Electrical | Original | A | 2/20/2024 | BERTHA | BERTHA | | | Electrical | 1964963 |
County Zoning | Original | D | 2/16/2024 | DSDHOWSER | DSDHOWSER | Per resolution no. 23-360 page 4, 7. The applicant shall process and have an effective LOMR approved by FEMA prior to issuance of any building permits within this filing. | | County Zoning | 1964735 |
Electronic Plan | Original | / | 2/16/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1964729 |
Submittal 6 | Original | / | 2/13/2024 | QUINTONW | QUINTONW | Submittal #6 | | Submittal 6 | 1962803 |
Enumeration | Original | A | 1/25/2024 | AMY | AMY | Secondary address was corrected. | | Enumeration | 1955452 |
Electrical | Original | D | 1/9/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1949540 |
CSU Contract Admin. | Original | A | 1/9/2024 | CSUAPPSPRM | CSUAPPSPRM | Electric Design Fee Paid 1/9/2024. BS | bschifferstein | CSU Contract Admin. | 1949367 |
Electronic Plan | Original | / | 1/9/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1949016 |
County Zoning | Original | D | 1/2/2024 | DSDRANGEL | DSDRANGEL | Per resolution No. 23-360 page 4, 7. The applicant shall process and have an effective LOMR approved by FEMA prior to issuance of any building permits within this filing. | | County Zoning | 1946024 |
CSU Contract Admin. | Original | D | 12/29/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires payment of electric design fee. BS | bschifferstein | CSU Contract Admin. | 1945489 |
Submittal 5 | Original | / | 12/28/2023 | QUINTONW | QUINTONW | Submittal #5 | | Submittal 5 | 1944984 |
County Zoning | Original | D | 12/11/2023 | DSDRANGEL | DSDRANGEL | Per resolution No. 23-360 page 4, 7. The applicant shall process and have an effective LOMR approved by FEMA prior to issuance of any building permits within this filing. | | County Zoning | 1938427 |
Zoning/Planning | Original | / | 12/11/2023 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1938419 |
Electrical | Original | D | 12/7/2023 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1937315 |
CSU Contract Admin. | Original | D | 12/7/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted - Requires payment of electric design fee. Please call 719-668-8111.
AMS | ASweet | CSU Contract Admin. | 1937184 |
Electronic Plan | Original | / | 12/7/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1937098 |
Gas/Elec. Utils | Original | A | 12/6/2023 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions.MDA | malcuran | Gas/Elec. Utils | 1937036 |
Submittal 4 | Original | / | 12/6/2023 | SIERRAC | SIERRAC | Submittal #4 | | Submittal 4 | 1936793 |
County Zoning | Original | D | 10/20/2023 | DSDRANGEL | DSDRANGEL | The site development plan must be approved in EDARP prior to approval in PPRBD's system. Upload a copy of the approved SDP once approved in EDARP. | | County Zoning | 1916514 |
Electrical | Original | D | 10/20/2023 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1916510 |
Electronic Plan | Original | / | 10/20/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1916501 |
CSU Contract Admin. | Original | D | 10/19/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted on 04/21/2023. Requires payment of electric design fee.
AMS | ASweet | CSU Contract Admin. | 1916471 |
Plumbing | Original | A | 10/19/2023 | SHANEN | SHANEN | | | Plumbing | 1916430 |
Gas/Elec. Utils | Original | D | 10/19/2023 | CSUREVIEW | CSUREVIEW | See previous comments. mjg | mgackle | Gas/Elec. Utils | 1916380 |
Construction | Original | A | 10/19/2023 | CGIECK | CGIECK | OK | | Construction | 1916376 |
Electronic Plan | Original | / | 10/19/2023 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1916041 |
Enumeration | Original | A | 10/17/2023 | AMY | AMY | Secondary addressing is incorrect when following the secondary addressing guide. Please see the corrections on sheet T1.09. I will notify CSU & MVEA and provide these changes to them. | | Enumeration | 1914608 |
Submittal 3 | Original | / | 10/12/2023 | BRIANNAM | BRIANNAM | Submittal #3 | | Submittal 3 | 1912799 |
Cimarron Hills Hazmat | Original | A | 4/25/2023 | CHFIRE | CHFIRE | CHFD has reviewed for HAZMAT and they are approved. JT McLeod, Fire Inspector III/Plans Examiner | CHFD1300 | Cimarron Hills Hazmat | 1835334 |
Cimarron Hills Fire | Original | A | 4/25/2023 | CHFIRE | CHFIRE | CHFD has reviewed for fire and life safety and they are approved. JT McLeod, Fire Inspector III/Plans Examiner | CHFD1300 | Cimarron Hills Fire | 1835332 |
Cimarron Hills Fire | Original | A | 4/25/2023 | CHFIRE | CHFIRE | CHFD has reviewed for fire and life safety and they are approved. JT McLeod, Fire Inspector III/Plans Examiner | CHFD1300 | Cimarron Hills Fire | 1835331 |
Electrical | Original | D | 4/24/2023 | BERTHA | BERTHA | See progress set for review comments - Comments are located on the one-line sheet.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1834422 |
Electronic Plan | Original | / | 4/24/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1834399 |
CSU Contract Admin. | Original | D | 4/21/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as 3/16/2023:
Requires payment of Electric Design Fee. Please contact our office at 719-668-8111/cca@csu.org for additional information. AG | aguerin | CSU Contract Admin. | 1833498 |
Gas/Elec. Utils | Original | D | 4/20/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1832968 |
Health Dept. | Original | N | 4/20/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1312 is valid from 3/31/2023 - 9/30/2023. SJ | skirst | Health Dept. | 1832894 |
County Zoning | Original | D | 4/20/2023 | DSDRANGEL | DSDRANGEL | The site development plan must be approved in EDARP prior to approval in PPRBD's system. Upload a copy of the approved SDP once approved in EDARP. | | County Zoning | 1832850 |
Mechanical | Original | A | 4/20/2023 | JUSTINC | JUSTINC | | | Mechanical | 1832842 |
Plumbing | Original | D | 4/20/2023 | SHANEN | SHANEN | P1.32: Per PPRBD plumbing plan review requirements, show DWV piping to each fixture on the enlarged typical unit plans. P1.36: Per PPRBD plumbing plan review requirements, provide an isometric drawing for the complete DWV system. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1832807 |
Construction | Original | D | 4/20/2023 | CGIECK | CGIECK | A5.32 - MISSING ENLARGED PLANS. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1832761 |
Enumeration | Original | D | 4/20/2023 | AMY | AMY | See progress set, page T1.09 for Enumerations comments.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1832690 |
Electronic Plan | Original | / | 4/20/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1832658 |
Submittal 2 | Original | / | 4/19/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1832343 |
Cherokee Water | Original | A | 3/20/2023 | CHEROKEEMETRO | CHEROKEEMETRO | Approved | kbrown | Cherokee Water | 1818526 |
Cherokee Waste Water | Original | A | 3/20/2023 | CHEROKEEMETRO | CHEROKEEMETRO | Approved | kbrown | Cherokee Waste Water | 1818525 |
Electrical | Original | D | 3/16/2023 | BERTHA | BERTHA | 1.Pending approval in Enumeration - Multi meter services must include a list of secondary enumerated addresses on the one-line. Secondary addresses must be approved by Enumeration.
2. Pending approval in Construction – see Construction review comments.
3. Provide all conduit/conductor size, type, and quantity, beginning at the utility transformer, to include all conductors in the chain of supply for the electrical equipment in the scope of work – conductors feeding meter centers
4. Remove parallel neutral – remove equipment ground in service conductor
5.Provide fault current information (SCA, SCCR, AIC) in tabular form, for all new and re-fed electrical equipment including; panel boards, switchboards, service equipment, transfer equipment, elevator control panel, fire pump control panel, industrial control panels, air conditioning and refrigeration equipment.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1817285 |
Mechanical | Original | A | 3/16/2023 | JUSTINC | JUSTINC | | | Mechanical | 1817208 |
Electronic Plan | Original | / | 3/16/2023 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1817187 |
Plumbing | Original | D | 3/16/2023 | SHANEN | SHANEN | P1.30A: 3"DD in breeze way must discharge to the sanitary sewer. P1.32: Show DWV piping to each fixture on the enlarged typical unit plans. P1.36: Provide isometric and/or riser diagram for the complete DWV system showing connections to each stack and horizontal branch of the building drain. Provide drainage fixture units served by the building drain and each section of the building drain. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1817028 |
Electronic Plan | Original | / | 3/16/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1816994 |
Elevators | Original | N | 3/16/2023 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 1816988 |
County Zoning | Original | D | 3/16/2023 | DSDRANGEL | DSDRANGEL | The site development plan must be approved in EDARP prior to approval in PPRBD's system. Upload a copy of the approved SDP once approved in EDARP. | | County Zoning | 1816956 |
CSU Contract Admin. | Original | D | 3/16/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires paymnet of an electric design fee. Please contact 719-668-8111 for more information.
AMS | ASweet | CSU Contract Admin. | 1816900 |
Zoning/Planning | Original | / | 3/16/2023 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1816833 |
Health Dept. | Original | D | 3/15/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3.CM | cmille96 | Health Dept. | 1816681 |
Gas/Elec. Utils | Original | D | 3/15/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | Gas/Elec. Utils | 1816628 |
Construction | Original | D | 3/15/2023 | CGIECK | CGIECK | PLEASE REVIEWED PLAN FOR ADDITIONAL NOTES G2.00 - ALL ASSEMBLIES WHERE THEY ARE INDICATING BOTH A RATED AND UNRATED VERSION, THEY NEED TO DIFFERENTIATE THE WALL TYPES. G2.07 – DETAIL FCA.12 -UL LISTING CALLS FOR TRUSSES NOT JOIST G2.12 – DETAIL 3 NEEDS AN ASSEMBLY FOR THE REDUCED WALL WIDTH WHERE A LISTED ASSEMBLY IS STILL REQUIRED G2.21,G2.24-G2.26 - PLEASE PROVIDE THE MOST UP TO DATE UL LISTING A3.03 – UPDATE MISSING WINDOW TYPES A3.23 – UPDATE MISSING INFORMATION A4.00 - REFERENCE THE CORRECT F/C ASSEMBLIES FOR THE BALCONIES AND DRAW THEM PER THE FLOOR TYPE. A6.21A6.30E - NEED ALL KITCHEN CLEARANCES. MISSING CLEAR FLOOR SPACE FOR WC. UPDATE MISSING LABELING AND CLEARANCES.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1816588 |
Electronic Plan | Original | / | 2/23/2023 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1806323 |
Enumeration | Original | D | 2/22/2023 | AMY | AMY | The tax schedule number and the platted legal description was corrected on the Code Study form for you. Also, the address to building M has been corrected for you on the Life Safety Plan and the Accessibility Plan to 5915 no 5995. If this sheet get changed out please correct this information.
The secondary addressing for all building types should have been provided to this department prior to plan submittal. Please do so, so that the plans can be approved. Amy@pprbd.org
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1805333 |
Electronic Plan | Original | / | 2/17/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1804201 |
Floodplain | Original | N | 2/17/2023 | KEITH | KEITH | | | Floodplain | 1804171 |
Electronic Plan | Original | / | 2/16/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1803847 |
Floodplain | Original | / | 2/15/2023 | RBD GIS | RBD GIS | Autogenerated Review: Floodplain status unknown. (Parcel: 5407200052) | | Floodplain | 1803529 |