CO Springs Hazmat | Original | D | 9/22/2023 | CSFIRE | CSFIRE | We regret to inform you, this plan is disapproved. You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | mark.stanwood@colora | CO Springs Hazmat | 1903345 |
Mechanical | Original | D | 9/18/2023 | DALEH | DALEH | Need to respond to all previous comments Responses to comments must be on the plan sheets response letters are not a means of approval 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1900712 |
CSU Contract Admin. | Original | D | 9/15/2023 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted:
Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1900244 |
Electrical | Original | D | 9/15/2023 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1900207 |
Electronic Plan | Original | / | 9/15/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1900040 |
Elevators | Original | D | 9/14/2023 | ERIC | ERIC | Basis of design-2 Schindler machineroom-less traction elevators with fire rated suspension means. Generator power in question. Full sets of elevator submittals are required prior to issuance of elevator permits.
See E011, E110B, E111C, E120B, P002, M001 Review incomplete . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 1899666 |
Health Dept. | Original | D | 9/14/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1899620 |
CO Springs DRE | Original | A | 9/14/2023 | ESHAFER | ESHAFER | Approved per DEPN-22-0070 & PUDD-23-0018. Development must conform to approved development plan. The outstanding non-compliant ADA parking stall on site (subject to a Letter Agreement) has been rectified and inspected for compliance as of 7/18/23. (see full review) | | CO Springs DRE | 1899557 |
City Engr | Original | A | 9/13/2023 | JDAGNILLO | JDAGNILLO | | | City Engr | 1898926 |
Zoning/Planning | Original | / | 9/12/2023 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1898813 |
CSU Water | Original | D | 9/12/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Water | 1898795 |
CSU Waste Water | Original | D | 9/12/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 1898792 |
Plumbing | Original | D | 9/12/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1898778 |
Construction | Original | D | 9/12/2023 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1898767 |
Enumeration | Original | N | 9/11/2023 | BRENT | BRENT | | | Enumeration | 1898037 |
Electronic Plan | Original | / | 9/11/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1898024 |
Submittal 3 | Original | / | 9/8/2023 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 1897537 |
CSU Contract Admin. | Original | D | 8/4/2023 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter sizing form approved - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8111 / cca@csu.org for additional information. CZ | c.zani | CSU Contract Admin. | 1880792 |
CSU Contract Admin. | Original | / | 8/4/2023 | CSUAPPSPRM | CSUAPPSPRM | | c.zani | CSU Contract Admin. | 1880789 |
CO Springs Hazmat | Original | D | 7/25/2023 | CSFIRE | CSFIRE | You are responsible for reviewing the disapproval comments found on the CSFD website and responding to them in your resubmittal to RBD: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | smitty91 | CO Springs Hazmat | 1875014 |
CSU Contract Admin. | Original | D | 7/19/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
CZ | c.zani | CSU Contract Admin. | 1872337 |
Mechanical | Original | D | 7/19/2023 | DALEH | DALEH | See progress set for comments 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1872227 |
CO Springs DRE | Original | A | 7/19/2023 | ESHAFER | ESHAFER | Approved per DEPN-22-0070 & PUDD-23-0018. Development must conform to approved development plan. The outstanding non-compliant ADA parking stall on site (subject to a Letter Agreement) has been rectified and inspected for compliance as of 7/18/23. (see full review) | | CO Springs DRE | 1872199 |
Electronic Plan | Original | / | 7/18/2023 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1871609 |
Plumbing | Original | D | 7/17/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1871424 |
Electrical | Original | D | 7/17/2023 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1871252 |
City Engr | Original | D | 7/17/2023 | PMORRIS | PMORRIS | Upload a copy of the Approved Development Plan into the building permit. | | City Engr | 1871230 |
CO Springs Fire | Original | A | 7/17/2023 | CSFIRE | CSFIRE | We are pleased to inform you this plan is approved You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION!
PLANS HAVE BEEN CHECKED IN FOR HAZMAT REVIEW (see full review) | csfdit | CO Springs Fire | 1871031 |
Electronic Plan | Original | / | 7/17/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1871003 |
Zoning/Planning | Original | / | 7/17/2023 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1870935 |
Elevators | Original | D | 7/14/2023 | ROBERTV | ROBERTV | Need to provide elevator submittals or preliminary drawings to perform a complete review.
See progress set pages listed for disapproval commnets: AS400, AS401, M102D, M102C, P002, E122C, E122D, E100B, E101C, E101D, E102C, E102D, E110B, E111C, E111D, E112C, E112D, E120B, E121C 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 1870521 |
Health Dept. | Original | D | 7/14/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | Health Dept. | 1870211 |
Gas/Elec. Utils | Original | A | 7/13/2023 | CSUREVIEW | CSUREVIEW | No apparent conflicts. MAR | MRoberts | Gas/Elec. Utils | 1869941 |
CSU Waste Water | Original | D | 7/13/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
MAR | MRoberts | CSU Waste Water | 1869939 |
CSU Water | Original | D | 7/13/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
MAR | MRoberts | CSU Water | 1869937 |
Construction | Original | D | 7/13/2023 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1869916 |
Electronic Plan | Original | / | 7/13/2023 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 1869448 |
Enumeration | Original | N | 7/12/2023 | BRENT | BRENT | | | Enumeration | 1869322 |
Electronic Plan | Original | / | 7/12/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1869282 |
Submittal 2 | Original | / | 7/12/2023 | JAY | JAY | Submittal #2 | | Submittal 2 | 1869243 |
Plan Coordinator (Main) | Original | D | 7/5/2023 | SHELLEY | SHELLEY | Disapprove all remaining departments to allow plan to be resubmitted = SEE CONSTRUCTION REVIEW. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plan Coordinator (Main) | 1866394 |
Construction | Original | D | 7/5/2023 | SHELLEY | SHELLEY | NO REVIEW PERFORMED. Need clarification on submittal. Two architectural sets provided, one for finish and one for superstructure. Clarify level of completion for this submittal, remove set that is not applicable. Combine sets if through finish. Do not provide separate plans for the super structure and the finish, should be one complete plan set for the phase to be completed under this scope. If a phased project, submit correctly as a phase project. Currently submitted as a complete building. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1866393 |
Electronic Plan | Original | / | 7/5/2023 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 1866391 |
Enumeration | Original | D | 6/30/2023 | BRENT | BRENT | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1865475 |
Electronic Plan | Original | / | 6/30/2023 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1865104 |
Floodplain | Original | N | 6/28/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220001022) | | Floodplain | 1864113 |