Mechanical | Original | D | 3/5/2025 | DALEH | DALEH | Some comments did not get addressed Please reference last disapproval for comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2127239 |
Energy | Original | D | 3/5/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2127240 |
Electrical | Original | D | 3/4/2025 | DANIELG | DANIELG | Pending elevator approval.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2126865 |
Plumbing | Original | D | 3/4/2025 | SHANEN | SHANEN | PS101: Place note L elsewhere in the plumbing plans as this sheet will be reviewed for reference only and this is required information. Note PS10: Shipping containers shown as proposed on the referenced civil plans and will not be reviewed with this submittal without corresponding USP. PL2.07: Provide required CSU variance letter for the indoor grease interceptor. Contact Robert Bowren at 719-668-1735 or fog@csu.org. CSU indoor grease interceptor variance letter will regulate which fixtures are required to discharge through the grease interceptor. Note PL01: Show piping from SP-2 to the noted floor sink. P-504: Elevator sump does not comply with section 301.6. Remove all references to a direct waste connection for the elevator sump. P-701: RD/ORD1 must show compliance with section 1102.6. Referenced standards not provided on manufacturer website. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2126712 |
Elevators | Original | D | 3/3/2025 | ROBERTV | ROBERTV | See pages: P-504, MH2.07, EP2.07. Note: Could not save any markups or stamps on Architectual Pages.
RBD Note: Schindler Machine Room-Less Traction Elevator w/ Fire Rated Suspension Means, no Generator. A17.1 - 2019, RBC 2023 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2126678 |
City Engr | Original | A | 2/27/2025 | HVO | HVO | EDRD has no additional comments. | | City Engr | 2125685 |
CO Springs Fire | Original | A | 2/27/2025 | CSFIRE | CSFIRE | Site Safety Plan per IFC 3301.1 required within 45 days of permit issuance.
You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2125463 |
CSU Waste Water | Original | D | 2/27/2025 | CSUREVIEW | CSUREVIEW | A variance is required for this unit as it is located too far from the existing grease interceptor. Contact CSU Industrial Pretreatment representative Bob Bowren via email at fog@csu.org to request a variance for this condition. Provide a copy of the Variance Letter in the building plan set. Upload the Approval letter. mjg | mgackle | CSU Waste Water | 2125379 |
CSU Water | Original | D | 2/27/2025 | CSUREVIEW | CSUREVIEW | Verify the water service size and type after approval of the Commercial Water meter Sizing form. mjg | mgackle | CSU Water | 2125378 |
Construction | Original | D | 2/26/2025 | JUSTINL | JUSTINL | Still need to address 1 hour ratings at supporting construction in rated exterior wall due to proximity to imaginary lot line. Still need to address horizontal assembly at top of elevator shaft fire barrier. Test report for Class A fire rating for roofing membrane were not provided when plans were resubmitted. AM&M on file. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2125368 |
Electronic Plan | Original | / | 2/25/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2124732 |
Enumeration | Original | A | 2/25/2025 | BRENT | BRENT | | | Enumeration | 2124723 |
Electronic Plan | Original | / | 2/25/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2124709 |
| Original | / | 2/25/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2124614 |
| Original | / | 2/25/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2124612 |
Submittal 3 | Original | / | 2/25/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2124611 |
CSU Contract Admin. | Original | N | 2/18/2025 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees due this plan set.BS | bschifferstein | CSU Contract Admin. | 2121617 |
EPC Health Dept | Original | A | 2/11/2025 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted.
Construction activity permit PT#1572 is valid from 01/23/2025 - 07/23/2025. To continue any earthmoving operations after 07/23/2025, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2119704 |
EPC Health Dept | Original | / | 2/11/2025 | HEALTHDEPT | HEALTHDEPT | | brothrock | EPC Health Dept | 2119699 |
Energy | Original | D | 2/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2119689 |
Mechanical | Original | D | 2/11/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2119688 |
Electrical | Original | D | 2/11/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2119573 |
Plumbing | Original | D | 2/11/2025 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2119464 |
Elevators | Original | D | 2/10/2025 | ROBERTV | ROBERTV | See pages: A5.07, S5.06, MP2.07, P-504, P-702, EP2.07, EL2.17. Note: Could not save markups on Architectural Drawings
RBD Note: Schindler Machine Room-Less Traction Elevator w/ Fire Rated Suspension Means, no Generator. A17.1 - 2019, RBC 2023 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2119320 |
CO Springs DRE | Original | A | 2/10/2025 | RSEVIGNY | RSEVIGNY | In general conformance with the approved Development Plan - Gabe Sevigny | | CO Springs DRE | 2118963 |
EPC Health Dept | Original | D | 2/10/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB
Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2118852 |
CO Springs Fire | Original | D | 2/5/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2117534 |
Zoning/Planning | Original | / | 2/4/2025 | RSEVIGNY | RSEVIGNY | In Current Review by RSEVIGNY | | Zoning/Planning | 2117080 |
CSU Contract Admin. | Original | D | 2/4/2025 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) under review. Paid utility receipt for applicable Development Charges/Fees required. Contact Customer Contract Administration at 719-668-8111 to request an estimate. BS | bschifferstein | CSU Contract Admin. | 2116920 |
Zoning/Planning | Original | / | 2/4/2025 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2116817 |
City Engr | Original | D | 2/4/2025 | JDAGNILLO | JDAGNILLO | Please address previous comment - Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2116761 |
CSU Water | Original | D | 2/4/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Water | 2116728 |
CSU Waste Water | Original | D | 2/4/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set.
Contact CSU Industrial Pretreatment representative Bob Bowren via email at fog@csu.org to determine if a variance for an interior grease trap is applicable. If applicable, provide a copy of the Variance letter in the building plan set. NOTE: The variance request form is attached, per instructions on the form it must be submitted to FOG@csu.org for review and then the variance approval letter must be attached to the permit set.
Contact Utilities Development Services at 719-668-8259 with any questions. CJS | cjsavage | CSU Waste Water | 2116727 |
Construction | Original | D | 2/4/2025 | SHELLEY | SHELLEY | See code study form, architectural sheets and testing reports. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2116636 |
CO Springs Hazmat | Original | A | 2/3/2025 | CSFIRE | CSFIRE | This will be a defered Submittal through Acelle - DFM-C-HM-25-0002You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | CO Springs Hazmat | 2116537 |
Electronic Plan | Original | / | 1/29/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2114930 |
Enumeration | Original | D | 1/27/2025 | BRENT | BRENT | PPRBD wrecking permits have not been issued. Enumerations approval pending issuance of wrecking permits. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2114162 |
Electronic Plan | Original | / | 1/27/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2114158 |
Submittal 2 | Original | / | 1/27/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2114151 |
Energy | Original | D | 12/30/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2103329 |
Mechanical | Original | D | 12/30/2024 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2103328 |
Electronic Plan | Original | / | 12/30/2024 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2103156 |
CO Springs DRE | Original | D | 12/26/2024 | KSCHOTT | KSCHOTT | Area "R" elevations from architectural drawings for new gift shop does not match Pages 13 and 14 of the approved amended DP. Please confirm with Allison Stocker at Land Use Review that these new elevations do not need further modification to the DP (allison.stocker@coloradosprings.gov). Informational: no further FAs or landscaping per the DP approval letter kerri.schott@coloradosprings.gov | | CO Springs DRE | 2102453 |
CSU Contract Admin. | Original | D | 12/23/2024 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. JMD | jdemello | CSU Contract Admin. | 2102099 |
CO Springs Fire | Original | D | 12/20/2024 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2101513 |
CO Springs Hazmat | Original | D | 12/20/2024 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2101512 |
EPC Health Dept | Original | D | 12/20/2024 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB
Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | EPC Health Dept | 2101382 |
Electrical | Original | D | 12/20/2024 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2101340 |
Electronic Plan | Original | / | 12/20/2024 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2101294 |
Zoning/Planning | Original | / | 12/20/2024 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 2101244 |
City Engr | Original | D | 12/19/2024 | HVO | HVO | Please see previous comment- include a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan, and a copy of the approved Stormwater Enterprise approved Permanent Control Measures in the electronic building permit set | | City Engr | 2101229 |
Plumbing | Original | D | 12/19/2024 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2101152 |
Elevators | Original | D | 12/19/2024 | ERIC | ERIC | Please provide Lift and Elevator submittals. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2101136 |
CSU Water | Original | D | 12/19/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Water | 2101127 |
CSU Waste Water | Original | D | 12/19/2024 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. mjg | mgackle | CSU Waste Water | 2101125 |
Gas/Elec. Utils | Original | A | 12/19/2024 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 2101124 |
Construction | Original | D | 12/19/2024 | JUSTINL | JUSTINL | Code study, architectural, structural, fire rated construction, supporting documentation deficiencies. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2101087 |
Energy | Original | / | 12/18/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2100252 |
Electronic Plan | Original | / | 12/11/2024 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2097843 |
Enumeration | Original | D | 12/11/2024 | BRENT | BRENT | Wrecking permits for the Lettuce Sales building and the Stroller Hut must be issued prior to Enumerations approval. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2097837 |
Electronic Plan | Original | / | 12/11/2024 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2097818 |
Energy | Original | / | 12/10/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2096807 |
Floodplain | Original | N | 12/10/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7500000272) | | Floodplain | 2096806 |