CO Springs Hazmat | Original | D | 5/3/2024 | CSFIRE | CSFIRE | (DISAPPROVED) CARBON DIOXIDE
It appears that carbon dioxide will be used in this facility. Prior to approval of these plans we will need a CSFD CO2 declaration completed, signed, dated, and returned with construction set of plans. You fill find this enclosed or you can access it on our website. https://csfd.coloradosprings.gov/public-safety/fire/fire-code-and-permits/new-construction | chiptaylor | CO Springs Hazmat | 1998223 |
CO Springs Fire | Original | D | 5/3/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 1998222 |
Energy | Original | A | 4/24/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1993510 |
Mechanical | Original | A | 4/24/2024 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 1993509 |
Plumbing | Original | A | 4/23/2024 | SHANEN | SHANEN | | | Plumbing | 1993057 |
CO Springs DRE | Original | A | 4/19/2024 | MOBRIEN | MOBRIEN | See previous approval comments. | | CO Springs DRE | 1991604 |
Health Dept. | Original | D | 4/19/2024 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | Health Dept. | 1991509 |
Electrical | Original | A | 4/18/2024 | DANIELG | DANIELG | | | Electrical | 1991309 |
CSU Waste Water | Original | D | 4/17/2024 | CSUREVIEW | CSUREVIEW | Previous comments not addressed: Provide the grease interceptor sizing form at https://www.csu.org/Documents/GreaseInterceptorSizingForm.pdf?csf=1&e=PJyGju. Sizing should include all fixtures draining to GI, from all tenant spaces. Original approved utility construction drawings call for a 3000 gal grease interceptor, these plumbing plans specify a 5000 gal interceptor. If the larger 5000 gal interceptor is needed then a revision to the utility service plans will be required. CJS | cjsavage | CSU Waste Water | 1990380 |
Zoning/Planning | Original | / | 4/17/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1990309 |
Construction | Original | A | 4/17/2024 | CGIECK | CGIECK | APPROVED | | Construction | 1990299 |
Electronic Plan | Original | / | 4/17/2024 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1990290 |
Enumeration | Original | A | 4/16/2024 | BECKYA | BECKYA | | | Enumeration | 1989973 |
Submittal 2 | Original | / | 4/16/2024 | BRIANNAM | BRIANNAM | Submittal #2 | | Submittal 2 | 1989858 |
CO Springs Fire | Original | D | 3/8/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 1972869 |
CO Springs Hazmat | Original | D | 3/8/2024 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 1972868 |
Mechanical | Original | D | 2/22/2024 | TCRIPPEN | TCRIPPEN | Disapproved:see either the "Progress Set" or the "Review Set" for required corrections. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1966567 |
Energy | Original | D | 2/22/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1966568 |
Electrical | Original | D | 2/21/2024 | DANIELG | DANIELG | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1965678 |
Electronic Plan | Original | / | 2/21/2024 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1965642 |
City Engr | Original | N | 2/20/2024 | JDAGNILLO | JDAGNILLO | | | City Engr | 1965327 |
CO Springs DRE | Original | A | 2/20/2024 | MOBRIEN | MOBRIEN | Approved for interior finish for new restaurant. Use is permitted per approved development plan. No CDI fees owed. Exterior signage is NOT approved with this permit. | | CO Springs DRE | 1965247 |
CSU Contract Admin. | Original | N | 2/20/2024 | CSUAPPSPRM | CSUAPPSPRM | No fees due this plan set. CZ | c.zani | CSU Contract Admin. | 1965087 |
Elevators | Original | N | 2/20/2024 | ERIC | ERIC | No conveyance | | Elevators | 1964969 |
Zoning/Planning | Original | / | 2/20/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1964953 |
Gas/Elec. Utils | Original | N | 2/20/2024 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. CJS | cjsavage | Gas/Elec. Utils | 1964945 |
CSU Water | Original | N | 2/20/2024 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 1964944 |
CSU Waste Water | Original | D | 2/20/2024 | CSUREVIEW | CSUREVIEW | Provide the grease interceptor sizing form at https://www.csu.org/Documents/GreaseInterceptorSizingForm.pdf?csf=1&e=PJyGju. Sizing should include all fixtures draining to GI, from all tenant spaces. Original approved utility construction drawings call for a 3000 gal grease interceptor, these plumbing plans specify a 5000 gal interceptor. If the larger 5000 gal interceptor is needed then a revision to the utility service plans will be required. CJS | cjsavage | CSU Waste Water | 1964942 |
Health Dept. | Original | D | 2/16/2024 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1964883 |
Construction | Original | D | 2/16/2024 | CGIECK | CGIECK | PLEASE REVIEW PROGRESS SET. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1964840 |
Plumbing | Original | D | 2/16/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1964561 |
Electronic Plan | Original | / | 2/16/2024 | CGIECK | CGIECK | In Current Review by CGIECK | | Electronic Plan | 1964383 |
Enumeration | Original | D | 2/15/2024 | BECKYA | BECKYA | Update all plan pages to show the correct Suite number, should be suite 110. Structural Plan pages show an incorrect address and suite number. Please update to show 1824 Democracy Pt SUITE 110.
Additionally, please provide the correct TSN on the Code Study Form and provide secondary addressing and separation of spaces on the second page of the Architectural Plans, see plans for the redlines.
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 1964284 |
Electronic Plan | Original | / | 2/15/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1964251 |
Energy | Original | / | 2/7/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1960748 |
Floodplain | Original | N | 2/7/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220402002) | | Floodplain | 1960747 |