City Engr | Original | D | 11/8/2024 | JDAGNILLO | JDAGNILLO | Please address previous comment - Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2083110 |
EPC Health Dept | Original | D | 11/8/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | EPC Health Dept | 2082982 |
Plumbing | Original | D | 11/8/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2082924 |
CSU Contract Admin. | Original | D | 11/7/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and paid utility receipt for applicable Development Charges/Fees. Contact Customer Contract Administration at 719-668-8111 to request an estimate. JMD | jdemello | CSU Contract Admin. | 2082901 |
CSU Contract Admin. | Original | D | 11/7/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and paid utility receipt for applicable Development Charges/Fees. Contact Customer Contract Administration at 719-668-8111 to request an estimate. JMD | jdemello | CSU Contract Admin. | 2082900 |
Mechanical | Original | A | 11/7/2024 | TREVORH | TREVORH | Approved; | | Mechanical | 2082804 |
CO Springs DRE | Original | D | 11/7/2024 | MAMBUUL | MAMBUUL | Previous comments not addressed. 1. Please upload approved development plans stamped by land use review to permit as well as recorded plat. 2. Need to provide financial assurances for public and private improvements. 3. CDI fees may be due upon release of approval letter by land use review. (see full review) | | CO Springs DRE | 2082790 |
CSU Water | Original | D | 11/7/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Water | 2082787 |
CSU Waste Water | Original | D | 11/7/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2082786 |
Gas/Elec. Utils | Original | D | 11/7/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 2082785 |
Zoning/Planning | Original | / | 11/7/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2082784 |
Construction | Original | D | 11/7/2024 | SHELLEY | SHELLEY | Canopy plans are not allowed to be deferred. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2082779 |
Enumeration | Original | A | 11/7/2024 | AMY | AMY | | | Enumeration | 2082645 |
Electronic Plan | Original | / | 11/7/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2082636 |
Submittal 2 | Original | / | 11/6/2024 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2082470 |
CO Springs Fire | Original | A | 10/1/2024 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | phil.valdez | CO Springs Fire | 2066563 |
Energy | Original | D | 9/26/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2064943 |
Mechanical | Original | D | 9/26/2024 | TREVORH | TREVORH | Disapproved; 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2064942 |
Electrical | Original | D | 9/24/2024 | RICHG | RICHG | Comply with 514.11 (A). Show location and distance from emergency shutoff and dispensers on the electrical site plan
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Customer CT to comply with CSU ELESS
Clearly depict location of transfer switch.
• Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
• Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
• Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
• The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2063955 |
Health Dept. | Original | D | 9/20/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. TG | tguerrero | Health Dept. | 2062935 |
CO Springs Hazmat | Original | A | 9/19/2024 | CSFIRE | CSFIRE | Defered Submittal for UST Fuel Tanks and CO2. You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | CO Springs Hazmat | 2062565 |
City Engr | Original | D | 9/19/2024 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2062473 |
Electronic Plan | Original | / | 9/18/2024 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 2061695 |
Electronic Plan | Original | / | 9/18/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2061694 |
CO Springs DRE | Original | D | 9/17/2024 | MAMBUUL | MAMBUUL | Need to provide approved development plans stamped by land use review, as well as recorded plat. (see full review) | | CO Springs DRE | 2061576 |
Plumbing | Original | D | 9/17/2024 | SHANEN | SHANEN | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2061498 |
Gas/Elec. Utils | Original | D | 9/17/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | Gas/Elec. Utils | 2061454 |
CSU Water | Original | D | 9/17/2024 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Water | 2061451 |
CSU Waste Water | Original | D | 9/17/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 2061448 |
Zoning/Planning | Original | / | 9/17/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2061415 |
CSU Contract Admin. | Original | D | 9/17/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees.
Please contact Utilities Development Services at 719-668-8111 or cca@csu.org for questions, assistance or to request an estimate.
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf
BS | bschifferstein | CSU Contract Admin. | 2061384 |
Elevators | Original | N | 9/17/2024 | ERIC | ERIC | No conveyance | | Elevators | 2061327 |
Construction | Original | D | 9/17/2024 | SHELLEY | SHELLEY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2061325 |
Electronic Plan | Original | / | 9/17/2024 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2061228 |
Enumeration | Original | A | 9/13/2024 | AMY | AMY | 1 PLAN 3 PERMITS | | Enumeration | 2059701 |
Electronic Plan | Original | / | 9/12/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2059656 |
Energy | Original | / | 9/12/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2059440 |
Floodplain | Original | N | 9/12/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6427111072) | | Floodplain | 2059439 |