Plan Coordinator (Main) | Original | D | 3/14/2024 | JAY | JAY | Disapprove all remaining departments to allow plan to be resubmitted | | Plan Coordinator (Main) | 1975248 |
Tri-Lakes Fire (CSFD) | Original | D | 11/29/2023 | CSFIRE | CSFIRE | We regret to inform you this plan is disapproved. You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account.
WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/fire-department/page/plan-and-construction-review-status | dwithee | Tri-Lakes Fire (CSFD) | 1933428 |
Electrical | Original | D | 11/20/2023 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1930633 |
Electronic Plan | Original | / | 11/20/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1930625 |
Health Dept. | Original | N | 11/17/2023 | HEALTHDEPT | HEALTHDEPT | Colorado Department of Health and Environment Air Pollutant Emission Notice (APEN) may be required for projects earthmoving > 25 acres. Contact CDPHE for more information or visit their website at https://cdphe.colorado.gov/apens-and-air-permits/do-you-need-an-apen-or-air-permit.TG | tguerrero | Health Dept. | 1930279 |
Elevators | Original | D | 11/16/2023 | ERIC | ERIC | Review cannot be completed without elevator submittals. See M004, A173, A174, A183, E193.1 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 1929454 |
Mechanical | Original | D | 11/16/2023 | JUSTINC | JUSTINC | After further review with elevator reviewer this fan is not indicated in the (M) drawings, however there is a drawing in the (A) sheets that indicate something on top of the hoistway. Clarify on (M) sheets if fan will be installed. Show locations and duct routing. If no fan will be installed remove fan from schedule 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1929426 |
Construction | Original | D | 11/15/2023 | JUSTINL | JUSTINL | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1929029 |
Plumbing | Original | D | 11/15/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1928722 |
Electronic Plan | Original | / | 11/15/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1928700 |
Enumeration | Original | D | 11/15/2023 | BECKYA | BECKYA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1928645 |
Submittal 4 | Original | / | 11/15/2023 | QUINTONW | QUINTONW | Submittal #4 | | Submittal 4 | 1928568 |
Monument Zoning | Original | D | 8/16/2023 | TOWNOFMON | TOWNOFMON | DECLINED-This project is not completed in Planning yet. Cannot review without final planning approval. | lukejameskerr | Monument Zoning | 1885463 |
Electrical | Original | D | 8/8/2023 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1882065 |
Electronic Plan | Original | / | 8/8/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1882054 |
Tri-Lakes Hazmat (CSFD) | Original | N | 8/7/2023 | CSFIRE | CSFIRE | na | phil.valdez | Tri-Lakes Hazmat (CSFD) | 1881276 |
Tri-Lakes Fire (CSFD) | Original | D | 8/7/2023 | CSFIRE | CSFIRE | We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1881275 |
Health Dept. | Original | D | 8/3/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1879716 |
Mechanical | Original | A | 8/1/2023 | JUSTINC | JUSTINC | | | Mechanical | 1878430 |
Plumbing | Original | D | 7/31/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1878218 |
Elevators | Original | D | 7/31/2023 | ROBERTV | ROBERTV | Basis of Design as noted on A183 is an Otis Hydrofit 2100 lbs / 125 fpm Machine Room-Less Hydraulic Elevator, no submittals or specifications provided.
Please see disapproval comments on pages: G000, S160, A173, A174, A183, P003, E193.1 E1002. . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 1878116 |
Construction | Original | D | 7/31/2023 | JUSTINL | JUSTINL | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1877954 |
Electronic Plan | Original | / | 7/28/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1877366 |
Enumeration | Original | D | 7/28/2023 | BECKYA | BECKYA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1876962 |
Submittal 3 | Original | / | 7/27/2023 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 1876624 |
Plan Coordinator (Main) | Original | D | 7/18/2023 | JUSTINL | JUSTINL | Disapprove all remaining departments to allow plan to be resubmitted | | Plan Coordinator (Main) | 1871515 |
Construction | Original | D | 7/18/2023 | JUSTINL | JUSTINL | Preliminary review only. Comments from previous review not addressed. Provide narrative of all changes and corrections to plans going forward. This should be uploaded with plan submittal to the "Other" document type going forward. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1871514 |
Electronic Plan | Original | / | 7/14/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1870427 |
Enumeration | Original | D | 7/13/2023 | BECKYA | BECKYA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1869964 |
Submittal 2 | Original | / | 7/13/2023 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 1869670 |
Plan Coordinator (Main) | Original | D | 6/30/2023 | JUSTINL | JUSTINL | Disapprove all remaining departments to allow plan to be resubmitted 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plan Coordinator (Main) | 1865541 |
Construction | Original | D | 6/30/2023 | JUSTINL | JUSTINL | Preliminary review only. RBD policy is that 100% completed construction documents be submitted for reviews. Will review once 100% CD are provided. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1865496 |
Electronic Plan | Original | / | 6/28/2023 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 1864057 |
Enumeration | Original | D | 6/28/2023 | BECKYA | BECKYA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1864042 |
Electronic Plan | Original | / | 6/28/2023 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1863839 |
Floodplain | Original | N | 6/28/2023 | KEITH | KEITH | | | Floodplain | 1863758 |
Waste Water Div | Original | / | 6/13/2023 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 1855669 |
Fire | Original | / | 6/13/2023 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 1855668 |
Hazmat | Original | / | 6/13/2023 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 1855667 |