CO Springs DRE | Original | A | 11/20/2024 | SSADLER | SSADLER | Interior remodel only. No change in footprint, No change in parking. No change in occupancy. (see full review) | | CO Springs DRE | 2087482 |
Zoning/Planning | Original | / | 11/15/2024 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2085915 |
CSU Water | Original | N | 11/15/2024 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSM | stefanm | CSU Water | 2085824 |
CSU Waste Water | Original | N | 11/15/2024 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSM | stefanm | CSU Waste Water | 2085823 |
Energy | Original | D | 11/15/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2085819 |
Plumbing | Original | D | 11/15/2024 | SHANEN | SHANEN | All condensate piping shall be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2085818 |
Mechanical | Original | D | 11/15/2024 | TREVORH | TREVORH | Disapproved ; need to see condensate drain * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2085817 |
Construction | Original | D | 11/15/2024 | DANM | DANM | Due to weight of new mechanical units - provide structural engineer letter or drawing * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2085794 |
Electrical | Original | D | 11/15/2024 | RICHG | RICHG | MDP amps dont match load summary.
MDP does not show M2 panel fed from it.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2085785 |
Enumeration | Original | N | 11/14/2024 | AMY | AMY | | | Enumeration | 2085407 |
Electronic Plan | Original | / | 11/14/2024 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2085405 |
Energy | Original | / | 11/14/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2085334 |
Floodplain | Original | N | 11/14/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6425007001) | | Floodplain | 2085333 |