CO Springs DRE | Original | D | 3/6/2025 | SSADLER | SSADLER | Previous comments not addressed. Upload the modified development plan. Upload the final recorded plat. All private assurances must be posted prior to building permit release. PLDO/CDI fees must be paid prior to building permit release. | | CO Springs DRE | 2127669 |
City Engr | Original | D | 3/5/2025 | JDAGNILLO | JDAGNILLO | Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (Project Dox #STM-REV24-1275 & 1277) | | City Engr | 2127329 |
EPC Health Dept | Original | D | 3/5/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. TG Sequence 197093 | tguerrero | EPC Health Dept | 2127287 |
Zoning/Planning | Original | / | 3/4/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2127036 |
CSU Contract Admin. | Original | D | 3/4/2025 | CSUAPPSPRM | CSUAPPSPRM | Same comment as previously noted: Requires approved Commercial Water Meter Sizing Form (CWMSF) and paid utility receipt for applicable Development Charges/Fees. Contact Customer Contract Administration at 719-668-8111 to request an estimate.
CWMSF available at: https://www.csu.org/extrx/util_dev_svcs/svc_standards/water/chapter/wp_8.pdf
BS | bschifferstein | CSU Contract Admin. | 2126933 |
CSU Water | Original | D | 3/4/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. DMM | dmakings | CSU Water | 2126919 |
Gas/Elec. Utils | Original | A | 3/4/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. DMM | dmakings | Gas/Elec. Utils | 2126918 |
CSU Waste Water | Original | D | 3/4/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2126917 |
Construction | Original | D | 3/4/2025 | DOUGC | DOUGC | Rated assemblies // IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2126910 |
Electronic Plan | Original | / | 3/4/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2126795 |
Plumbing | Original | D | 2/27/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All gas piping related items shall be on the mechanical plans.Remove all references to gas piping from the plumbing plans. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Provide gpm and/or square footage served by each component of the roof drainage system. Calculations not provided on referenced sheet A3.07. Clarify WD. WB riser diagram does not comply with section 406.2. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Provide required water pipe size analysis data on the plumbing plans per PPRBD plumbing plan review requirements. Schedule only the plumbing fixtures that apply to this building. Provide a piping materials insulation schedule. All components within the water distribution system must show compliance with section 605. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2125528 |
Enumeration | Original | D | 2/24/2025 | BECKYA | BECKYA | Wrecking permits will need to be issued for existing structures prior to Enumerations approval of any plans submitted for this development. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2124277 |
Submittal 2 | Original | / | 2/24/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2124086 |
Energy | Original | D | 1/23/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2112087 |
Electrical | Original | D | 1/23/2025 | BERTHA | BERTHA | Provide all conductor size, type and quantity.
Provide feeder schedule for all feeders on the one-line sheet - unit panels feeders
Provide approval for meters/cts located indoors - Comply with Colorado Springs Utilities Electric Line Extension Service Standards
Provide model # for breakers in series rated combinations.
Pending approval in Elevators - see Elevator review comments
Pending approval in Enumerations - see Enumerations review comments
STATE REQUIREMENTS FOR MULTI-FAMILY (R2) Starting July 29, 2024, the State of Colorado will require new multi-family (R2 occupancy) projects to have a certain number of electric vehicle spaces based on the number of parking spots provided. The amount of required electric vehicle spaces is determine by the Model Electric Ready and Solar Ready Code that can be accessed through the Colorado Energy Office within the Energy Policy section at https://energyoffice.colorado.gov/building-energy-codes-toolkit.
Please see https://www.pprbd.org/File/ByAlias/ElectricalReview for an example * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2112086 |
Mechanical | Original | D | 1/15/2025 | TCRIPPEN | TCRIPPEN | Disapproved : condensate isometrics with sizes and locations. See section 1109 Through 1110 of the 21 IMC for Refrigerant pipe installation locations and penetrations. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2108890 |
Plumbing | Original | D | 1/14/2025 | SHANEN | SHANEN | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2108165 |
CO Springs Fire | Original | D | 1/14/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2108142 |
CO Springs Hazmat | Original | N | 1/14/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2108141 |
Electronic Plan | Original | / | 1/14/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2108078 |
Elevators | Original | D | 1/13/2025 | ROBERTV | ROBERTV | See Pages A1.02, A1.39, A5.04, M2.04, M9.01, P9.01, E9.01 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2108071 |
CO Springs DRE | Original | D | 1/7/2025 | SSADLER | SSADLER | Upload the final recorded plat. All financial assurances need to be posted prior to building permit release. PLDO fees are due prior to building permit release. | | CO Springs DRE | 2105351 |
City Engr | Original | D | 1/6/2025 | JDAGNILLO | JDAGNILLO | Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. (Project Dox #STM-REV24-1275 & 1277) | | City Engr | 2105269 |
CSU Contract Admin. | Original | D | 1/6/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2105199 |
CSU Water | Original | D | 1/6/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.MDA | malcuran | CSU Water | 2104901 |
CSU Waste Water | Original | D | 1/6/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | CSU Waste Water | 2104900 |
Gas/Elec. Utils | Original | D | 1/6/2025 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | Gas/Elec. Utils | 2104899 |
Zoning/Planning | Original | / | 1/6/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2104791 |
EPC Health Dept | Original | D | 1/3/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2104780 |
Construction | Original | D | 1/3/2025 | DOUGC | DOUGC | Rated Assemblies // Accessibility * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2104764 |
Energy | Original | / | 12/31/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2103918 |
Electronic Plan | Original | / | 12/23/2024 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2102075 |
Enumeration | Original | D | 12/18/2024 | BECKYA | BECKYA | 1. Provide proper Accessibility Site plan, see plan for comment. 2. Page A1.01 - Show addressing for the entire development and add the street name. 3. Enumerations will not approve any plans for this development until the Final Plat has been recorded and sent to us for our records. Once recorded, okay to email Becky Allen a copy of the recorded plat (beckya@pprbd.org) . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2100634 |
Electronic Plan | Original | / | 12/18/2024 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2100354 |
Energy | Original | / | 12/18/2024 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2100189 |
Floodplain | Original | N | 12/18/2024 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7413410030) | | Floodplain | 2100188 |