Electrical | Original | D | 8/29/2023 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1892573 |
Electronic Plan | Original | / | 8/29/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1892543 |
Health Dept. | Original | N | 7/27/2023 | HEALTHDEPT | HEALTHDEPT | Not applicable. Per Keith Ebner, Project Manager of AO, earthmoving activities are < 1 acre. MLL | mlockwood | Health Dept. | 1876766 |
CO Springs Hazmat | Original | D | 7/24/2023 | CSFIRE | CSFIRE | pending receipt of completed documents required by fire construction review | dwithee | CO Springs Hazmat | 1874333 |
CO Springs Fire | Original | D | 7/24/2023 | CSFIRE | CSFIRE | Previous comments not addressed
We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/fire-department/page/plan-and-construction-review-status (see full review) | csfdit | CO Springs Fire | 1874331 |
CSU Contract Admin. | Original | D | 7/20/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1872844 |
City Engr | Original | D | 7/13/2023 | PMORRIS | PMORRIS | Same comment: Upload a copy of the Approved Development Plan into the building permit. Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. | | City Engr | 1869520 |
Health Dept. | Original | D | 7/12/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | Health Dept. | 1869216 |
Mechanical | Original | A | 7/12/2023 | JUSTINC | JUSTINC | | | Mechanical | 1869061 |
CO Springs DRE | Original | D | 7/11/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1868566 |
Plumbing | Original | D | 7/11/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1868564 |
CSU Water | Original | D | 7/11/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. SSM | stefanm | CSU Water | 1868542 |
CSU Waste Water | Original | D | 7/11/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1868538 |
Gas/Elec. Utils | Original | D | 7/11/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1868533 |
Construction | Original | D | 7/11/2023 | JUSTINL | JUSTINL | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1868528 |
Electronic Plan | Original | / | 7/11/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1868455 |
Enumeration | Original | D | 7/11/2023 | BECKYA | BECKYA | Wrecking Permit 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1868309 |
Submittal 3 | Original | / | 7/11/2023 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 1868274 |
Electrical | Original | D | 5/30/2023 | BERTHA | BERTHA | See progress set for review comments - Comments are located on the one-line sheet.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1849044 |
Electronic Plan | Original | / | 5/26/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1848566 |
CSU Contract Admin. | Original | D | 5/22/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) submitted; however is incomplete. Payment of applicable utility charges and fees will also be required. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CZ | c.zani | CSU Contract Admin. | 1845907 |
Health Dept. | Original | D | 5/17/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1844439 |
CO Springs Hazmat | Original | D | 5/16/2023 | CSFIRE | CSFIRE | PENDING RECEIPT OF COMPLETED DOCUMENTS REQUIRED BY FIRE CONSTRUCTION REVIEW | dwithee | CO Springs Hazmat | 1844145 |
CO Springs Fire | Original | D | 5/16/2023 | CSFIRE | CSFIRE | PREVIOUS REVIEW COMMENTS NOT ADDRESSED (see full review) | csfdit | CO Springs Fire | 1844143 |
City Engr | Original | D | 5/11/2023 | PMORRIS | PMORRIS | Same comment: Upload a copy of the Approved Development Plan into the building permit. Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. | | City Engr | 1842593 |
Mechanical | Original | A | 5/11/2023 | JUSTINC | JUSTINC | | | Mechanical | 1842423 |
Gas/Elec. Utils | Original | D | 5/10/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 1842066 |
Gas/Elec. Utils | Original | D | 5/10/2023 | CSUREVIEW | CSUREVIEW | See previous comments. DMM | dmakings | Gas/Elec. Utils | 1842064 |
CSU Waste Water | Original | D | 5/10/2023 | CSUREVIEW | CSUREVIEW | See previous comments. DMM | dmakings | CSU Waste Water | 1842063 |
CSU Water | Original | D | 5/10/2023 | CSUREVIEW | CSUREVIEW | See previous comments. DMM | dmakings | CSU Water | 1842061 |
Plumbing | Original | D | 5/10/2023 | SHANEN | SHANEN | See progress set for review comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1842048 |
CO Springs DRE | Original | D | 5/10/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1842035 |
Construction | Original | D | 5/10/2023 | JUSTINL | JUSTINL | See review set or progress set for review comments. NOTE: plans appear to be incomplete. Review comments may be incomplete as a result and may be subject to changes. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1841947 |
Electronic Plan | Original | / | 5/9/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1841509 |
Enumeration | Original | D | 5/8/2023 | BECKYA | BECKYA | See plans for disapproval comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1841071 |
Submittal 2 | Original | / | 5/8/2023 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1841061 |
CO Springs Hazmat | Original | D | 3/3/2023 | CSFIRE | CSFIRE | SEE FIRE COMMENTS | jt09ff | CO Springs Hazmat | 1809777 |
CO Springs Fire | Original | D | 3/3/2023 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1809775 |
Health Dept. | Original | D | 2/17/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1804625 |
Electrical | Original | D | 2/17/2023 | BERTHA | BERTHA | Provide compliance with Colorado Springs Utilities – Electric Line Extension and Service Standards – Chapter 5 – 5.04 – CT’s
Provide the rated input current for VFD’s in compliance with 430.122
Comply with 430.5(B) Note 2
Provide 2015 IECC
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1804601 |
Mechanical | Original | D | 2/16/2023 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Remove all notes, data for Denver. This project is located in El Paso County. Revise to adopted 2015 IMC and IFGC code years Provide refrigeration calculation per 2015 IMC 1103.1 Verify if within allowable limits per table on plan. If over the allowable limits indicate how protecting on plan. Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection.
Review stopped
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1803782 |
Electronic Plan | Original | / | 2/16/2023 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1803778 |
City Engr | Original | D | 2/15/2023 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 1803454 |
Electronic Plan | Original | / | 2/15/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1803060 |
Gas/Elec. Utils | Original | D | 2/14/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | Gas/Elec. Utils | 1802734 |
CSU Waste Water | Original | D | 2/14/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 1802733 |
CSU Water | Original | D | 2/14/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. CJS | cjsavage | CSU Water | 1802731 |
CO Springs DRE | Original | D | 2/14/2023 | APAQUETTE | APAQUETTE | Please provide APPROVED development plan entitlement with stamp from city planning. Also provide final plat. (see full review) | | CO Springs DRE | 1802683 |
Plumbing | Original | D | 2/14/2023 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1 Minimum number of fixtures. Separate toilet facilities, a drinking fountain and a service sink may be required based on actual occupant load. CSU comments, if any, must be addressed. P0.1: Reference only 2018 IPC code sections. P0.2: Reference only PPRBD adopted codes. P1.1: Key notes - Remove one of the layers for clarity. Water service is 2" per referenced civil plans, 2-1/2" shown. P1.1A: Provide key notes. P1.2, P2.1: Provide sizing for each section of water distribution and drainage piping. Embolden backgrounds for clarity. Print all key notes within the key notes block for clarity. P2.2: Provide gpm and/or square footage served by each component of the roof drainage system. P6.1: All drainage and water piping materials, fittings and standards shall be per 2018 IPC chapters 6 and 7 material tables. P6.2: Provide required water pipe size analysis data, see 2018 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. P7.1: Provide water diagram/isometric drawing for the complete water distribution system. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1802627 |
Elevators | Original | N | 2/14/2023 | ERIC | ERIC | No conveyance | | Elevators | 1802595 |
CSU Contract Admin. | Original | D | 2/14/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1802556 |
Construction | Original | D | 2/14/2023 | JUSTINL | JUSTINL | PRIMARILY REVIEW ONLY: SEE PLANS Need to address if building is sprinkled or not, Address occupancy load discrepancies, address egress requirements. Compare all pages. lots of conflicting information. Ensure correct code cycle referenced throughout. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1802537 |
Electronic Plan | Original | / | 2/14/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1802479 |
Enumeration | Original | D | 2/8/2023 | BECKYA | BECKYA | A wrecking permit for 7061 Commerce Center Drive will need to be in place before Enumerations can approve the building plan.
Trash enclosure is under 7' in height, no separate address or permit is required. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1800810 |
Floodplain | Original | N | 2/7/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6307003013) | | Floodplain | 1800311 |