Canceled Plans | Original | / | 5/8/2024 | | JANE | Location = Canceled Plans by JANE | | Canceled Plans | 2000727 |
Zoning/Planning | Original | / | 5/8/2024 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2000530 |
Zoning/Planning | Original | / | 5/8/2024 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 2000526 |
- Not Set - | Original | / | 5/8/2024 | | SCANNING | Location = - Not Set - by SCANNING | | - Not Set - | 2000456 |
Plumbing | Original | D | 5/8/2024 | TCRIPPEN | TCRIPPEN | Disapproved see paper plans, and return red lines with next review 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2000376 |
Energy | Original | D | 5/8/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2000377 |
Plumbing (Main) | Original | / | 4/19/2024 | | SCANNING | Location = Plumbing (Main) by SCANNING | | Plumbing (Main) | 1991635 |
Plan Coordinator (Main) | Original | / | 4/19/2024 | | DALEH | Location = Plan Coordinator (Main) by DALEH | | Plan Coordinator (Main) | 1991558 |
Mechanical | Original | D | 4/19/2024 | DALEH | DALEH | Provide a complete set of mechanical plans 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 1991556 |
Mechanical (Main) | Original | / | 4/17/2024 | | SCANNING | Location = Mechanical (Main) by SCANNING | | Mechanical (Main) | 1990157 |
Plan Coordinator (Main) | Original | / | 4/16/2024 | | BERTHA | Location = Plan Coordinator (Main) by BERTHA | | Plan Coordinator (Main) | 1989535 |
Electrical | Original | D | 4/16/2024 | BERTHA | BERTHA | Provide electrical - Change of Occupancy - see Construction review comments. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1989534 |
Electrical (Main) | Original | / | 4/12/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical (Main) | 1988675 |
Electrical (Main) | Original | / | 4/9/2024 | | SCANNING | Location = Electrical (Main) by SCANNING | | Electrical (Main) | 1986864 |
Plan Coordinator (Main) | Original | / | 4/9/2024 | | JUSTINL | Location = Plan Coordinator (Main) by JUSTINL | | Plan Coordinator (Main) | 1986774 |
Construction | Original | D | 4/9/2024 | JUSTINL | JUSTINL | Building contains separated and non-separated occupancies -- See suite 120 history. Provide sum of ratios. Incorrect occupancy load factors used. seating area should be at 1:15 - No fixed seating. Occupancy load will exceed 49, occupancy updated to A-2 from B. Provide life safety plan with increased occupancy load over 49. Change of occupancy requires compliance with IECC C505 or Indicate if any of the exceptions apply on plans. (NO WALK ) 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1986773 |
Construction (Main) | Original | / | 4/9/2024 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Construction (Main) | 1986466 |
Construction (Main) | Original | / | 4/5/2024 | | SCANNING | Location = Construction (Main) by SCANNING | | Construction (Main) | 1985213 |
Plan Coordinator (Main) | Original | / | 4/5/2024 | | BECKYA | Location = Plan Coordinator (Main) by BECKYA | | Plan Coordinator (Main) | 1985069 |
Enumeration | Original | N | 4/5/2024 | BECKYA | BECKYA | | | Enumeration | 1985068 |
Enumeration (Main) | Original | / | 4/5/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Enumeration (Main) | 1985035 |
Energy | Original | / | 4/4/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1984411 |
Floodplain | Original | N | 4/4/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6405215013) | | Floodplain | 1984410 |