Electrical | Original | A | 8/15/2023 | SHELBY | SHELBY | | | Electrical | 1885195 |
Electronic Plan | Original | / | 8/15/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1885194 |
Plumbing | Original | A | 7/24/2023 | SHANEN | SHANEN | | | Plumbing | 1874622 |
Mechanical | Original | A | 7/24/2023 | JUSTINC | JUSTINC | | | Mechanical | 1874505 |
Construction | Original | D | 7/24/2023 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1874421 |
Submittal 3 | Original | / | 7/24/2023 | SHELLEY | SHELLEY | Submittal #3 | | Submittal 3 | 1874290 |
Electrical | Original | D | 6/28/2023 | SHELBY | SHELBY | Please include a demo plan clearly showing demolition extent. ( Currently the demo plan and the new work plan are identical). 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1864115 |
Electronic Plan | Original | / | 6/28/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1864112 |
Mechanical | Original | A | 6/5/2023 | JUSTINC | JUSTINC | | | Mechanical | 1851747 |
Plumbing | Original | D | 6/5/2023 | SHANEN | SHANEN | Construction review comments must be addressed. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1851729 |
Construction | Original | D | 6/5/2023 | SHELLEY | SHELLEY | Please see commercial plan review handout for commercial plan requirements.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1851618 |
Enumeration | Original | N | 6/5/2023 | BECKYA | BECKYA | | | Enumeration | 1851301 |
Submittal 2 | Original | / | 6/5/2023 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 1851287 |
CO Springs Hazmat | Original | N | 3/31/2023 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1823898 |
CO Springs Fire | Original | N | 3/31/2023 | CSFIRE | CSFIRE | no fire final | csfdit | CO Springs Fire | 1823895 |
CO Springs DRE | Original | N | 3/22/2023 | CHUDSPETH | CHUDSPETH | Interior commercial remodel, no change of use or occupancy. (see full review) | | CO Springs DRE | 1819355 |
Zoning/Planning | Original | / | 3/22/2023 | CHUDSPETH | CHUDSPETH | In Current Review by CHUDSPETH | | Zoning/Planning | 1819354 |
Electrical | Original | D | 3/21/2023 | BERTHA | BERTHA | See Construction review comments. Electrical Demo is required.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1818847 |
Electronic Plan | Original | / | 3/21/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1818845 |
Mechanical | Original | D | 3/20/2023 | JUSTINC | JUSTINC | See construction reviewer comments. Mechanical review incomplete
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1818413 |
CSU Water | Original | N | 3/20/2023 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 1818374 |
CSU Waste Water | Original | N | 3/20/2023 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Waste Water | 1818371 |
Plumbing | Original | D | 3/20/2023 | SHANEN | SHANEN | Review stopped. Incomplete plumbing plan review. Construction review requirements must be addressed. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1818266 |
Construction | Original | D | 3/20/2023 | SHELLEY | SHELLEY | Plans do not meet RBD commercial plan requirements. Provide code data, structural design data, wall framing detail, scaled plans (1/8" minimum), demo plan, listed assemblies for floor repair, ETC. PRELIMINARY REVIEW ONLY. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1818256 |
Electronic Plan | Original | / | 3/20/2023 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 1818246 |
Enumeration | Original | D | 3/13/2023 | BECKYA | BECKYA | Please provide a site plan in the Architectural Plan pages showing secondary addressing for both floors. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1815158 |
Floodplain | Original | N | 3/9/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7411233011) | | Floodplain | 1813995 |