Electrical | Original | D | 8/13/2024 | BERTHA | BERTHA | 1. Comply with previous review comment - Door swing in room C106 violates 110.26(C)(3) NEC 2. Comply with previous review comment - Electrical approval is not possible without elevator comments being addressed. 3. Comply with previous review comment - Prior approval is required from Colorado Springs Utilities for C/T's in customer owned gear. Approval must be provided with the electrical plan set. 4. Comply with previous review comment - Prior approval is required from Colorado Springs Utilities for termination cabinet. Approval must be provided with the electrical plan set. 5. Comply with previous review comment - Provide withstand rating for all electrical equipment in the fault current calculations table. 6. Comply with previous review comment - Provide fault current information for common space cooling equipment in the fault current calculations table. 7. Specify location of fire pump controller in compliance with 695.4(3)(a)(4) 8. Provide elevator motor on one-line - indicate elevator HP motor. 9. All multi-meter installations must show the secondary addressing that is approved by Enumerations. 10. Comply with 250.122 - revised feeders. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2046014 |
Mechanical | Original | D | 7/24/2024 | DALEH | DALEH | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2036834 |
CO Springs Fire | Original | D | 7/23/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2036207 |
CO Springs Hazmat | Original | D | 7/23/2024 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2036206 |
CO Springs DRE | Original | D | 7/16/2024 | MOBRIEN | MOBRIEN | Site dimensional standards met. However, park, school, police and fire fees for these units have not been paid. Please contact DREPlanningInfo@coloradosprings.gov to pay fees. Plans are stamped and may be approved once fees are paid. (see full review) | | CO Springs DRE | 2032717 |
Health Dept. | Original | D | 7/12/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 2031880 |
Electronic Plan | Original | / | 7/12/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2031616 |
Plumbing | Original | D | 7/12/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2031601 |
Stormwater | Original | N | 7/11/2024 | JLANDON | JLANDON | retaining wall under 4' | | Stormwater | 2031225 |
CSU Contract Admin. | Original | D | 7/11/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires a completed Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. JMD | jdemello | CSU Contract Admin. | 2030998 |
Elevators | Original | D | 7/11/2024 | ERIC | ERIC | There are 2 sets of elevator submittals, 1 for Kone and 1 for Thyssen Krupp, please remove the one you are not going to install. Review not made. . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 2030906 |
Zoning/Planning | Original | / | 7/10/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2030744 |
Construction | Original | D | 7/10/2024 | JUSTINL | JUSTINL | Review is subject to new review comments pending changes that could affect building height and area, life safety, fire ratings and structural components once plans are resubmitted. Full recheck will be required 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2030650 |
Electronic Plan | Original | / | 6/27/2024 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2026053 |
Enumeration | Original | A | 6/27/2024 | BRENT | BRENT | | | Enumeration | 2025999 |
Electronic Plan | Original | / | 6/27/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2025945 |
Submittal 4 | Original | / | 6/27/2024 | BRIANNAM | BRIANNAM | Submittal #4 | | Submittal 4 | 2025925 |
CO Springs Fire | Original | D | 12/4/2023 | CSFIRE | CSFIRE | We regret to inform you this plan is disapproved. You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | dwithee | CO Springs Fire | 1935370 |
CO Springs Hazmat | Original | D | 12/4/2023 | CSFIRE | CSFIRE | PENDING RECEIPT OF COMPLETED DOCUMENTS REQUIRED BY FIRE CONSTRUCTION REVIEW | dwithee | CO Springs Hazmat | 1935369 |
Electrical | Original | D | 11/28/2023 | SHELBY | SHELBY | 1. Door swings in rooms C106 and C115 violate 110.26(C)(3) NEC. 2. Electrical approval in not possible without elevator comments being addressed. 3. Permission is required from SCU for C/T's in customer owned gear. 4. Permission is required from SCU for termination cabinet. 5. Short circuit schedule is missing AIC. 6. Add common space cooling equipment to the short circuit schedule. 7. Show fire pump horse power on one line. 8. Show fire pump location on floor plan;comply 695.4(B)(2)(a)(1) NEC. 9. Specify 4X for panels PE and CP. 10. Provide load summary for MSB-1, MSB-2 and MSB-3. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1933244 |
Electronic Plan | Original | / | 11/27/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1932546 |
Plumbing | Original | D | 11/27/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1932523 |
Mechanical | Original | D | 11/27/2023 | JUSTINC | JUSTINC | Cannot perform mechanical review at this time due to construction reviewer comments. Will need to address construction comment so they can perform their review first.
Also see elevator review comments.
NO WALK 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1932357 |
Electronic Plan | Original | / | 11/27/2023 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1932336 |
Elevators | Original | D | 11/27/2023 | ERIC | ERIC | Basis of design changed to 3-Schindler 3300, full set of preliminary submittals required to do complete review.
See M601, P601, E000 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 1932332 |
CO Springs DRE | Original | D | 11/27/2023 | APAQUETTE | APAQUETTE | Upload approved and recorded final plat. Current upload does not show that its been recorded. (see full review) | | CO Springs DRE | 1932180 |
Zoning/Planning | Original | / | 11/27/2023 | APAQUETTE | APAQUETTE | In Current Review by APAQUETTE | | Zoning/Planning | 1932175 |
Stormwater | Original | D | 11/22/2023 | EWANG | EWANG | Previous comment was not addressed: Retaining wall TW/BW elevations should be labelled on DP, and match approved GEC plan. | | Stormwater | 1931906 |
CSU Contract Admin. | Original | D | 11/22/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted.
Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1931558 |
Health Dept. | Original | D | 11/21/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1931548 |
Construction | Original | D | 11/21/2023 | JUSTINL | JUSTINL | Review stopped. Still have not proven that building will work with proposed occupancies for height and area or separated and non separate occupancies. NOTE that upgrade to project to now include through finish requires an accessibility plan as well. No accessibility plan was provided. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1931526 |
Electronic Plan | Original | / | 11/21/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1931402 |
Enumeration | Original | D | 11/21/2023 | BRENT | BRENT | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1931309 |
Electronic Plan | Original | / | 11/21/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1931268 |
Submittal 3 | Original | / | 11/21/2023 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 1931040 |
Electrical | Original | N | 6/28/2023 | SHELBY | SHELBY | | | Electrical | 1864128 |
Electronic Plan | Original | / | 6/28/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1864126 |
CO Springs Hazmat | Original | D | 6/23/2023 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1861268 |
CO Springs Fire | Original | D | 6/23/2023 | CSFIRE | CSFIRE | We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1861267 |
CSU Contract Admin. | Original | D | 6/9/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted.
Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1854730 |
Stormwater | Original | D | 6/9/2023 | EWANG | EWANG | Retaining wall TW/BW elevations should be labelled on DP, and match approved GEC plan. | | Stormwater | 1854393 |
Plumbing | Original | D | 6/8/2023 | SHANEN | SHANEN | See progress set for review comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1854162 |
Health Dept. | Original | D | 6/8/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. TG | tguerrero | Health Dept. | 1854089 |
CSU Water | Original | A | 6/8/2023 | CSUREVIEW | CSUREVIEW | Comments addressed. MLW | mlwilliams | CSU Water | 1853952 |
CSU Waste Water | Original | A | 6/8/2023 | CSUREVIEW | CSUREVIEW | Comment addressed. MLW | mlwilliams | CSU Waste Water | 1853951 |
Gas/Elec. Utils | Original | A | 6/8/2023 | CSUREVIEW | CSUREVIEW | Comment addressed. MLW | mlwilliams | Gas/Elec. Utils | 1853950 |
Elevators | Original | D | 6/8/2023 | ERIC | ERIC | 3 Kone Monospace 500 machineroomless elevators. 1 with control space, 2 with entrance frame controllers. Provide full sets of elevator submittals at next phase of construction plan review.
See progress set A403.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Elevators | 1853880 |
Construction | Original | D | 6/8/2023 | JUSTINL | JUSTINL | Review stopped. Still have not proven that building will work with proposed occupancies for height and area or separated and non separate occupancies. With the presence of newly indicated firewalls, A sum of ratio calculation will be required for each building and not the overall structure. If any proposed occupancies are intended to be non separated, will need to prove that non separated occupancy will work. Indicate if any occupancy is accessory occupancy and prove that proposed occupancy will meet requirements of an accessory occupancy. Unable to continue review until this is addressed. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1853872 |
Electronic Plan | Original | / | 6/8/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1853828 |
Enumeration | Original | D | 6/7/2023 | BRENT | BRENT | PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1853357 |
Electronic Plan | Original | / | 6/7/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1853305 |
Submittal 2 | Original | / | 6/7/2023 | KALLISTAJ | KALLISTAJ | Submittal #2 | | Submittal 2 | 1852821 |
CO Springs DRE | Original | A | 4/21/2023 | PLANGE | PLANGE | The plan set submitted for building permit review is consistent with the approved development plan set (DEPN-22-0063). (see full review) | | CO Springs DRE | 1833354 |
CO Springs Hazmat | Original | D | 4/20/2023 | CSFIRE | CSFIRE | | Jacob.Watson | CO Springs Hazmat | 1832712 |
CO Springs Fire | Original | D | 4/20/2023 | CSFIRE | CSFIRE | Submitted By: Watson, Jacob Thomas
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1832708 |
Plumbing | Original | D | 4/11/2023 | SHANEN | SHANEN | Preliminary review. See progress set for review comments. PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Plumbing | 1828606 |
Electrical | Original | A | 4/10/2023 | SHELBY | SHELBY | UNG only | | Electrical | 1827922 |
Electronic Plan | Original | / | 4/10/2023 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1827918 |
Health Dept. | Original | D | 4/10/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1827636 |
City Engr | Original | A | 4/7/2023 | PMORRIS | PMORRIS | | | City Engr | 1827168 |
CSU Contract Admin. | Original | D | 4/7/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1827151 |
Mechanical | Original | N | 4/7/2023 | JUSTINC | JUSTINC | No mechanical scope indicated for superstructure permit | | Mechanical | 1827117 |
Zoning/Planning | Original | A | 4/7/2023 | PLANGE | PLANGE | The plan set submitted for building permit review is consistent with the approved development plan set (DEPN-22-0063). | | Zoning/Planning | 1827112 |
Elevators | Original | A | 4/7/2023 | ERIC | ERIC | Superstructure only
3 Kone Monospace 500 machineroom-less traction elevators. | | Elevators | 1827102 |
CSU Water | Original | D | 4/7/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. ------------------------------------------------------------------------------------------------------------------------------------------ Reference Colorado Springs Utilities Water LESS meter detail with correct size after approval of Commercial Water Meter Sizing Form. MLW | mlwilliams | CSU Water | 1827069 |
CSU Waste Water | Original | D | 4/7/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Waste Water | 1827068 |
Gas/Elec. Utils | Original | D | 4/7/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | Gas/Elec. Utils | 1827067 |
Construction | Original | D | 4/6/2023 | JUSTINL | JUSTINL | PRELIMINARY REVIEW ONLY: See progress set for review comments.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1826944 |
Electronic Plan | Original | / | 4/5/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1826341 |
Enumeration | Original | D | 4/4/2023 | BRENT | BRENT | PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Enumeration | 1825725 |
Electronic Plan | Original | / | 4/4/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1825633 |
Floodplain | Original | N | 3/20/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5307000114) | | Floodplain | 1818606 |