CSU Water | Original | N | 4/24/2024 | CSUREVIEW | CSUREVIEW | No plumbing scope of work. MLW | mlwilliams | CSU Water | 1993876 |
CSU Waste Water | Original | N | 4/24/2024 | CSUREVIEW | CSUREVIEW | No plumbing scope of work. MLW | mlwilliams | CSU Waste Water | 1993874 |
Gas/Elec. Utils | Original | N | 4/24/2024 | CSUREVIEW | CSUREVIEW | No apparent conflicts. MLW | mlwilliams | Gas/Elec. Utils | 1993870 |
CO Springs Hazmat | Original | N | 4/24/2024 | CSFIRE | CSFIRE | | MrLouis | CO Springs Hazmat | 1993858 |
CO Springs Fire | Original | N | 4/24/2024 | CSFIRE | CSFIRE | No inspection required. (see full review) | MrLouis | CO Springs Fire | 1993856 |
CO Springs DRE | Original | N | 4/24/2024 | KDODGE | KDODGE | Interior remodel, commercial, no change of use or occupancy. new furnace and ac units only. (see full review) | | CO Springs DRE | 1993824 |
Mechanical | Original | A | 4/24/2024 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 1993806 |
Electrical | Original | A | 4/24/2024 | BERTHA | BERTHA | Bee walking | | Electrical | 1993763 |
Electrical | Original | D | 4/12/2024 | DANIELG | DANIELG | Provide feeder #2 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1988635 |
Plumbing | Original | N | 4/12/2024 | TCRIPPEN | TCRIPPEN | No plumbing | | Plumbing | 1988605 |
Enumeration | Original | N | 4/12/2024 | BECKYA | BECKYA | | | Enumeration | 1988560 |
Out to Review | Original | / | 4/12/2024 | DANM | DANM | | | Out to Review | 1988547 |
Construction | Original | D | 4/12/2024 | DANM | DANM | Provide architectural floor plan(s) for any framing scope of work and any affected fire rated construction ( JL 4-24-24) reviewed previous comment with contractor at walk through counter. Expanded on the need for architectural plans indicating if new scope of work required the removal or modification of any framing or fire resistive rated assemblies. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1988546 |
Electrical | Original | D | 3/22/2024 | BERTHA | BERTHA | Provide feeder #2 Provide SCA and SCCR for new air conditioning equipment. Service conductor is overloaded. Verify that drawing notes are on all plans.
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1978360 |
Energy | Original | N | 3/22/2024 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 1978318 |
Floodplain | Original | N | 3/22/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6421226005) | | Floodplain | 1978317 |