/2024 | CSUREVIEW | CSUREVIEW | Callout the water service with size and material on the plumbing plan. Water Meter Sizing Form indicates the water piping size interior to the building after the water meter shall be 2.5" diameter. Add the appropriate water meter clearance detail B4-16 through 4-22 on the plumbing plan. mjg | mgackle | CSU Water | 1994597 |
CSU Waste Water | Original | D | 4/25/2024 | CSUREVIEW | CSUREVIEW | Callout the wastewater pipe services with size and material on the Plumbing plan. mjg | mgackle | CSU Waste Water | 1994594 |
CSU Waste Water | Original | / | 4/25/2024 | CSUREVIEW | CSUREVIEW | | mgackle | CSU Waste Water | 1994592 |
City Engr | Original | A | 4/25/2024 | JDAGNILLO | JDAGNILLO | | | City Engr | 1994341 |
Plumbing | Original | A | 4/23/2024 | TCRIPPEN | TCRIPPEN | Approved | | Plumbing | 1992823 |
City Engr | Original | D | 4/22/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan in the electronic building permit set. | | City Engr | 1992774 |
CO Springs DRE | Original | D | 4/19/2024 | MOBRIEN | MOBRIEN | Please upload approved development plan stamped by Land Use Review, as well as recorded plat. (see full review) | | CO Springs DRE | 1991613 |
Gas/Elec. Utils | Original | A | 4/17/2024 | CSUREVIEW | CSUREVIEW | Approved development plan and utility construction drawings provided with permit set.
CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. CJS | cjsavage | Gas/Elec. Utils | 1990521 |
CSU Waste Water | Original | D | 4/17/2024 | CSUREVIEW | CSUREVIEW | Refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
Plumbing plan sanitary outfall does not align with provided sanitary outfall on civil drawings. Both plans must match.
Remove unapproved versions of the development plan and water/utility service plans from the permit set. Only the approved development plan and approved utility construction drawings shall be attached. CJS | cjsavage | CSU Waste Water | 1990520 |
CSU Water | Original | D | 4/17/2024 | CSUREVIEW | CSUREVIEW | Refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
Plumbing plan sanitary outfall does not align with provided sanitary outfall on civil drawings. Both plans must match.
Remove unapproved versions of the development plan and water/utility service plans from the permit set. Only the approved development plan and approved utility construction drawings shall be attached. CJS | cjsavage | CSU Water | 1990519 |
Zoning/Planning | Original | / | 4/17/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1990448 |
Submittal 6 | Original | / | 4/17/2024 | QUINTONW | QUINTONW | Submittal #6 | | Submittal 6 | 1990440 |
CO Springs Hazmat | Original | N | 2/12/2024 | CSFIRE | CSFIRE | Below Permit Quantities Submitted By: Stanwood, Mark Antone,Submitted By: Stanwood, Mark Antone | mark.stanwood@colora | CO Springs Hazmat | 1962297 |
CO Springs Fire | Original | A | 2/8/2024 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | rpeterson | CO Springs Fire | 1961266 |
Electrical | Original | A | 1/30/2024 | BERTHA | BERTHA | | | Electrical | 1956807 |
Electronic Plan | Original | / | 1/30/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1956788 |
CSU Contract Admin. | Original | A | 1/26/2024 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved and applicable development charges and fees paid. CZ | c.zani | CSU Contract Admin. | 1955959 |
CSU Contract Admin. | Original | D | 1/25/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted.
Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1955136 |
CO Springs DRE | Original | D | 1/24/2024 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1954833 |
City Engr | Original | D | 1/24/2024 | PMORRIS | PMORRIS | Same comments: Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit. Upload a copy of the Approved Development Plan into the building permit. | | City Engr | 1954816 |
Plumbing | Original | D | 1/24/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1954733 |
CSU Water | Original | D | 1/24/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
MAR | MRoberts | CSU Water | 1954639 |
CSU Waste Water | Original | D | 1/24/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
MAR | MRoberts | CSU Waste Water | 1954638 |
Gas/Elec. Utils | Original | D | 1/24/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MAR | MRoberts | Gas/Elec. Utils | 1954636 |
Submittal 5 | Original | / | 1/24/2024 | BRIANNAM | BRIANNAM | Submittal #5 | | Submittal 5 | 1954623 |
Electrical | Original | D | 8/29/2023 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1892452 |
Electronic Plan | Original | / | 8/29/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1892264 |
CO Springs Fire | Original | D | 8/11/2023 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1883824 |
CO Springs Hazmat | Original | D | 8/11/2023 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1883823 |
City Engr | Original | D | 8/9/2023 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (STM-REV23-0071) | | City Engr | 1882469 |
CSU Water | Original | D | 8/8/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Water | 1882305 |
CSU Waste Water | Original | D | 8/8/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1882301 |
Gas/Elec. Utils | Original | D | 8/8/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | Gas/Elec. Utils | 1882298 |
Plumbing | Original | D | 8/8/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1881888 |
CO Springs DRE | Original | D | 8/8/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1881857 |
Mechanical | Original | A | 8/8/2023 | JUSTINC | JUSTINC | | | Mechanical | 1881845 |
CSU Contract Admin. | Original | D | 8/8/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted : Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
AMS | ASweet | CSU Contract Admin. | 1881825 |
Submittal 4 | Original | / | 8/8/2023 | QUINTONW | QUINTONW | Submittal #4 | | Submittal 4 | 1881801 |
Health Dept. | Original | N | 7/27/2023 | HEALTHDEPT | HEALTHDEPT | Not applicable. Per Keith Ebner, Project Manager of AO, earthmoving activities are < 1 acre. MLL | mlockwood | Health Dept. | 1876781 |
Electrical | Original | D | 5/26/2023 | BERTHA | BERTHA | See progress set for review comments - comments are located on the one-line sheet.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1848516 |
Electronic Plan | Original | / | 5/26/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1848485 |
CO Springs Hazmat | Original | D | 5/22/2023 | CSFIRE | CSFIRE | (DISAPPROVED) HAZARDOUS MATERIALS:
Provide completed Hazarous Materials Operations Triage form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility.
Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2009 IFC Table 105.6.20.
PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS, AND FILL OUT THE REQUESTED INFORMATION.
All forms and packets are available at https://coloradosprings.gov/hazmat | dwithee | CO Springs Hazmat | 1845981 |
CO Springs Fire | Original | D | 5/22/2023 | CSFIRE | CSFIRE | *****(DISAPPROVED) WATER SUPPLIES
To help us ensure there is adequate exterior fire protection, please provide the following:
---XXX-- Fire flow report from CSU with map (where there is no new hydrants and/or this is a an infill project. You can requestion one here: https://www.csu.org/Pages/PermitsApplicationsForms.aspx | dwithee | CO Springs Fire | 1845980 |
City Engr | Original | D | 5/19/2023 | PMORRIS | PMORRIS | Same comment: Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit (ProjectDox #: STM-REV23-0071) Upload a copy of the Approved Development Plan into the building permit. | | City Engr | 1845297 |
CSU Contract Admin. | Original | D | 5/18/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted:
Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1845106 |
Health Dept. | Original | D | 5/18/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1845037 |
Plumbing | Original | D | 5/18/2023 | SHANEN | SHANEN | See progress set for review comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1845020 |
CO Springs DRE | Original | D | 5/17/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1844602 |
CSU Water | Original | D | 5/16/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Water | 1844282 |
CSU Waste Water | Original | D | 5/16/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | CSU Waste Water | 1844281 |
Gas/Elec. Utils | Original | D | 5/16/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 1844277 |
Submittal 3 | Original | / | 5/16/2023 | KALLISTAJ | KALLISTAJ | Submittal #3 | | Submittal 3 | 1844267 |
Electrical | Original | D | 4/11/2023 | BERTHA | BERTHA | See progress set for review comments. Comments are located on the one-line sheet.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1828858 |
Electronic Plan | Original | / | 4/11/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1828826 |
CO Springs Hazmat | Original | D | 4/11/2023 | CSFIRE | CSFIRE | Provide completed hazmat triage form and hazmat inventory sheet | rpeterson | CO Springs Hazmat | 1828769 |
CO Springs Fire | Original | D | 4/11/2023 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | CO Springs Fire | 1828766 |
Health Dept. | Original | D | 3/31/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1824193 |
City Engr | Original | D | 3/31/2023 | PMORRIS | PMORRIS | Same comment: Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit (ProjectDox #: STM-REV23-0071) | | City Engr | 1823892 |
CO Springs DRE | Original | D | 3/30/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1823500 |
CSU Water | Original | D | 3/30/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. CJS | cjsavage | CSU Water | 1823294 |
Gas/Elec. Utils | Original | D | 3/30/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | Gas/Elec. Utils | 1823293 |
CSU Waste Water | Original | D | 3/30/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 1823288 |
Plumbing | Original | D | 3/30/2023 | SHANEN | SHANEN | See progress set for review comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1823178 |
Mechanical | Original | A | 3/30/2023 | JUSTINC | JUSTINC | | | Mechanical | 1823117 |
CSU Contract Admin. | Original | D | 3/30/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previous:
Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1823061 |
Construction | Original | A | 3/30/2023 | BPHILLIPS | BPHILLIPS | | | Construction | 1823054 |
Electronic Plan | Original | / | 3/29/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1822866 |
Enumeration | Original | A | 3/29/2023 | BRENT | BRENT | | | Enumeration | 1822778 |
Electronic Plan | Original | / | 3/29/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1822742 |
Submittal 2 | Original | / | 3/29/2023 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1822708 |
CO Springs Hazmat | Original | D | 2/15/2023 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1803252 |
CO Springs Fire | Original | D | 2/15/2023 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1803250 |
Electrical | Original | D | 2/6/2023 | BERTHA | BERTHA | 1. Provide wire size, type, quantity from the utility transformer to main service disconnect.
2. Provide rated input current in compliance with 430.122 for all VFD’s on the one-line
3. Comply with 450.3 (B) (3) table note 2
4. Provide 2015 IECC
5. Comply with Colorado Springs Utilities – Electric Line Extension Service Standards – Chapter 5 – 5.04 Instrument Transformer – CTs and Vts – CTs cannot be located in customer owned gear.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1799406 |
Health Dept. | Original | D | 2/3/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1798696 |
City Engr | Original | D | 2/1/2023 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (STM-REV23-0071) | | City Engr | 1797856 |
Mechanical | Original | D | 2/1/2023 | JUSTINC | JUSTINC | See (M) sheets for mechanical comments associated with this review
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1797623 |
Electronic Plan | Original | / | 2/1/2023 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1797609 |
Plumbing | Original | D | 1/31/2023 | SHANEN | SHANEN | CSU comments, if any, must be addressed Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1 Minimum number of fixtures.Note: Occupant loads exceeding 15 occupants require a service sink and high/low drinking fountain. B occupancy exceeding 25 occupants requires separate toilet facilities. Provide street address and correct zip code on all plumbing sheets. P1.2: Key note P36 near water entry does not match description. CSU approved utility plans required to verify building drain to sewer connection location/sizing and water service location/sizing. Provide code path that allows floor drains and floor sinks to discharge indirectly to the trench drain. Per section 802.1 Where required. Fixtures not required to be indirectly connected by this section and the exception to section 301.6 shall be directly connected to the plumbing system in accordance with chapter 7. Clarify location of water meter/backflow preventer assembly. P2.1: Clothes washer requires hot and cold water. Clarify location of water meter/backflow preventer assembly. DCW serving HB labeled as ICW. Clarify. P2.2: Provide gpm and/or square footage served by each component of the roof drainage system. P6.1: Water piping materials not listed on table 605.3 and/or 605.4. Piping materials standard not listed on table 702.1, 702.2 and/or 702.3. Provide standards per table 702.4. See clouds. P6.2: Provide required water pipe size analysis data, see 2018 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Schedule drinking fountain and service sink if applicable. P7.1: Show water piping to all fixtures (clothes washer, wall hydrants, etc).Clarify hot water source for the clothes washer and show water piping to the clothes washer. Address comments regarding indirect wastes on sheet P1.2 and adjust waste and vent diagram accordingly. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1797453 |
CSU Contract Admin. | Original | D | 1/31/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1797447 |
Electronic Plan | Original | / | 1/31/2023 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1797439 |
Gas/Elec. Utils | Original | D | 1/31/2023 | CSUREVIEW | CSUREVIEW | Upload approved development plan (with Land Use Review stamp present) and the approved USP (with CSU review stamp present). CM | CoreyM | Gas/Elec. Utils | 1797392 |
CSU Waste Water | Original | D | 1/31/2023 | CSUREVIEW | CSUREVIEW | Upload approved development plan (with Land Use Review stamp present) and the approved USP (with CSU review stamp present). CM | CoreyM | CSU Waste Water | 1797391 |
CSU Water | Original | D | 1/31/2023 | CSUREVIEW | CSUREVIEW | Upload approved development plan (with Land Use Review stamp present) and the approved USP (with CSU review stamp present). CM | CoreyM | CSU Water | 1797389 |
CO Springs DRE | Original | D | 1/31/2023 | ESHAFER | ESHAFER | Upload approved development plan (with Land Use Review stamp present) and the recorded final plat. (see full review) | | CO Springs DRE | 1797318 |
Zoning/Planning | Original | / | 1/31/2023 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1797317 |
Elevators | Original | N | 1/31/2023 | ERIC | ERIC | No conveyance | | Elevators | 1797270 |
Construction | Original | D | 1/31/2023 | BPHILLIPS | BPHILLIPS | Revise occupant load code reference to 2015 IBC and corresponding values. Use 300 sf for OLF in car wash area. LS1.0 - Code summary shows this is to be a sprinklered, but not indicated as such on code study form. Clarify. On architectural site plan, show distance to property line on west side of building. Revise code references on structural sheet - 2015 IBC/ ASCE 7-10. Areas shown on page 2 of code study form do not equal total square footage. Also, car washes are considered B occupancies. Review and revise. Design professional stamp missing from page 3 of code study form. Wrong jurisdiction and wrong code referenced on Comcheck. Colorado Springs is the location, and 2015 IECC is the currently adopted code. Appears north and south components are missing from assembly list. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1797205 |
Electronic Plan | Original | / | 1/30/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1796571 |
Enumeration | Original | D | 1/24/2023 | BRENT | BRENT | The code study form states that the project includes vacuum canopies and a pay canopy, but no elevations are included in the plans. These structures require separate addresses and building permits. Verify whether or not these structures are intended to be built with this plan. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1794818 |
Electronic Plan | Original | / | 1/24/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1794775 |
Floodplain | Original | N | 1/20/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6325418007) | | Floodplain | 1793327 |