Electrical | Original | A | 10/2/2023 | BERTHA | BERTHA | Re-approved - no new plans submitted. | | Electrical | 1907456 |
Electronic Plan | Original | / | 10/2/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1907453 |
Triview Waste Water | Original | A | 9/28/2023 | TRIVIEWMETRO | TRIVIEWMETRO | | rnortonTMD | Triview Waste Water | 1905739 |
Plumbing | Original | A | 9/28/2023 | SHANEN | SHANEN | | | Plumbing | 1905664 |
Submittal 5 | Original | / | 9/28/2023 | QUINTONW | QUINTONW | Submittal #5 | | Submittal 5 | 1905650 |
Triview Water | Original | A | 9/21/2023 | TRIVIEWMETRO | TRIVIEWMETRO | | rnortonTMD | Triview Water | 1902574 |
Triview Waste Water | Original | D | 9/21/2023 | TRIVIEWMETRO | TRIVIEWMETRO | 1. The sand/oil interceptor must be at least 1000 gallons in volume. 2. Per Section 5-9.C.2.d of the District's Sewer Standards, the tank and discharge line shall be vented and the vents shall not tie together less than 42 inches above the tank lid elevation. | rnortonTMD | Triview Waste Water | 1902573 |
Waste Water Div | Original | / | 9/13/2023 | SYSTEM | SYSTEM | Contact Waste Water Div department for approval prior to permit | | Waste Water Div | 1899373 |
Water Division | Original | / | 9/13/2023 | SYSTEM | SYSTEM | Contact Water Division department for approval prior to permit | | Water Division | 1899372 |
Electrical | Original | A | 9/6/2023 | BERTHA | BERTHA | Re-approved. No revisions. No new plans submitted. | | Electrical | 1895902 |
Electronic Plan | Original | / | 9/6/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1895897 |
Plumbing | Original | A | 9/6/2023 | SHANEN | SHANEN | | | Plumbing | 1895673 |
Construction | Original | A | 9/6/2023 | BPHILLIPS | BPHILLIPS | | | Construction | 1895632 |
Electronic Plan | Original | / | 9/6/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1895629 |
Submittal 4 | Original | / | 9/3/2023 | QUINTONW | QUINTONW | Submittal #4 | | Submittal 4 | 1894875 |
Electrical | Original | A | 8/29/2023 | BERTHA | BERTHA | | | Electrical | 1892542 |
Electronic Plan | Original | / | 8/29/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1892453 |
Triview Water | Original | D | 8/11/2023 | TRIVIEWMETRO | TRIVIEWMETRO | Disapproved to allow resubmittal. | rnortonTMD | Triview Water | 1883714 |
Triview Waste Water | Original | D | 8/11/2023 | TRIVIEWMETRO | TRIVIEWMETRO | Disapproved to allow resubmittal. | rnortonTMD | Triview Waste Water | 1883713 |
Donald Wescott Fire (CSFD) | Original | A | 8/10/2023 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L
You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | Donald Wescott Fire (CSFD) | 1883274 |
Plumbing | Original | D | 8/7/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1881179 |
Mechanical | Original | A | 8/4/2023 | JUSTINC | JUSTINC | | | Mechanical | 1880986 |
Submittal 3 | Original | / | 8/4/2023 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 1880963 |
Donald Wescott Hazmat (CSFD) | Original | A | 7/7/2023 | CSFIRE | CSFIRE | You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | smitty91 | Donald Wescott Hazmat (CSFD) | 1867338 |
Donald Wescott Fire (CSFD) | Original | D | 6/23/2023 | CSFIRE | CSFIRE | Walk OK - resubmittal qualifies for walkthrough. please see link for how to request a walkthrough review from Fire: https://coloradosprings.gov/document/walk-thrumemo.pdf
We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | Donald Wescott Fire (CSFD) | 1861308 |
Electrical | Original | D | 6/17/2023 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1858457 |
Health Dept. | Original | N | 6/9/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1328 is valid from 8/1/2023 - 2/1/2024. To continue any earthmoving operations after 2/1/2024, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application . For questions, contact Environmental Health at 719-578-3199 option 3. TG | tguerrero | Health Dept. | 1854889 |
Mechanical | Original | D | 6/9/2023 | JUSTINC | JUSTINC | Still need a Colorado engineer stamp on all (M) pages
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1854595 |
Plumbing | Original | D | 6/9/2023 | SHANEN | SHANEN | Review stopped, incomplete plumbing plan review. Colorado licensed design professional stamp and signature required on all plumbing drawings. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1854536 |
Electronic Plan | Original | / | 6/9/2023 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1854529 |
Construction | Original | A | 6/9/2023 | BPHILLIPS | BPHILLIPS | | | Construction | 1854527 |
Electronic Plan | Original | / | 6/9/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1854515 |
Enumeration | Original | A | 6/8/2023 | AMY | AMY | | | Enumeration | 1853916 |
Electronic Plan | Original | / | 6/8/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1853893 |
Submittal 2 | Original | / | 6/8/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1853710 |
Triview Water | Original | D | 5/10/2023 | TRIVIEWMETRO | TRIVIEWMETRO | Disapproved to allow resubmittal | nharrisTMD | Triview Water | 1841892 |
Triview Waste Water | Original | D | 5/10/2023 | TRIVIEWMETRO | TRIVIEWMETRO | Disapproved to allow resubmittal | nharrisTMD | Triview Waste Water | 1841890 |
Enumeration | Original | D | 5/1/2023 | AMY | AMY | NOTE: ADJUST ADDRESSING ON LABEL PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1837948 |
Monument Zoning | Original | A | 3/30/2023 | TOWNOFMON | TOWNOFMON | Plan conditionally approved by Town of Monument. Permit Fees are due within 10 days of permit authorization. Note that no final Monument Inspection for C/O can be completed unless all permit fees are paid, Development items/requests are completed and inspection requirements are met which could include the Monument Water Department. Any change to the approved plot plan or variations in the model as depicted on the plot plan requires a plot plan modification and re-review. For more information you may email the Planning Department at planning@tomgov.org. Thank you | lukejameskerr | Monument Zoning | 1823230 |
Donald Wescott Hazmat (CSFD) | Original | D | 3/17/2023 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | jt09ff | Donald Wescott Hazmat (CSFD) | 1817892 |
Donald Wescott Fire (CSFD) | Original | D | 2/27/2023 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | Donald Wescott Fire (CSFD) | 1807747 |
Electrical | Original | A | 2/10/2023 | SHELBY | SHELBY | | | Electrical | 1801400 |
Health Dept. | Original | D | 2/9/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.CM | cmille96 | Health Dept. | 1801058 |
Mechanical | Original | D | 2/8/2023 | JUSTINC | JUSTINC | Colorado licensed design professional stamp and signature required
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1800729 |
Electronic Plan | Original | / | 2/8/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1800724 |
Electronic Plan | Original | / | 2/8/2023 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1800718 |
Plumbing | Original | D | 2/8/2023 | SHANEN | SHANEN | Review stopped, incomplete plumbing plan review. Colorado licensed design professional stamp and signature required on all plumbing drawings. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1800638 |
Construction | Original | D | 2/8/2023 | BPHILLIPS | BPHILLIPS | Revise code references as noted. Provide architectural site plan, showing distances to property lines. Show clear floor spaces required for accessibility in pay station. Show all required clear floor spaces for accessibility on enlarged restroom plan. Provide a separate Comcheck for payment booth. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1800602 |
Electronic Plan | Original | / | 2/3/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1798874 |
Enumeration | Original | D | 1/30/2023 | AMY | AMY | 1. I stated numerous times in my comments to Monument Planning department to not use the platted address. This lot is too far away from Baptist Road and this address should not be used, (805 W Baptist Road). Submit a request to change this lot address to the private street name Smile View. The address assigned to the Carwash was also given in my comments. The address is 15424 Smile View. Please submit this request via email to Amy Vanderbeek; Amy@pprbd.org as soon as possible. Link: https://www.pprbd.org/File/Resources/Downloads/Addressing/REQUEST_TO_CHANGE_ADDRESS.pdf
2. There are 3 of the same Code Study forms included. There should only be 1. Please remove the other 2. Correct the address. An additional Code Study form is listed under “Other File” below Spill Containment-If the canopies are the same the both addresses can be added to this Code Study Form. Those addresses are 15420 & 15412 Smile View.
3. In the Architectural pages there needs to be a site plan showing the entire lot with all intended structures and equipment. Surround street need to be shown, north arrow, etc. Enumerations should not be marking up the development plan. The site plan will be used as the addressing plan. See Enumerations plan review requirements here in this link: https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Enumerations%20Plan%20review%20requirements%20V2.pdf
4. Here are the following addresses for this project: The height of the vacuum enclosure is over 7’ therefore, it will require a separate address and permit. Address is 15416 Smile View. The trash enclosure 15414 Smile View, South Canopy 15412 Smile View, North canopy 15420 Smile View. The canopies are detached from the main structure therefore, separate addresses are required. These addresses should be shown on the site plan next to or on top of.
5. Page E1.1, E1.2., is showing the corner lot as Dillion Drive & Eagleridge Blvd, this is incorrect information.
6. All addresses are list on the plan label below. 1 plan 5 permits are required.
7. Address change to the following sheets: Code Study Forms, A pages, Structural, Mechanical, Plumbing, Soils Report.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1796496 |
Elevators | Original | N | 1/27/2023 | ERIC | ERIC | No conveyance | | Elevators | 1796111 |
Electronic Plan | Original | / | 1/27/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1796054 |
Mechanical | Original | / | 1/25/2023 | KALLISTAJ | KALLISTAJ | Overtime approved for Mechanical by Joseph Earnest | | Mechanical | 1795428 |
Enumeration | Original | / | 1/25/2023 | KALLISTAJ | KALLISTAJ | Overtime approved for Enumeration by Joseph Earnest | | Enumeration | 1795427 |
Plumbing | Original | / | 1/25/2023 | KALLISTAJ | KALLISTAJ | Overtime approved for Plumbing by Joseph Earnest | | Plumbing | 1795426 |
Electrical | Original | / | 1/25/2023 | KALLISTAJ | KALLISTAJ | Overtime approved for Electrical by Joseph Earnest | | Electrical | 1795425 |
Construction | Original | / | 1/25/2023 | KALLISTAJ | KALLISTAJ | Overtime approved for Construction by Joseph Earnest | | Construction | 1795424 |
Waste Water Div | Original | / | 1/25/2023 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 1795423 |
Water Division | Original | / | 1/25/2023 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 1795422 |
Floodplain | Original | N | 1/25/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7136201005) | | Floodplain | 1795421 |