Energy | Original | D | 11/11/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2083670 |
Electrical | Original | D | 11/11/2024 | BERTHA | BERTHA | Provide Harmonic Filter specification.
Provide new panel OP-H2 schedule. Provide panel schedules to include - disconnect and panel ampacity, panelboard AIC rating, volt amps on all branch circuits and calculated load of panel in amps
Provide available fault current and withstand rating of new panel.
Provide service load summary. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2083669 |
Electronic Plan | Original | / | 11/5/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2082025 |
Submittal 2 | Original | / | 11/4/2024 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2081378 |
Ellicott Fire | Original | A | 2/29/2024 | ELLICOTTFIRE | ELLICOTTFIRE | EFD Approved, MAS For EFD | ELLICOTTFD | Ellicott Fire | 1969416 |
Ellicott Hazmat | Original | N | 2/29/2024 | ELLICOTTFIRE | ELLICOTTFIRE | EFD N/A No Hazmat MAS for EFD | ELLICOTTFD | Ellicott Hazmat | 1969415 |
Energy | Original | D | 2/28/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1968675 |
Electrical | Original | D | 2/28/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1968674 |
Electronic Plan | Original | / | 2/28/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1968637 |
Mechanical | Original | N | 2/26/2024 | DALEH | DALEH | | | Mechanical | 1967754 |
Plumbing | Original | N | 2/26/2024 | SHANEN | SHANEN | | | Plumbing | 1967738 |
County Zoning | Original | N | 2/26/2024 | DSDRANGEL | DSDRANGEL | | | County Zoning | 1967691 |
Zoning/Planning | Original | / | 2/26/2024 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1967656 |
Enumeration | Original | N | 2/26/2024 | BECKYA | BECKYA | updated interior site plan under images | | Enumeration | 1967631 |
Water Division | Original | / | 2/22/2024 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 1966726 |
Waste Water Div | Original | / | 2/22/2024 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 1966727 |
Energy | Original | / | 2/22/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1966725 |
Floodplain | Original | N | 2/22/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 3500000275) | | Floodplain | 1966724 |