Electrical | Original | A | 8/12/2024 | BERTHA | BERTHA | | | Electrical | 2045122 |
Energy | Original | D | 8/12/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2045123 |
Electronic Plan | Original | / | 8/12/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2045083 |
City Engr | Original | D | 8/6/2024 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (#STM-REV24-0485 and 0660) | | City Engr | 2042931 |
CO Springs DRE | Original | D | 8/6/2024 | MOBRIEN | MOBRIEN | Previous comments not addressed. Please upload approved minor modification (DEPN-24-0086) with Land Use Review approval stamp, as well as approved and recorded plat. (see full review) | | CO Springs DRE | 2042915 |
Plumbing | Original | D | 8/6/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2042664 |
CSU Contract Admin. | Original | D | 8/6/2024 | CSUAPPSPRM | CSUAPPSPRM | CWMSF Apprvd - needs development charges paid - jmd | jdemello | CSU Contract Admin. | 2042647 |
Zoning/Planning | Original | / | 8/6/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2042602 |
CSU Water | Original | D | 8/1/2024 | CSUREVIEW | CSUREVIEW | See previous comments. Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Water | 2040977 |
CSU Waste Water | Original | D | 8/1/2024 | CSUREVIEW | CSUREVIEW | See previous comments. Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Waste Water | 2040976 |
| Original | / | 8/1/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2040968 |
Submittal 5 | Original | / | 8/1/2024 | SIERRAC | SIERRAC | Submittal #5 | | Submittal 5 | 2040966 |
City Engr | Original | D | 7/25/2024 | JDAGNILLO | JDAGNILLO | See previous comment - Include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (#STM-REV24-0484 & 0660) | | City Engr | 2037472 |
Electrical | Original | D | 7/22/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2035836 |
Energy | Original | D | 7/22/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2035837 |
Electronic Plan | Original | / | 7/22/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2035450 |
CSU Contract Admin. | Original | D | 7/17/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted. CWMSF requires corrections. We will also require payment of developmnet fees.
AMS | ASweet | CSU Contract Admin. | 2033740 |
CO Springs DRE | Original | D | 7/17/2024 | MOBRIEN | MOBRIEN | Once approved, please upload copy of DEPN-24-0086 with Land Use Review approval stamp, as well as approved and recorded plat. (see full review) | | CO Springs DRE | 2033716 |
Plumbing | Original | D | 7/17/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2033562 |
Mechanical | Original | A | 7/17/2024 | TREVORH | TREVORH | Approved; | | Mechanical | 2033459 |
Zoning/Planning | Original | / | 7/17/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2033389 |
CSU Waste Water | Original | D | 7/17/2024 | CSUREVIEW | CSUREVIEW | See previous comments. DMM | dmakings | CSU Waste Water | 2033319 |
CSU Water | Original | D | 7/17/2024 | CSUREVIEW | CSUREVIEW | See previous comments. DMM | dmakings | CSU Water | 2033318 |
Elevators | Original | A | 7/17/2024 | ERIC | ERIC | Basis of design 2 Otis Gen3 machineroom-less traction elevators with fire rated suspension, No generator, 2019 code
Full sets of elevator submittals are required to be spliced into planset prior to the issuance of elevator permit. | | Elevators | 2033313 |
| Original | / | 7/12/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due- PAID OVER THE PHONE REFERENCE #1848420 RECEIPT #2086199 | | | 2031504 |
Submittal 4 | Original | / | 7/12/2024 | QUINTONW | QUINTONW | Submittal #4 | | Submittal 4 | 2031503 |
CO Springs DRE | Original | D | 6/25/2024 | SSADLER | SSADLER | Minor modification of the development plan is not approved. Once the modification is approved, you can resubmit with the stamped updated development plan. (see full review) | | CO Springs DRE | 2024300 |
Energy | Original | D | 6/25/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2024291 |
Electrical | Original | D | 6/25/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2024290 |
City Engr | Original | D | 6/21/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (#STM-REV24-0484 & 0660) | | City Engr | 2023374 |
CSU Contract Admin. | Original | D | 6/21/2024 | CSUAPPSPRM | CSUAPPSPRM | Same comment as 5/31/24
CWMSF recieved but required corrections,and requires payment of applicable fee.Email sent to customer
JMD | jdemello | CSU Contract Admin. | 2023093 |
Mechanical | Original | D | 6/21/2024 | TREVORH | TREVORH | Disapproved; 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2022888 |
Electronic Plan | Original | / | 6/21/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2022858 |
Electronic Plan | Original | / | 6/20/2024 | TREVORH | TREVORH | In Current Review by TREVORH | | Electronic Plan | 2022713 |
Zoning/Planning | Original | / | 6/20/2024 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2022672 |
CSU Water | Original | D | 6/20/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. SSM | stefanm | CSU Water | 2022665 |
CSU Waste Water | Original | D | 6/20/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. SSM | stefanm | CSU Waste Water | 2022661 |
Construction | Original | A | 6/20/2024 | DANM | DANM | | | Construction | 2022637 |
Plumbing | Original | D | 6/17/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2020193 |
Electronic Plan | Original | / | 6/14/2024 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 2020043 |
Enumeration | Original | A | 6/13/2024 | BRENT | BRENT | | | Enumeration | 2019245 |
Electronic Plan | Original | / | 6/13/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2019224 |
Elevators | Original | D | 6/12/2024 | ERIC | ERIC | Basis of design 2 Otis Gen3 machineroom-less traction elevators with fire rated suspension, No generator, 2019 code Full sets of elevator submittals are required to be spliced into planset prior to the issuance of elevator permit.
See M-118, M-119, P-301, E-118, E-119, E-111 and E-112 . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 2018935 |
| Original | / | 6/12/2024 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due---PAID: RECEIPT #2073969 | | | 2018544 |
Submittal 3 | Original | / | 6/12/2024 | BRIANNAM | BRIANNAM | Submittal #3 | | Submittal 3 | 2018543 |
CSU Contract Admin. | Original | D | 5/31/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate.
CWMSF recieved but required corrections. Email sent to customer.
AMS | ASweet | CSU Contract Admin. | 2013914 |
CO Springs Fire | Original | A | 5/30/2024 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | rpeterson | CO Springs Fire | 2013026 |
CO Springs DRE | Original | D | 5/30/2024 | MOBRIEN | MOBRIEN | Modification to approved development plan is still in review. Please submit approved plans with Land Use Review stamp when complete. (see full review) | | CO Springs DRE | 2012979 |
Energy | Original | D | 5/30/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2012780 |
Electrical | Original | D | 5/30/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2012779 |
Mechanical | Original | D | 5/30/2024 | TREVORH | TREVORH | Disapproved; 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2012766 |
City Engr | Original | D | 5/30/2024 | PMORRIS | PMORRIS | Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) and the Permanent Control Measure (water quality facility) construction plan into the building permit. (ProjectDox #: STM-REV24-0484, STM-REV24-0660) | | City Engr | 2012606 |
Zoning/Planning | Original | / | 5/29/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 2012502 |
Electronic Plan | Original | / | 5/29/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2012408 |
CSU Water | Original | D | 5/29/2024 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
CSU-approved Construction Drawings must be attached to the permit set. Plumbing plans to be reviewed alongside approved Utility Construction Drawings and further comments may be provided. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Water | 2012345 |
CSU Waste Water | Original | D | 5/29/2024 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 2012344 |
Gas/Elec. Utils | Original | A | 5/29/2024 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. CJS | cjsavage | Gas/Elec. Utils | 2012342 |
Construction | Original | D | 5/29/2024 | DANM | DANM | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2012336 |
Plumbing | Original | D | 5/28/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2011818 |
Elevators | Original | D | 5/28/2024 | ERIC | ERIC | Previous review issue not addressed. See A-308 and page 1 of elevator basis of design . 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 2011402 |
Electronic Plan | Original | / | 5/28/2024 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 2011359 |
Enumeration | Original | A | 5/24/2024 | BRENT | BRENT | | | Enumeration | 2011128 |
Electronic Plan | Original | / | 5/24/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2011110 |
Submittal 2 | Original | / | 5/24/2024 | BRIANNAM | BRIANNAM | Submittal #2 | | Submittal 2 | 2010824 |
Energy | Original | D | 5/9/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2000947 |
Mechanical | Original | D | 5/9/2024 | DALEH | DALEH | RAPID RESPONSE 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2000946 |
Electrical | Original | D | 5/7/2024 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1999987 |
City Engr | Original | D | 5/7/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (#STM-REV24-0485) | | City Engr | 1999815 |
Electronic Plan | Original | / | 5/7/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1999652 |
CSU Contract Admin. | Original | D | 5/6/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/fees and to request an estimate.
CWMSF was received, but required a couple of revisions.
AMS | ASweet | CSU Contract Admin. | 1999105 |
CO Springs Fire | Original | D | 5/6/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | rpeterson | CO Springs Fire | 1998914 |
CO Springs Hazmat | Original | N | 5/6/2024 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1998911 |
CO Springs DRE | Original | D | 5/6/2024 | MOBRIEN | MOBRIEN | Per A. Cooper (Land Use Review planner), plans are denied pending approval of landscape plan modifications. (see full review) | | CO Springs DRE | 1998887 |
Zoning/Planning | Original | / | 5/6/2024 | MOBRIEN | MOBRIEN | In Current Review by MOBRIEN | | Zoning/Planning | 1998884 |
Plumbing | Original | D | 5/6/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 1998861 |
Health Dept. | Original | N | 5/6/2024 | HEALTHDEPT | HEALTHDEPT | Not applicable. Per Architect, Kerrie Kannberg, no retail food establishment will be on premise. Dining, bistro, and kitchen areas on plans are areas for potlucks and residential gatherings only. AB | abrannon | Health Dept. | 1998821 |
CSU Waste Water | Original | D | 5/6/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. --------------------------------------------------------------------------------------------------------------------- Provide copy of variance letter for internal sand/oil interceptor. MLW | mlwilliams | CSU Waste Water | 1998787 |
CSU Water | Original | D | 5/6/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan(USP). Call UDS at 719-668-8259 with questions. ------------------------------------------------------------------------------------------------------------------ On Plumbing sheets MEP-101 and P-111, fire service location does not match civil construction drawings. ------------------------------------------------------------------------------------------------------------------ Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. MLW | mlwilliams | CSU Water | 1998783 |
Gas/Elec. Utils | Original | D | 5/6/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. MLW | mlwilliams | Gas/Elec. Utils | 1998763 |
Electronic Plan | Original | / | 5/6/2024 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1998704 |
Elevators | Original | D | 5/6/2024 | ERIC | ERIC | See elevator page # 1 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Elevators | 1998703 |
Construction | Original | D | 5/3/2024 | DANM | DANM | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 1998678 |
Electronic Plan | Original | / | 4/29/2024 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1995738 |
Enumeration | Original | A | 4/25/2024 | BRENT | BRENT | | | Enumeration | 1994610 |
Electronic Plan | Original | / | 4/25/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1994568 |
Energy | Original | / | 4/25/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 1994393 |
Floodplain | Original | N | 4/25/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6417301031) | | Floodplain | 1994391 |