Energy | Original | D | 2/28/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1969080 |
Electrical | Original | D | 2/28/2024 | RICHG | RICHG | Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
Provide SCA and SCCR for all refrigeration equipment. Must be listed out for each roof top and all refrigeration equipment.
Show location of fire pump.
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1969079 |
CO Springs Fire | Original | D | 2/22/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 1966720 |
CO Springs Hazmat | Original | D | 2/22/2024 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 1966719 |
Electronic Plan | Original | / | 2/22/2024 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1966387 |
CO Springs DRE | Original | D | 2/7/2024 | APAQUETTE | APAQUETTE | Upload recorded final plat. (see full review) | | CO Springs DRE | 1960763 |
Health Dept. | Original | D | 2/7/2024 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0. Please email application and all required documents to healthinfo@elpasoco.com.
Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application.
For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | Health Dept. | 1960676 |
City Engr | Original | D | 2/7/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set (Project Dox #STM-REV23-0798). | | City Engr | 1960424 |
CSU Contract Admin. | Original | D | 2/6/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5
AMS | ASweet | CSU Contract Admin. | 1960133 |
Mechanical | Original | D | 2/6/2024 | JUSTINC | JUSTINC | Comment from last review for refrigeration calculations for each walk-in cooler or freezer Must be addressed. Response letter says to see refrigeration drawings which does not indicate this data. Provide calculation for each and indicate how protecting if over allowable limits. Or show alarm locations. This must be addressed before mechanical permit can be issued 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1960024 |
Zoning/Planning | Original | / | 2/6/2024 | APAQUETTE | APAQUETTE | In Current Review by APAQUETTE | | Zoning/Planning | 1959909 |
CSU Water | Original | D | 2/6/2024 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Water | 1959907 |
CSU Waste Water | Original | D | 2/6/2024 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1959904 |
Construction | Original | D | 2/6/2024 | BPHILLIPS | BPHILLIPS | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1959834 |
Plumbing | Original | D | 2/5/2024 | SHANEN | SHANEN | ////PPRBD note: See sheet P6.0 detail 2 to address sheet P1.0 floor drains in coolers/freezers comment.\\\\ 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1959548 |
Electronic Plan | Original | / | 2/5/2024 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1959492 |
Enumeration | Original | A | 2/5/2024 | AMY | AMY | | | Enumeration | 1959377 |
Electronic Plan | Original | / | 2/5/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1959362 |
Submittal 2 | Original | / | 2/5/2024 | BRIANNAM | BRIANNAM | Submittal #2 | | Submittal 2 | 1959299 |
CO Springs Fire | Original | D | 12/4/2023 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. (see full review) | phil.valdez | CO Springs Fire | 1935310 |
CO Springs Hazmat | Original | D | 12/4/2023 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. (see full review) | phil.valdez | CO Springs Hazmat | 1935309 |
Energy | Original | D | 11/20/2023 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1930547 |
Electrical | Original | D | 11/20/2023 | RICHG | RICHG | Indicate copper or aluminum wire on plan. Show feeder schedule for one type. Alternates are not allowed.
Provide SCA and SCCR for all refrigeration equipment.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Comply with 445.18 (C) NEC
Show location of fire pump.
_______________________________________________________________________________________________________ 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1930546 |
Health Dept. | Original | D | 11/17/2023 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application. For questions, contact Environmental Health at 719-578-3199 option 3.
Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. TG | tguerrero | Health Dept. | 1930284 |
Electronic Plan | Original | / | 11/17/2023 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 1930234 |
CSU Contract Admin. | Original | D | 11/17/2023 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
Thank you-BS | bschifferstein | CSU Contract Admin. | 1930068 |
Plumbing | Original | D | 11/17/2023 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1930021 |
Mechanical | Original | D | 11/17/2023 | JUSTINC | JUSTINC | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1929951 |
CO Springs DRE | Original | D | 11/17/2023 | APAQUETTE | APAQUETTE | Upload approved DP numbered DEPN-23-0016 and recorded final plat (see full review) | | CO Springs DRE | 1929945 |
Electronic Plan | Original | / | 11/17/2023 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1929923 |
City Engr | Original | D | 11/17/2023 | PMORRIS | PMORRIS | Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit. | | City Engr | 1929901 |
Elevators | Original | N | 11/17/2023 | ERIC | ERIC | No conveyance | | Elevators | 1929873 |
CSU Water | Original | D | 11/17/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. SSM | stefanm | CSU Water | 1929859 |
CSU Waste Water | Original | D | 11/17/2023 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 1929854 |
Gas/Elec. Utils | Original | A | 11/17/2023 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. SSM | stefanm | Gas/Elec. Utils | 1929852 |
Construction | Original | D | 11/17/2023 | BPHILLIPS | BPHILLIPS | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1929844 |
Electronic Plan | Original | / | 11/15/2023 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1929048 |
Enumeration | Original | A | 11/15/2023 | AMY | AMY | | | Enumeration | 1928966 |
Electronic Plan | Original | / | 11/15/2023 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1928945 |
Energy | Original | / | 10/26/2023 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1919061 |
Floodplain | Original | N | 10/26/2023 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220402004) | | Floodplain | 1919060 |