Falcon Fire (CSFD) | Original | A | 5/8/2024 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | phil.valdez | Falcon Fire (CSFD) | 2000934 |
County Zoning | Original | A | 5/8/2024 | DSDLETKE | DSDLETKE | PCD file no. COM243 has been approved. Per direction of DPW Engineering, Bret Dilts, road impact fees are not applicable due to office designation.
A driveway permit is required and can be applied for at https://epcdevplanreview.com/
Joe Letke Planner II 719-520-7964 | | County Zoning | 2000639 |
Electrical | Original | D | 5/8/2024 | SHELBY | SHELBY | Elevator over current violates 430.6 NEC 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2000369 |
Energy | Original | D | 5/8/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2000370 |
Electronic Plan | Original | / | 5/8/2024 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 2000352 |
Zoning/Planning | Original | A | 5/8/2024 | DSDLETKE | DSDLETKE | PCD file no. COM243 has been approved. Per direction of DPW Engineering, Bret Dilts, road impact fees are not applicable due to office designation.
A driveway permit is required and can be applied for at https://epcdevplanreview.com/
Joe Letke Planner II 719-520-7964 | | Zoning/Planning | 2000249 |
Mechanical | Original | D | 5/7/2024 | TREVORH | TREVORH | Disapprove : Clarify rated shaft for ductwork , this is 3B construction , and if requiring rated shaft then provide details for all plan pages. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2000092 |
Plumbing | Original | A | 5/7/2024 | SHANEN | SHANEN | | | Plumbing | 1999934 |
Construction | Original | A | 5/7/2024 | SHELLEY | SHELLEY | | | Construction | 1999905 |
Enumeration | Original | N | 5/7/2024 | AMY | AMY | | | Enumeration | 1999763 |
Plumbing | Original | / | 5/6/2024 | WEBSITE | WEBSITE | Overtime Authorized for Plumbing by Lisa Peterson | Hammers | Plumbing | 1999077 |
Enumeration | Original | / | 5/6/2024 | WEBSITE | WEBSITE | Overtime Authorized for Enumeration by Lisa Peterson | Hammers | Enumeration | 1999076 |
Electrical | Original | / | 5/6/2024 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by Lisa Peterson | Hammers | Electrical | 1999075 |
Electronic Plan | Original | / | 5/6/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1998739 |
Elevators | Original | D | 5/3/2024 | ERIC | ERIC | Please provide elevator submittals. No review made . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 1998506 |
Submittal 2 | Original | / | 5/3/2024 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 1998312 |
Woodmen Hills Waste Water | Original | N | 5/2/2024 | NELIDA | NELIDA | Not applicable, per email received from Wally Eaves. | | Woodmen Hills Waste Water | 1998061 |
Falcon Fire (CSFD) | Original | D | 4/10/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. (see full review) | phil.valdez | Falcon Fire (CSFD) | 1987246 |
Energy | Original | D | 4/10/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1987229 |
Mechanical | Original | D | 4/10/2024 | TCRIPPEN | TCRIPPEN | Disapproved:Clarify what is in the equipment room ? fan exhaust should have FRD as well need to clarify shaft or chase ? 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1987228 |
Electronic Plan | Original | / | 4/10/2024 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1987198 |
County Zoning | Original | D | 4/9/2024 | DSDRANGEL | DSDRANGEL | COM project must be approved prior to PPRBD sign off. Upload the approved site plan once received. | | County Zoning | 1986460 |
Zoning/Planning | Original | / | 4/9/2024 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1986458 |
Mechanical | Original | / | 4/9/2024 | WEBSITE | WEBSITE | Overtime Authorized for Mechanical by Lisa Peterson | Hammers | Mechanical | 1986257 |
Energy | Original | / | 4/8/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1985850 |
Falcon Highlands Water | Original | D | 4/8/2024 | AMY | AMY | | | Falcon Highlands Water | 1985820 |
Woodmen Hills Waste Water | Original | D | 4/8/2024 | AMY | AMY | | | Woodmen Hills Waste Water | 1985819 |
Plan Coordinator (Main) | Original | D | 4/8/2024 | AMY | AMY | Disapprove all remaining departments to allow plan to be resubmitted. This plan needs to be split out into 3 plan submittals for 3 separate tenant spaces. | | Plan Coordinator (Main) | 1985817 |
Electrical | Original | D | 4/8/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1985253 |
Plumbing | Original | D | 4/8/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1985248 |
Electronic Plan | Original | / | 4/8/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1985247 |
Enumeration | Original | D | 4/8/2024 | AMY | AMY | Proposed to be all one business under 7165. | | Enumeration | 1985240 |
Elevators | Original | D | 4/5/2024 | ERIC | ERIC | Please provide elevator submittals. . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 1985227 |
Construction | Original | D | 4/5/2024 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1985202 |
Electronic Plan | Original | / | 4/5/2024 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 1984900 |
Construction | Original | / | 4/1/2024 | WEBSITE | WEBSITE | Overtime Authorized for Construction by Lisa Peterson | Hammers | Construction | 1982076 |
Enumeration | Original | N | 3/28/2024 | AMY | AMY | | | Enumeration | 1980819 |
Electronic Plan | Original | / | 3/28/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1980801 |
Energy | Original | / | 3/28/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1980770 |
Waste Water Div | Original | / | 3/28/2024 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 1980772 |
Water Division | Original | / | 3/28/2024 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 1980771 |
Floodplain | Original | N | 3/28/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5312114005) | | Floodplain | 1980769 |