City Engr | Original | D | 9/7/2023 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (STM-REV23-0402 & 0404) | | City Engr | 1896845 |
CO Springs Hazmat | Original | A | 9/6/2023 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | CO Springs Hazmat | 1895648 |
Plumbing | Original | D | 9/6/2023 | SHANEN | SHANEN | CSU approved construction drawings required.Plumbing plans must correspond with CSU approved construction drawings. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1895623 |
CSU Contract Admin. | Original | A | 9/5/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved and applicable development charges and fees paid. CZ | c.zani | CSU Contract Admin. | 1895589 |
CO Springs DRE | Original | D | 9/5/2023 | APAQUETTE | APAQUETTE | Approved Development Plan (with Land Use Review approval stamp present) must be uploaded along with the recorded plat. (see full review) | | CO Springs DRE | 1895578 |
CSU Water | Original | D | 9/5/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 1895537 |
CSU Waste Water | Original | D | 9/5/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1895535 |
Gas/Elec. Utils | Original | D | 9/5/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 1895528 |
Construction | Original | A | 9/5/2023 | SHELLEY | SHELLEY | | | Construction | 1895498 |
Enumeration | Original | A | 9/5/2023 | BECKYA | BECKYA | | | Enumeration | 1895292 |
Submittal 5 | Original | / | 9/1/2023 | SHELLEY | SHELLEY | Submittal #5 | | Submittal 5 | 1894585 |
CO Springs Fire | Original | A | 8/31/2023 | CSFIRE | CSFIRE | Submitted By: Stanwood, Mark Antone,Submitted By: Stanwood, Mark Antone (see full review) | csfdit | CO Springs Fire | 1893712 |
CSU Contract Admin. | Original | D | 8/21/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF requires corrections.
AMS | ASweet | CSU Contract Admin. | 1887764 |
CO Springs Fire | Original | D | 8/21/2023 | CSFIRE | CSFIRE | Submitted By: Stanwood, Mark Antone,Submitted By: Stanwood, Mark Antone (see full review) | csfdit | CO Springs Fire | 1887694 |
CO Springs Hazmat | Original | D | 8/21/2023 | CSFIRE | CSFIRE | WE regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | mark.stanwood@colora | CO Springs Hazmat | 1887689 |
Plumbing | Original | A | 8/18/2023 | TCRIPPEN | TCRIPPEN | Approved | | Plumbing | 1886632 |
City Engr | Original | D | 8/18/2023 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 1886511 |
Electrical | Original | A | 8/18/2023 | DANIELG | DANIELG | | | Electrical | 1886486 |
Electronic Plan | Original | / | 8/18/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1886482 |
CSU Water | Original | D | 8/17/2023 | CSUREVIEW | CSUREVIEW | See previous comments.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. | cjsavage | CSU Water | 1886149 |
CSU Waste Water | Original | D | 8/17/2023 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | CSU Waste Water | 1886147 |
Gas/Elec. Utils | Original | D | 8/17/2023 | CSUREVIEW | CSUREVIEW | See previous comments. CJS | cjsavage | Gas/Elec. Utils | 1886146 |
CO Springs DRE | Original | D | 8/17/2023 | MOBRIEN | MOBRIEN | Please upload approved development plan stamped by Land Use Review. (see full review) | | CO Springs DRE | 1886045 |
Zoning/Planning | Original | / | 8/17/2023 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1886043 |
Construction | Original | A | 8/17/2023 | SHELLEY | SHELLEY | Fire riser room and millwork changes. | | Construction | 1885890 |
Enumeration | Original | A | 8/15/2023 | BECKYA | BECKYA | | | Enumeration | 1885051 |
Electronic Plan | Original | / | 8/15/2023 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1885049 |
Submittal 4 | Original | / | 8/15/2023 | BECKYA | BECKYA | Submittal #4 | | Submittal 4 | 1885011 |
CO Springs Hazmat | Original | D | 8/8/2023 | CSFIRE | CSFIRE | We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | mark.stanwood@colora | CO Springs Hazmat | 1881902 |
CO Springs Fire | Original | A | 7/24/2023 | CSFIRE | CSFIRE | We are pleased to inform you this plan is approved and ready for payment. The fee is $312.50. You may remit payment through the EPlans Customer Portal *DO NOT SEND PAYMENT INFORMATION VIA EMAIL* You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1874503 |
Mechanical | Original | A | 7/14/2023 | JUSTINC | JUSTINC | | | Mechanical | 1870468 |
Electrical | Original | D | 7/14/2023 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1870177 |
Electronic Plan | Original | / | 7/14/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1870173 |
CSU Contract Admin. | Original | D | 7/13/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing form submitted however, will need updated plumbing plans before review and approval. CZ | c.zani | CSU Contract Admin. | 1870019 |
City Engr | Original | D | 7/13/2023 | PMORRIS | PMORRIS | Same comment: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1869632 |
Gas/Elec. Utils | Original | D | 7/13/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
MAR | MRoberts | Gas/Elec. Utils | 1869476 |
CSU Water | Original | D | 7/13/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
MAR | MRoberts | CSU Water | 1869473 |
CSU Waste Water | Original | D | 7/13/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
MAR | MRoberts | CSU Waste Water | 1869472 |
Plumbing | Original | D | 7/13/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1869429 |
CO Springs DRE | Original | D | 7/12/2023 | MOBRIEN | MOBRIEN | Please upload approved development plan stamped by Land Use Review. (see full review) | | CO Springs DRE | 1869358 |
Zoning/Planning | Original | / | 7/12/2023 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1869357 |
Construction | Original | A | 7/12/2023 | SHELLEY | SHELLEY | | | Construction | 1869281 |
Enumeration | Original | A | 7/12/2023 | BECKYA | BECKYA | | | Enumeration | 1869030 |
Submittal 3 | Original | / | 7/12/2023 | JAY | JAY | Submittal #3 | | Submittal 3 | 1868951 |
CO Springs Hazmat | Original | D | 6/6/2023 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1852136 |
CO Springs Fire | Original | D | 6/6/2023 | CSFIRE | CSFIRE | Walk OK - resubmittal qualifies for walkthrough. please see link for how to request a walkthrough review from Fire: https://coloradosprings.gov/document/walk-thrumemo.pdf
We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1852129 |
CSU Contract Admin. | Original | D | 6/2/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) submitted however is incomplete. Payment of applicable utility charges and fees will be required upon approval of CWMSF. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CZ | c.zani | CSU Contract Admin. | 1850528 |
Electrical | Original | D | 5/31/2023 | DANIELG | DANIELG | Please see progress report for comments.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1849401 |
Electronic Plan | Original | / | 5/31/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1849386 |
Health Dept. | Original | N | 5/26/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1325 is valid from 7/3/23 - 1/3/24. To continue any earthmoving operations after 1/3/24, please reapply for a new permit online at https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application . For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | Health Dept. | 1848475 |
City Engr | Original | D | 5/26/2023 | PMORRIS | PMORRIS | Same comment: Upload a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (permanent water quality facility) construction plan into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1848404 |
CO Springs DRE | Original | D | 5/26/2023 | CSULLIVAN | CSULLIVAN | This does not have an approved development plan. Please consult your case planner for more details. (see full review) | | CO Springs DRE | 1848247 |
CSU Water | Original | D | 5/25/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Water | 1847970 |
CSU Waste Water | Original | D | 5/25/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1847968 |
Gas/Elec. Utils | Original | D | 5/25/2023 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | Gas/Elec. Utils | 1847940 |
Mechanical | Original | D | 5/25/2023 | JUSTINC | JUSTINC | See progress set.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1847934 |
Plumbing | Original | D | 5/25/2023 | SHANEN | SHANEN | See progress set for review comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1847899 |
Zoning/Planning | Original | / | 5/25/2023 | CSULLIVAN | CSULLIVAN | In Current Review by CSULLIVAN | | Zoning/Planning | 1847882 |
Construction | Original | D | 5/25/2023 | SHELLEY | SHELLEY | See progress/review set. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1847869 |
Enumeration | Original | A | 5/25/2023 | BECKYA | BECKYA | | | Enumeration | 1847691 |
Submittal 2 | Original | / | 5/24/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1847490 |
CO Springs Fire | Original | D | 3/28/2023 | CSFIRE | CSFIRE | We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | dwithee | CO Springs Fire | 1821751 |
CO Springs Hazmat | Original | D | 3/28/2023 | CSFIRE | CSFIRE | pending receipt of completed documents required by fire construction review | dwithee | CO Springs Hazmat | 1821750 |
City Engr | Original | D | 3/16/2023 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 1817286 |
Health Dept. | Original | D | 3/10/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1814738 |
Electrical | Original | D | 3/10/2023 | DANIELG | DANIELG | 1. Comply with 110.26(C)(3) NEC.
2. Provide the SCA and SCCR for all cooling and refrigeration equipment.
3. Add the AIC and SCCR to the fault current schedule.
4. Comply with 240.4(B) NEC. Conductors to 150 fused disconnects are undersized.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1814490 |
CSU Contract Admin. | Original | D | 3/10/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5
CZ | c.zani | CSU Contract Admin. | 1814457 |
Electronic Plan | Original | / | 3/10/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1814432 |
Plumbing | Original | D | 3/10/2023 | SHANEN | SHANEN | CSU and construction review comments must be addressed. P-0: All gas piping related items shall be on the mechanical plans.Remove all references to gas piping from the plumbing plans and provide on the mechanical plans. P-1: S/O piping does not match plumbing legend. Building drain location does not match referenced civil plans. Horizontal dry vent serving PD-1 does not comply with section 905 VENT CONNECTIONS AND GRADES. P-2: Water service entry location and sizing does not match the utility plan. 1"CW is undersized to serve two water closets, two urinals, two lavatories and break sink. P-4: Provide required water pipe size analysis data, see 2018 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1814398 |
Mechanical | Original | D | 3/9/2023 | JUSTINC | JUSTINC | See (M) sheets for mechanical comments
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1814295 |
CSU Water | Original | D | 3/9/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Water | 1814203 |
CSU Waste Water | Original | D | 3/9/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Waste Water | 1814202 |
Gas/Elec. Utils | Original | D | 3/9/2023 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | Gas/Elec. Utils | 1814201 |
CO Springs DRE | Original | D | 3/9/2023 | MOBRIEN | MOBRIEN | Please upload Land Use Review approved (stamped) development plan. (see full review) | | CO Springs DRE | 1814198 |
Construction | Original | D | 3/9/2023 | SHELLEY | SHELLEY | Discrepancy throughout plans on whether building is sprinklered or not. Several items in architectural plans are not applicable. Occupant load for B is gross and cannot remove the garden. Show all exit signs on LSP to clearly indicate which doors are exits and which ones aren't. Show all fire separation distances on site plan. Show accessible clearances for all accessible restroom fixtures. Show turning spaces. Other comments on plans. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1814177 |
Electronic Plan | Original | / | 3/9/2023 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 1814143 |
Elevators | Original | N | 3/2/2023 | ERIC | ERIC | No conveyance | | Elevators | 1809423 |
Enumeration | Original | A | 3/2/2023 | BECKYA | BECKYA | The Structural Plans were updated to show the correct address for this project. If the Structural Plans are resubmitted, please make this change prior to resubmitting the plans.
Per the DP, trash enclosure is under 7’ in height. No separate address or permit is required. | | Enumeration | 1809401 |
Plumbing | Original | / | 3/2/2023 | BECKYA | BECKYA | Overtime approved for Plumbing by David Spratlen | | Plumbing | 1809391 |
Mechanical | Original | / | 3/2/2023 | BECKYA | BECKYA | Overtime approved for Mechanical by David Spratlen | | Mechanical | 1809390 |
Electrical | Original | / | 3/2/2023 | BECKYA | BECKYA | Overtime approved for Electrical by David Spratlen | | Electrical | 1809389 |
Construction | Original | / | 3/2/2023 | BECKYA | BECKYA | Overtime approved for Construction by David Spratlen | | Construction | 1809388 |
Electronic Plan | Original | / | 3/2/2023 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1809386 |
Floodplain | Original | N | 2/28/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7424402019) | | Floodplain | 1808153 |