CO Springs Hazmat | Original | D | 11/5/2024 | CSFIRE | CSFIRE | See Fire Comments | phil.valdez | CO Springs Hazmat | 2081682 |
CO Springs Fire | Original | D | 11/5/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2081681 |
Energy | Original | D | 11/5/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2081518 |
Electrical | Original | D | 11/5/2024 | BERTHA | BERTHA | Provide conduit/conductor size, type (CU or AL) and quantity beginning at the utility transformer to include all conductors in the scope of work.
Provide feeder schedule on one-line sheet.
Provide fault current information for refrigeration / air conditioning equipment in the Available Short Circuit Calculations table.
Provide rated input current for VFD's
Comply with 430.122
Provide MDP panel schedule
Complete re-review required. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 2081517 |
Electronic Plan | Original | / | 11/5/2024 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2081516 |
Electrical | Original | / | 11/1/2024 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by Aaron Karraker | AKarraker | Electrical | 2080346 |
Plumbing | Original | / | 10/31/2024 | ROGER | ROGER | Overtime approved for Plumbing by Danny Mika w/ Equity Group | | Plumbing | 2079802 |
Mechanical | Original | / | 10/31/2024 | ROGER | ROGER | Overtime approved for Mechanical by Danny Mika w/ Equity Group | | Mechanical | 2079801 |
Electrical | Original | / | 10/31/2024 | ROGER | ROGER | Overtime approved for Electrical by Danny Mika w/ Equity Group | | Electrical | 2079800 |
Construction | Original | / | 10/31/2024 | ROGER | ROGER | Overtime approved for Construction by Danny Mika w/ Equity Group | | Construction | 2079799 |
CSU Contract Admin. | Original | A | 10/31/2024 | CSUAPPSPRM | CSUAPPSPRM | Electric design fees paid. BS | bschifferstein | CSU Contract Admin. | 2079748 |
EPC Health Dept | Original | N | 10/29/2024 | HEALTHDEPT | HEALTHDEPT | Not applicable. AB | abrannon | EPC Health Dept | 2078710 |
CO Springs DRE | Original | D | 10/28/2024 | MAMBUUL | MAMBUUL | Please upload approved development plan set stamped by land use review to permit as well as recorded plat. (see full review) | | CO Springs DRE | 2078228 |
Plumbing | Original | D | 10/28/2024 | SHANEN | SHANEN | No plumbing plans provided. Construction review comments must be addressed. F-1 occupancy requires compliance with section 403. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Plumbing | 2078112 |
CSU Contract Admin. | Original | D | 10/28/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires payment of $398.00 Electric Design Fee. Please contact our office at 719-668-8111 for additional information or to make payment. BS | bschifferstein | CSU Contract Admin. | 2078000 |
City Engr | Original | N | 10/25/2024 | JDAGNILLO | JDAGNILLO | | | City Engr | 2077733 |
Zoning/Planning | Original | / | 10/24/2024 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2077180 |
Mechanical | Original | D | 10/24/2024 | TREVORH | TREVORH | Disapproved; Need to see Architectural plans for the lift station. 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Mechanical | 2077090 |
CSU Water | Original | D | 10/24/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Water | 2077014 |
CSU Waste Water | Original | D | 10/24/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | CSU Waste Water | 2077013 |
Gas/Elec. Utils | Original | D | 10/24/2024 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSM | stefanm | Gas/Elec. Utils | 2077012 |
Construction | Original | D | 10/24/2024 | BPHILLIPS | BPHILLIPS | Provide architectural drawings for lift station as well. Provide separate code study form for electrical building. TRUSSES PENDING 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Construction | 2076992 |
Enumeration | Original | D | 10/24/2024 | AMY | AMY | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Enumeration | 2076970 |
Electronic Plan | Original | / | 10/24/2024 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2076868 |
Enumeration | Original | A | 10/22/2024 | AMY | AMY | Once the residential subdivision is platted and the access road is built out the address to the lift station will need to change. See link here for information needed to do so: https://www.pprbd.org/File/Resources/Downloads/Addressing/Request%20for%20change%20of%20address%20ACCESS.pdf | | Enumeration | 2075997 |
Electronic Plan | Original | / | 10/22/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2075717 |
Elevators | Original | N | 10/21/2024 | ERIC | ERIC | No conveyance | | Elevators | 2075448 |
Energy | Original | / | 10/21/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2075318 |
Floodplain | Original | N | 10/21/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5400000300) | | Floodplain | 2075317 |